Loading...
Addendum 1, 2021-07-01_Police Search Building_Narrative__and_Drawings_Add A Addendum A 1 CITY OF KALISPELL POLICE SEARCH BUILDING KALISPELL, MONTANA ADDENDUM A Issued: 7/2/2021 JACKOLA ENGINEERING & ARCHITECTURE, P.C. P.O. BOX 1134 KALISPELL, MONTANA 59903 406.755.3208 voice 406.755.3218 fax Project No. 200204 Addendum A 2 Permit Drawings Dated April 1, 2021. This Addendum constitutes one part of the Contract Documents and shall be incorporated by reference in both the Contractor’s Bid and the Construction Contract. Where provisions of the following differ from those of the original Contract Documents, this Addendum shall govern and take precedence: FRONT END DOCUMENTS Item 1: 00100 – 2 INVITATION FOR BIDS a. Replace number of days that "No bid shall be withdrawn after the opening of bids for a period of sixty (60) days" to thirty (30) days. Item 2: 00300 – 1 BID CONDITIONS a. Replace number of days that "Bid will remain subject to acceptance for sixty (60) days after Bid opening" to thirty (30) days. DRAWINGS Item 1: Sheet C0.10 – EXISTING SITE SURVEY AND DEMO PLAN a. Update demo area. Item 2: Sheet C1.10 – COMBINED SITE AND UTILITY PLAN a. Update keynotes. b. Change catch basin inverts. c. Remove downspout connection to storm drain. d. Add INSERTA TEE connection to storm drain per COK. Item 3: Sheet C1.30 – SITE GRADING PLAN a. Adjust grading at south and west side of building. b. Add concrete valley to south. Item 4: Sheet C2.00 – GENERAL NOTES AND DETAILS a. Added details 1 and 4. b. Updated details 5, 6 and 7. Item 5: Sheet P1.00 – UNDERFLOOR PLUMBING PLAN a. Mop sink (MS-1) routed to sand oil separator and new floor cleanout added for mop sink in mechanical room. b. Trap primer supply lines added to all floor drains. c. Updated keynotes. Item 6: Sheet P1.10 – LEVEL 1 PLUMBING SUPPLY PLAN a. Mechanical trap primer valve added in mechanical ro om. b. Added keynote 6. Item 7: Sheet P7.00 – PLUMBING DETAILS a. Added details 1 and 11. Item 8: Sheet P8.00 – PLUMBING SCHEDULES a. Updated EWS-1 model number. Addendum A 3 b. Changed floor drain FD-1. Item 9: Sheet E1.10 – LEVEL 1 LIGHTING PLAN a. Changed “E2” exit sign + egress lamp combo to match exit sign “E1” with no egress lamps, in mechanical room. b. Corrected mislabeled “L1” battery backup to “L1E” in mechanical room. c. Corrected north “WP2” exterior fixture symbol to be bold to match other fixture and schedule indicating egress fixture. Item 10: Sheet E2.10 – LEVEL 1 POWER AND SYSTEMS PLAN a. Clarified keynote 5 scope of work associated with security camera install. b. Identified Hand-Off-Auto location. c. Shown mechanical equipment to be controlled by H.O.A. for reference. d. Included keynotes and associated power/conduit for equipment to further define scope of work. Item 11: Sheet E2.20 – LEVEL 2 POWER AND SYSTEMS PLAN a. Removed EF-1 homerun, as it is now shown from H.O.A. switch location. b. Added keynote for equipment coordination and material to reference. Item 12: Sheet E7.00 – ELECTRICAL DETAILS a. Included Hand-Off-Auto detail. Item 13: Sheet E8.00 – ELECTRICAL SCHEDULES a. Removed “E2” fixture from basis of design lighting fixture schedule. b. Changed Circuit P1-16 to include H.O.A. verbiage. Added Spare to unidentified P1-14 location. SPECIFICATIONS Item 1: Sectional Doors – 08 3613.2.02.B a. Door Panels: Steel construction; outer steel sheet of 27 gage, 0.016 inch minimum thickness, flush profile; inner steel sheet of 28 gage, 0.015 inch minimum thickness, flat profile; core reinforcement 1-3/4 inch sheet steel roll formed to channel shape, rabbeted weather joints at meeting rails; polyurethane insulation. Item 2: Sectional Doors – 08 3613.2.04.E.1.a a. Liftmaster H51L5 (Commercial use). 4. 3. 2. 1. GENERAL CONDITIONS GENERAL NOTES 1. CONTRACTOR TO REVIEW AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO COMMENCING WORK. ANY CONDITIONS NOT INDICATED ON CONTRACT DOCUMENTS ARE TO BE REPORTED TO THE ARCHITECT PRIOR TO BEGINNING WORK. 2. CONTRACTOR TO CONTACT LOCAL UTILITIES, IF NECESSARY, SUBMIT ALL APPLICABLE PERMIT DOCUMENTS, QUALIFICATIONS, ETC., AND BE RESPONSIBLE FOR ALL FEES ASSOCIATED WITH PERMITS, UTILITY EXTENSIONS, TAP-INS, ETC. 3. THE CONTRACTOR SHALL REMOVE ALL DEBRIS AS A RESULT OF THIS PROJECT. 4. THE CONTRACTOR SHALL SCHEDULE HIS WORK AND MATERIAL AND EQUIPMENT DELIVERIES SO AS NOT TO INTERFERE WITH THE DAILY OPERATIONS OF THE REMAINDER OF THE FACILITY. 5. THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, EQUIPMENT, FIXTURES, ETC. FROM DAMAGE DURING THE COURSE OF CONSTRUCTION. 6. ALL SURFACES AND/OR FINISHES DAMAGED AS A RESULT OF AND ADJACENT TO THE WORK SHALL BE REPAIRED AND FINISHED TO THEIR ORIGINAL CONDITION. 7. EACH SUBCONTRACTOR IS RESPONSIBLE TO COORDINATE AND SCHEDULE HIS WORK WITH THE GENERAL CONTRACTOR AND ALL OTHER SUBCONTRACTORS WHOSE WORK WILL BE AFFECTED. 8. USE DETAILS MARKED 'TYPICAL' (TYP) WHEREVER APPLICABLE. 9. ALL ITEMS REQUIRED BY THE DRAWINGS AND SPECIFICATIONS SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY PERSONS SKILLED IN THEIR RESPECTIVE TRADE AND WHO NORMALLY PARTICIPATE IN THE WORK OF THAT TRADE. 10. WORDS WHICH HAVE WELL KNOWN TECHNICAL OR TRADE MEANINGS ARE USED IN THE DRAWINGS AND SPECIFICATIONS IN ACCORDANCE WITH SUCH RECOGNIZED MEANINGS. 11. WITHIN THE DRAWINGS AND RELATED SPECIFICATIONS THERE SHALL BE THE FOLLOWING PRECEDENCE: A) ADDENDA OR MODIFICATIONS TO THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE OVER THE ORIGINAL, WHEN ISSUED BY THE ARCHITECT. B) SPECIFICATIONS SHALL TAKE PRECEDENCE OVER DRAWINGS. C) WITHIN THE DRAWINGS THE LARGER SCALE TAKES PRECEDENCE OVER THE SMALLER, FIGURED DIMENSIONS OVER SCALED AND NOTED MATERIALS OVER GRAPHIC INDICATIONS. 