08/11/94 Fraser/DSL Well Evaluation®MAS, DEAN i&HOSKINS INC. ENGINEERING CONSULTANTS No. 6 Sunset Plaza • Kalispell. Montana 59901 • (406) 752-5246 • FAX (406) 752-5230 August 11, 1994 John Wilson City of Kalispell P.O. Box 1997 Kalispell, MT 59903-1997 RE: DSL - Well Evaluation Dear John: We have acquired what appears to be the available information on the subject well. Our review and recommendations follow the WQB circular for groundwater sources. Quality Water quality of the artisan aquifer is excellent. Notes and data are available to confirm the quality. Tests should be conducted prior to finalizing decisions. Location Land uses in the area surrounding the well are agricultural and should not impact the water quality. Clear zone easements should be obtained for the well as a well head protection zone. Yield and Drawdown Tests �2i l,��E d ry,,,Ktcrl 1 Z Well Construction A 13 hour test was conducted, apparently by the driller, Biggs Drilling. No detailed record is available. The rate recorded is 3000 gallons per minute. Detailed test pumping will be necessary for verification of hydrological characteristics. Testing at 3000 GPM would allow production at 2000 gallons per minute. There are no notes on grouting of the surface pipe. This would be required for well protection. Casing is 20" to 200 feet and the 16" to 400 feet. There are no indicators of the seal. A television inspection should reveal the method of sealing. If there is no seal, one may have to be installed or a deviation received from the WQB. OFFICES IN GREAT FALLS, BOZEMAN, KALISPELL AND SPOKANE John Wilson 8-11-94 Page 2 Casing wall thickness meets the standards. The lower casing is perforated, 12 perforations per foot, each 3/81' x 2 1/2111±. Total inlet area is 8.44 sq. ft. Allowable flow at 0.1 feet per second inlet velocity is etc 379 gallons. The inlet velocity at 3000 gallons per minute is 0.79 feet per second. Velocities this high in moderate to hard water 1462 t�308­ may cause mineral encrustation in the openings. Before requesting a deviation from 314e the standards for the increased velocity, the -7 35-f S1 12 76 I e should be T. V ' a to determine the perforations condition. Permitting The water right is to the state for irrigation on 620 acres. An application to transfer, change the place of use, change the period of use and change the use would be necessary. Review by DNRC would be similar to new application. Recommendations The easiest information to obtain is yield and drawdown data. If the City wishes to pursue acquisition, the well should be test pumped. The existing pump may be used but a meter will be necessary to determine flow. An access point in the pumped well and any nearby well must be installed to allow close monitoring of pumping levels. In the fall we recommend the pump be removed and the well televised. At the same time, the excavation occurs to determine the presence or not of surface grouting. If the well is not grouted, a deviation would be necessary. if the transition between the casing is not sealed it would require sealing or a deviation. Summary The well has an oral history of good production. Televising the well may document deficiencies in construction which may not be correctable. The major problems are the inlet velocities and sealing. John Wilson 8-11-94 Page 3 The well is approximately 7600 feet from the existing 12" water main at Grandview and US 93. An extension will be required to connect to the well, minimum diameter would be 12" but to provide flows from the elevated tank headloss may be too high. For planning, we recommend a 16" main. Hydraulic analysis may indicate a 14" main would be adequate. Our experience indicates the City approved, spend a large sum of obstacles which are insurmountable MWF: mj K94-28-9 a:wilson.ltr could work on having this well money and eventually discover Very truly yours, • DEAN & HOSKINS, IN flIchael -W. Fraser Item 1. 2. 3. 4. 5. 6. 7. l "' • I l 10 + M • , • • Estimated Unit Description Quan/Unit Price Amount Install Meter for Test Pumping Lump Sum $ 2,000.00 Test Pumping & Monitoring (Labor Only) 48 Hrs. $ 90.00 4,320.00 Pump 24 Hrs. 125.00 3,000.00 Television Inspection 400 L.F. 15.00 6,000.00 Water Main 161° PVC 7600 L.F. 40.00 304,000.00 Connection to Existing 1 L.F. 2,500.00 2,500.00 Crossing Grandview 100 L.F. 250.00 25,000.00 /�ar�ufi.�� .fib®r7i�✓'G Gvsrs Cst�r vrU�ltiauvc/ �cr� ��s�i�s�Y X<6K) °* .F.,,cJu�aaUEF�,�Ea FF�'S �.�s/�;N �F- CorUST,evGTtas� ��S�EG%icvJ � CA2.2Ec-T�riE �ocE,� v�.S .�3`' Gr>��-r- tF5 �i�i�G� cg ?iv�tJS 5 �•flv/J �iT<lia� .� fCo ' �.gr�ivs LvicuNG To croc Y ® 79(2 &At-r C SrTTE 15 Ai�;e Y . d�T� •� sr'ov� aup2 SYSTEM. August 11, 1994 L.®D5E C.UY[/! �DL, '�t� G�us7.�v'GTiA'tJ e_ P2a1.�4��4