12. THE ARCHITECT OR ENGINEER SHALL BE IN THE FIRST INSTANCE THE SOLE INTERPRETER OF THE DRAWINGS AND SPECIFICATIONS WITH REGARD TO THEIR MEANING OR INTENT. 13. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES AND PROCEDURES. 14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ASPECTS OF SAFETY DURING BUILDING CONSTRUCTION. THE GENERAL CONTRACTOR IS TO GUARANTEE ALL WORK INCLUDING WORK DONE BY SUBCONTRACTORS FOR A PERIOD COMMENCING WITH THE SUBSTANTIAL COMPLETION OF THE CONTRACT. ALL GUARANTEES/WARANTIES BEGIN AT SUBSTATIAL COMPLETION AND EXTEND FOR THE IDENTIFIED DURATION FROM FINAL ACCEPTANCE. BUILDING 1 YEAR, ROOF 2 YEARS ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL GOV- ERNING CODES, ORDINANCES AND AUTHORITIES HAVING JURISDICTION. GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED BUILDING PERMITS. THE GENERAL CONTRACTOR IS TO HAVE A FULL TIME QUALIFIED SUPERVISOR ON THE SITE AT ALL TIMES WHILE WORK IS BEING PERFORMED. ALL MATERIAL SPECIFIED IS TO BE NEW & INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND SPECIFICATIONS. GENERAL CONTRACTOR IS TO CONSTRUCT PROJECT IN ACCORDANCE WITH THE DOCUMENTS. ANY DEVIATION FROM THE INTENT OF THE DOCUMENTS, WITHOUT ARCHITECT OR ENGINEER'S APPROVAL, ARE AT THE CONTRACTOR'S OWN RISK AND MAY RESULT IN THE WORK BEING DONE OVER AT CONTRACTOR'S EXPENSE (MATERIALS AND LABOR). DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com T0.00 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 TITLE SHEET MSHMH PR O J E C T # : 2 0 0 2 0 4 POLICE SEARCH BUILDING PROJECT INFORMATION: SHEET INDEX NUMBER NAME ISSUE DATE REVISION TITLE T0.00 TITLE SHEET 4/1/2021 A T0.10 CODE REVIEW 4/1/2021 CIVIL C000 GENERAL CIVIL INFORMATION 4/1/2021 C010 EXISTING SITE SURVEY AND DEMO PLAN 4/1/2021 A C110 SITE AND UTILITY PLAN 4/1/2021 A C130 SITE GRADING PLAN 4/1/2021 A C200 GENERAL NOTES AND DETAILS 4/1/2021 A ARCHITECTURAL A0.0 ARCHITECTURAL NOTES 4/1/2021 A1.00 LEVEL 1 FLOOR PLAN 4/1/2021 A1.20 MEZZANINE LEVEL PLAN 4/1/2021 A2.00 LEVEL 1 REFLECTED CEILING PLAN 4/1/2021 A2.10 MEZZANINE LEVEL REFLECTED CEILING PLAN 4/1/2021 A3.00 ROOF PLAN 4/1/2021 A3.10 ROOF DETAILS 4/1/2021 A4.00 EXTERIOR ELEVATIONS 4/1/2021 A5.00 BUILDING SECTIONS 4/1/2021 A6.00 WALL SECTIONS 4/1/2021 A7.00 FLOOR FINISH PLAN 4/1/2021 A7.10 INTERIOR ELEVATIONS 4/1/2021 A8.00 DOOR AND WINDOW SCHEDULE AND DETAILS 4/1/2021 STRUCTURAL S0.00 STRUCTURAL NOTES 4/1/2021 S1.00 FOUNDATION PLAN 4/1/2021 S2.00 MEZZANINE FLOOR FRAMING PLAN 4/1/2021 S2.10 ROOF FRAMING PLAN 4/1/2021 S3.00 SHEAR PLAN 4/1/2021 S4.00 FOUNDATION DETAILS 4/1/2021 S4.10 FRAMING DETAILS 4/1/2021 S4.20 SHEAR DETAILS 4/1/2021 MECHANICAL M0.00 MECHANICAL TITLE SHEET 4/1/2021 M1.10 LEVEL 1 HVAC PLAN 4/1/2021 M7.00 MECHANICAL DETAILS 4/1/2021 M8.00 MECHANICAL SCHEDULES 4/1/2021 PLUMBING P0.00 PLUMBING TITLE SHEET 4/1/2021 P1.00 UNDERFLOOR PLUMBING PLAN 4/1/2021 A P1.10 LEVEL 1 PLUMBING SUPPLY PLAN 4/1/2021 A P2.10 LEVEL 1 WASTE & VENT PLAN 4/1/2021 P3.00 ROOF PLUMBING PLAN 4/1/2021 P7.00 PLUMBING DETAILS 4/1/2021 A P8.00 PLUMBING SCHEDULES 4/1/2021 A ELECTRICAL E0.00 ELECTRICAL TITLE SHEET 4/1/2021 E0.10 ELECTRICAL SITE PLAN 4/1/2021 E1.10 LEVEL 1 LIGHTING PLAN 4/1/2021 A E1.20 LEVEL 2 LIGHTING PLAN 4/1/2021 E2.10 LEVEL 1 POWER AND SYSTEMS PLAN 4/1/2021 A E2.20 LEVEL 2 POWER AND SYSTEMS PLAN 4/1/2021 A E5.00 ELECTRICAL DIAGRAMS 4/1/2021 E7.00 ELECTRICAL DETAILS 4/1/2021 A E8.00 ELECTRICAL SCHEDULES 4/1/2021 SIT E OWNER/DEVELOPER DESIGN PROFESSIONAL BUILDING DEPARTMENT KALISPELL BUILDING DEPARTMENT 201 1ST AVE E KALISPELL, MT 59901 ATTN: JEFF CLAWSON EMAIL: JCLAWSON@KALISPELL.COM TEL: (406) 785-7730 JACKOLA ENGINEERING & ARCHITECTURE, P.C. 2250 HWY. 93 SOUTH PO BOX 1134 KALISPELL, MT 59903 ARCHITECT: MELISSA STEINER CIVIL ENGINEER: ERIK GARBERG STRUCTURAL ENGINEER: ERIK GARBERG MECHANICAL ENGINEER: COURTNEY CARRIER SURVEYOR: SAM DUGUAY CITY OF KALISPELL 312 1ST AVE E KALISPELL, MT 59901 ATTN: DOUG OVERMAN EMAIL: doverman@kalispell.com TEL: (406) 253.4633 CITY OF KALISPELL 1ST AVE WEST KALISPELL, MT 59901 SITE LOCATION: A ADDENDUM 7/2/2021 MELISSA KATHLEEN STEINER 13707 SN E D ECIL ARCHIT E CT ANS T ATEOFM O N TA BOZEMAN, MT GM GM SS CB CB CB SD 6" PVC SD CB CB W SD XSDCB-1 XSDMH-01 XSDCB-02 XOS-01 XSDCB-03 XSSMH-02 C C EM 6" S T O R M P V C 8" ST O R M P V C 8" STORM PV C 6" S T O R M P V C 6 " S T O R M P V C 4" S T O R M P V C 30" SEWER RCP 30" SEWER RCP 30" SEWER RCP EXISTING BUILDING EXISTING BUILDING 29 3 0 2930 2 9 3 0 2930 2 9 3 0 2931 29 3 1 293 1 NEW BUILDING FOOTPRINT SHOWN FOR REFERENCE 1 1 2 POINT COORDINATE TABLE POINT 1 2 3 5 NORTHING 1470504.07 1470586.48 1470358.74 1470571.83 EASTING 795854.26 795857.86 795844.96 795788.25 ELEVATION 2930.63 2930.98 2930.26 2930.62 DESCRIPTION NAIL NAIL NAIL NAIL BASIS OF SURVEY: BASIS OF BEARINGS IS PER CITY OF KALISPELL UTILITY MAP UTILZING SEWER MANHOLES XSSMH-01 AND XSSMH-02 AS A BASIS. ELEVATION DATUM IS PER CITY OF KALISPELL UTILITY MAP ELEVATION AT SEWER MANHOLE XSSMH-02. COORDINATE SYSTEM IS PER CITY OF KALISPELL UTILITY MAP UTILIZING SEWER MANHOLES XSSMH-01 AND XSSMH-02 AS A BASIS. SURVEY NOTES:1.UTILITIES ARE SHOWN BASED ON THE SITE SURVEY PERFORMED BY JACKOLA ENGINEERING AND ARCHITECTURE ON 02/04/2020. UNDERGROUND CABLE, GAS, AND ELECTRICUTILITIES WERE SURVEYED BASED ON UTILITY MARKINGS PROVIDED BY OTHERS. OVERHEAD POWER WAS MARKEDBASED ON OBSERVABLE POLES AND WIRES. SEWER, WATER, AND STORM ON FIRST AVENUE WEST WERE NOT MARKEDPRIOR TO THE FIELD SURVEY. THESE UTILITIES ARE SHOWN ASAPPROXIMATE AND ARE BASED ON OBSERVABLE MANHOLES,HYDRANTS, AND VALVES AS WELL AS GIS DRAWINGS PROVIDEDBY THE CITY OF KALISPELL. 2.PRIVATE UTILITIES WERE NOT LOCATED PRIOR TO THE FIELDSURVEY. DEMO NOTES: 1.NEATLY SAWCUT, REMOVE, AND PROPERLY DISPOSE OF EXISTING ASPHALT. 2.REMOVE AND STOCKPILE CLEAN GRAVEL FOR RE-USE. # SEWER STRUCTURE TABLE: XSSMH-01 RIM: 2931.25' IE OUT: 2925.74' XSSMH-02 RIM: 2929.89' IE IN:2923.84' STORM STRUCTURE TABLE: XSDCB-01 RIM: 2929.94' XSDCB-02 RIM: 2930.17' IE OUT:2926.34' XSDCB-03 RIM: 2929.65' IE IN:2925.88' XSDMH-01 RIM: 2930.40' XOS-01 RIM: 2930.21' IE OUT:2927.38' GM GM SS SD W SD XOS-01 XSSMH-02 C EM 8" STORM PVC 4" S T O R M P V C 30" SEWER RCP 30" SEWER RCP EXISTINGBUILDING 29 3 0 2930 2 9 3 0 2930 2 1 DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com PR O J E C T # : E No.14108 PE T LCE SEN DI P RIKD.GARBERG ANANOM** F O R ISS E LANO E REENIGN z:\ c l i e n t f i l e s \ 2 0 2 0 \ c i t y o f k a l i s p e l l \ 2 0 0 2 0 4 p o l i c e s e a r c h b u i l d i n g \ 6 d r a w i n g s \ 1 a u t o c a d \ C O K _ P S B _ C 0 . 1 0 . d w g FOR PERMIT C0.1020 0 2 0 4 4/1/2021 EDGJAC EXISTING SITE SURVEY AND DEMO PLAN KA L S I P E L L M T 5 9 9 0 1 1S T A V E W . PO L I C E S E A R C H B U I L D I N G CI T Y O F K A L I S P E L L EXISTING SITE SURVEY AND DEMO PLAN11" = 10'5-5 10 20 SCALE: 1" = 0 10' UTILITY CONNECTION DEMO PLAN21" = 30'15-15 30 60 SCALE: 1" = 0 30' ADDENDUM 7/2/2021A A GM GM SS CB CB CB 6" PVC SD CB CB W SD XSDCB-1 XSDMH-01 XSDCB-02 XOS-01 XSDCB-03 XSSMH-02 C C EM 8" STO R M P V C 8" STORM PVC 6" S T O R M P V C 6 " S T O R M P V C 8" STORM PVC 4" S T O R M P V C 30" SEWER RCP 30" SEWER RCP 30" SEWER RCP EXISTING BUILDING EXISTING BUILDING 29 3 0 2930 2 9 3 0 2930 2 9 3 0 2931 29 3 1 293 1 NEW BUILDING FF: 2930.8' W W co UPUPUPUPUPUP UPUP UP UP F O FO FO FO EM GGGGGGGGGGGGGGGG G G CB GM W 2 2 4 4 4 9 5 4 3 11 8 7 1312 1 1 1 7. 0 0 ' 5. 0 0 ' 8.15'3.85' 5.00' 1" W A T E R S E R V I C E 4" S E W E R S E R V I C E 4" S T O R M C2.00 4 C2.00 3 C2.00 3C2.00 4 6 10 CB-01RIM ELEV. = 2930.30' (W) 4" IE OUT = 2929.30' SUMP = 2927.30' GM GM SS SD W SD XOS-01 XSSMH-02 C EM 8" STORM PVC 4" S T O R M P V C 30" SEWER RCP 30" SEWER RCP EXISTINGBUILDING 29 3 0 2930 2 9 3 0 2930 NEW BUILDING FF: 2930.8' co UPUP UP FO EM GGGGGGGGGGGGG G CB GM W 111 7.0 0 ' 5.0 0 ' 8.15'3.85' 5.00' KEYNOTES: 1.NEW ASPHALT SECTION TO MATCH EXISTING. 2.NEW 5" THICK CONCRETE SLAB, REFER TO STRUCTURAL DRAWINGS. 3.VALLEY GUTTER PER DTL. 1/C2.00. 4.NEW BOLLARD PER DTL. 2/C2.00. 5.WATER METER PIT PER DTL. 6/C2.00. 6.WATER SERVICE CONNECTION PER DTL. 5/C2.00. 7.4" SEWER SERVICE OFF EXISTING SEWER MAIN PER DTL. 7/C2.00. 8.SANITARY SEWER CLEAN-OUT PER DTL. 8/C2.00. 9.NEW STORM CATCH BASIN PER DTL. 9/C2.00. 10.INSERTA-TEE CONNECTION TO EXISTING STORM MAIN PER CITY OF KALISPELL. CONTRACTOR TO FIELD VERIFY DEPTH AND ALIGNMENT. 11.3/4" GAS SERVICE WITH GAS METER, COORDINATE WITH UTILITY. 12.3" UNDERGROUND POWER WITH ELECTRIC METER. 13.2" CONDUIT FOR FUTURE COMMUNICATION CONNECTION. GENERAL NOTES: 1.PATCH ASPHALT AS REQUIRED FOR NEW UTILITY CONNECTIONS. 2.CONTRACTOR TO FIELD VERIFY ELEVATIONS AND NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO INSTALLATION. # DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com PR O J E C T # : E No.14108 PE T LCE SEN DI P RIKD.GARBERG ANANOM** F O R ISS E LANO E REENIGN z:\ c l i e n t f i l e s \ 2 0 2 0 \ c i t y o f k a l i s p e l l \ 2 0 0 2 0 4 p o l i c e s e a r c h b u i l d i n g \ 6 d r a w i n g s \ 1 a u t o c a d \ C O K _ P S B _ C 1 . 1 0 . d w g FOR PERMIT C1.1020 0 2 0 4 4/1/2021 EDGEMS SITE AND UTILITY PLAN KA L S I P E L L M T 5 9 9 0 1 1S T A V E W . PO L I C E S E A R C H B U I L D I N G CI T Y O F K A L I S P E L L SITE AND UTILITY PLAN11" = 10'5-5 10 20 SCALE: 1" = 0 10' UTILITY CONNECTION PLAN21" = 30'15-15 30 60 SCALE: 1" = 0 30' ADDENDUM 7/2/2021A A A GM GM SS CB CB CB SD SD CB CB W SD C C EM EXISTING BUILDING EXISTING BUILDING 29 3 0 2930 2 9 3 0 2930 2 9 3 0 2931 29 3 1 293 1 NEW BUILDING FF: 2930.8' CB 2930 2930 2930 29312931293129312931 29 3 1 293 1 2930 293 1 293 0 . 8 0 293 0 . 8 0 29 3 0 . 8 0 293 0 . 8 0 29 3 0 . 3 0 -3 . 3 % 293 0 . 6 6 293 0 . 6 6 29 3 0 . 7 0 29 3 0 . 0 4 29 3 0 . 4 0 VA L L E Y 29 3 0 . 7 0 29 3 0 . 7 0 2930 . 8 0 2930 . 8 0 -0 . 8 % MAT C H E X I S T I N G MA T C H E X I S T I N G MA T C H E X I S T I N G MA T C H E X I S T I N G MAT C H E X I S T I N G MA T C H E X I S T I N G MA T C H E X I S T I N G MATC H E X I S T I N G MATC H E X I S T I N G MATC H E X I S T I N G MATC H E X I S T I N G 29 3 0 . 0 0 293 0 . 0 2 293 0 . 4 1 2 9 3 0 . 4 4 29 3 0 . 2 5 2 9 3 0 . 2 0 293 0 . 2 4 MA T C H E X I S T I N G 29 3 0 29 3 0 29 3 1 2 9 3 0 2 9 3 0 2 9 3 0 2930 2930 2930 29 3 0 2 9 3 0 293 0 293 0 29 3 0 2930 2930 2 9 3 0 2930 2930.0 293 0 . 1 293 0 . 2 293 0 . 3 29 3 0 . 4 29 3 0 . 5 29 3 0 . 6 29 3 0 . 4 2930.5 2930.6 2930.7 2930.12930 . 2 2930. 3 2930.4 29 3 0 . 5 2 9 3 0 . 6 2 9 3 0 . 7 -3.1% 1. 4 % -3 . 2 % -2 . 0 % -3.5% -3.4% 2930 . 8 0 2930 . 4 0 2930 . 2 8 293 0 . 1 4 LEGEND: EXISTING SPOT GRADE DESIGN SPOT GRADE DESIGN TBC SPOT GRADE 2979.04(e) 2979.73 (2980.23) GM GM SS SD W SD C EM EXISTINGBUILDING 29 3 0 2930 2 9 3 0 2930 NEW BUILDING FF: 2930.8' CB 2930 2930 VA L L E Y MATCH EXISTING ELEVATIONS ALONG ASPHALT/GRAVEL PATCH 293 0 293 0 29 3 0 2930 293 0 29 3 0 2930 2930 293 0 2930 2930 29 3 0 2930 2930.0 2930 . 1 2930 . 2 293 0 . 3 293 0 . 4 293 0 . 5 293 0 . 6 29 3 0 . 4 2930.5 2930.6 2930.7 2930.12930.2 2930.3 2930.4 293 0 . 5 29 3 0 . 6 29 3 0 . 7 -3.1% 1.4 % -3. 2 % -2 . 0 % -3.5% -3.4% DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com PR O J E C T # : E No.14108 PE T LCE SEN DI P RIKD.GARBERG ANANOM** F O R ISS E LANO E REENIGN z:\ c l i e n t f i l e s \ 2 0 2 0 \ c i t y o f k a l i s p e l l \ 2 0 0 2 0 4 p o l i c e s e a r c h b u i l d i n g \ 6 d r a w i n g s \ 1 a u t o c a d \ C O K _ P S B _ C 1 . 3 0 . d w g FOR PERMIT C1.3020 0 2 0 4 4/1/2021 EDGJAC SITE GRADING PLAN KA L S I P E L L M T 5 9 9 0 1 1S T A V E W . PO L I C E S E A R C H B U I L D I N G CI T Y O F K A L I S P E L L SITE GRADING PLAN11" = 10'10-10 20 40 SCALE: 1" = 0 20' ADDENDUM 7/2/2021A UTILITY CONNECTION GRADING PLAN21" = 30'15-15 30 60 SCALE: 1" = 0 30' A NOTES: 1.1/2" EXPANSION JOINT MATERIAL SHALL BE PLACED AT EACH POINT OF CURVATURE AND POINT OF TANGENCY. 2.CONTRACTION JOINTS SHALL BE PLACED AT EVERY 10' OF CURB LENGTH AND SHALL HAVE A MINIMUM DEPTH OF 1-1/2" AND A MINIMUM WIDTH OF 1/8". CONTRACTION JOINTS SHALL BE CONSTRUCTED BY SAWING OR SCORING. A TOOL SHALL BE USED WHICH WILL LEAVE CORNERS ROUNDED AND DESTROY AGGREGATE INTERLOCK FOR THE SPECIFIED MINIMUM DEPTH. 3.EXPOSED EDGES SHALL BE FINISHED TO A RADIUS OF 1/4". 4.CONCRETE SHALL BE M-4000 WITH 3/4" MAXIMUM AGGREGATE, MINIMUM 28-DAY STRENGTH OF 4000 PSI, 6%+ 1 1/2% AIR ENTRAINMENT, AND MAXIMUM SLUMP OF 4". 5.INDIVIDUAL CONTRACTORS FORMS MAY VARY SLIGHTLY FROM THIS PATTERN. PATTERNS DIFFERING MATERIALLY FROM THE ABOVE DIMENSIONS SHALL BE SUBMITTED TO THE CITY FOR REVIEW. 6.FOUR INCHES OF CRUSHED GRAVEL BASE MATERIAL, -3/4" DIAMETER IS REQUIRED FOR THE CURB AND GUTTER FOUNDATION. THE BASE MATERIAL SHALL BE COMPACTED TO 95% DENSITY (+ 3% OPTIMUM MOISTURE) PER AASHTO T-99. VALLEY GUTTER DETAIL1N.T.S. 2'-0"7" 1" 7" 1'FLOW LINE PAVEMENT PER PAVEMENT SECTION 6" 4" DETECTABLE WARNING TAPE, MIN. 3" IN WIDTH, APWA COLORS 12 " - 2 4 " 12 GAUGE HDPE OR HMWPE INSULATED SOLID CORE COPPER TONING WIRE, TAPE TO TOP OF WATER MAIN EVERY 5 FT. JOINTS SHALL BE MADE WITH MOISTURE DISPLACEMENT CONNECTORS 12" MIN. SLOPING, BENCHING, SHORING OR SUPPORT SYSTEMS IN THIS AREA TO CONFORM TO O.S.H.A. REGULATIONS MIN TRENCH WIDTH PER MPWSS 4" ASPHALT 6" CRUSHED GRAVEL BASE 9"-15" SUB-BASE 1.5"-3.5" DIAMETER CRUSHED STONE TO STABILIZE UNSTABLE FOUNDATION BEDDING, HAUNCHING, AND INITIAL BACKFILL 3" MINUS CRUSHED SUBBASE MPWSS SECTION 02234 PARAGRAPH 2.3 AND 2.4 NOTES: 1.ALL PIPE BEDDING AND TRENCH BACKFILL SHALL BE COMPACTED TO 95% MAXIMUM DRY DENSITY IN ACCORDANCE WITH AASHTO T-99. 2.ALL TRENCH CONSTRUCTION SHALL CONFORM TO CURRENT OSHA STANDARDS - EXCAVATIONS. 3.INSTALL DETECTABLE WARNING TAPE AND TONER WIRE ON ALL WATER MAINS AND SEWER FORCE MAINS PER CITY STANDARDS. 4.BEDDING, HAUNCHING, AND INITIAL BACKFILL SHALL BE A CLEAN SAND MEETING USCS CLASSIFICATION SYSTEM SW, OR A CLASS I MATERIALS AS DEFINED IN ASTM D 2321 WITH A MAXIMUM PARTICLE SIZE OF 3/4" AND MEETING MIGRATION REQUIREMENTS OF THE SAME STANDARD. (SECTION X.1.8) 4 NTS TYPICAL UTILITY TRENCH SECTION DETAIL STEEL PIPE BOLLARD2NTS 3' 1'-6" DIA. 3" 4'4" Ø CONC. FILLED STEEL PIPE W/ YELLOW PLASTIC SHEATH 1/2" PRE-MOLDED EXPANSION JOINT WHERE CONCRETE OCCURS PAVING GRANULAR FILL CONCRETE SONNOTUBE 10x10x1/4" THICK PLATE WELDED ALL AROUND MUELLER SERIES 300 BALL STYLE CURB STOP VALVE 9" RADIUS NOTES: 1.3/4" - 2" SERVICES SHALL BE INSTALLED WITH BR2 SERIES SERVICE SADDLES AND PE SERVICE LINE. 2.4" AND LARGER SERVICES SHALL BE INSTALLED WITH A ROMAC SSTIII STAINLESS STEEL TAPPING SLEEVE AND CLASS 150 PVC SERVICE LINE. 5 NTS WATER SERVICE CONNECTION DETAIL TO BUILDING EXISTING WATER MAIN 4" PVC, TYP. 12" MIN. 1. PRIMARY TRENCH (UTILITY POLE TO VAULT: TRENCH TO TRANSFORMER PAD/VAULT PER PLAN) CONDUIT AMBIENT TEMP. SHALL START @20°C (68°F) BEFORE ANY DERATE & CONDUCTOR AMBIENT TEMP. SHALL START @75°C (167°F) BEFORE ANY DERATE. NOTES: 1.TRENCH CONTENTS SHALL CONFORM TO NEC ARTICLE 300 AND TABLES 300-5 & 310-60, AND APPENDIX B. 2.MULTIPLE ELECTRICAL POWER CONDUITS SHALL MAINTAIN 7.5" SPACING CL TO CL HORIZONTAL AND VERTICALLY (2" MIN), AND SHALL MAINTAIN 12" SEPARATION FROM ALL GAS LINES, COMMUNICATION LINES, AND OPTIC LINES. 3.SLIGHT SERPENTINE LAY IS ALLOWED TO ADEQUATELY COMPENSATE FOR FROST HEAVE. 4.PROVIDE FULL LENGTH 1/4" POLY PULL LINE IN EMPTY CONDUIT SECTIONS. LABEL EACH END. 5.ALL DRY UTILITIES SHALL BE 5' MIN. FROM WATER AND SEWER MAINS 6.REFER TO E1.0 FOR DUCT BANK DESCRIPTIONS EXISTING STREET SURFACE 3' - 0 " N T S GRADE PHONE 2" PVC, TYP. CONDUITS AND WIRE SIZE PER NEC AND SITE ELECTRICAL PLAN 4" SPARE EXCAVATEDMATERIAL 18" MIN. PROVIDE 12" MIN., SEPARATION FROM ALL COMMUNICATION LINES AND OPTIC LINES. PROVIDE 36" SEPARATION FROM GAS LINES. 3. FEEDER TRENCH (VAULT TO SERVICE PANEL & METERS) TRENCH WIDTH=0.D. OF PIPE + 24" INSTALL DETECTABLE WARNING TAPE 12" MAX. DEPTH. SUB GRADE OR GROUND SURFACE RESURFACE TO MATCH ORIGINAL 1 1 3 3/4" 1" 3"1" 2. SITE ELECTRICAL (LOT LIGHTS & SIGNS TO SERVICE PANEL) 36 " M I N . 40 " M A X . 4" PVC, TYP. 2" CATV 2" PHONE 2- 0 " T O 2 ' - 6 " CATV ELECTRICAL TRENCH SECTION31" = 1'-0" 12" METER PIT DETAIL6N.T.S. W W W MUELLER THERMAL COIL METER BOX WITH DOMESTIC METER WITH METER VALVES AND CHECK VALVE WATER SERVICE CURB STOP WITH MUELLER H-10306 CURB BOX FOR 3/4" AND 1" SERVICES AND H-10310 FOR 2" SERVICES CLASS 200 PSI C901 PE PIPE TO B U I L D I N G NOTES: 1.CURB STOPS TO MUELLER 300 SERIES BALL VALVE.. 2.SERVICE FITTINGS TO BE MUELLER INSTATITE OR 110 SERIES COMPRESSION FITTINGS. USE STAINLESS STEEL INSERTS PER MANUFACTURER RECOMMENDATIONS ON FITTINGS LARGER THAN 1". TRAFFIC RATED LID REQUIRED WITH TRAFFIC-RATED RING AND COLLAR SANITARY SEWER SERVICE LINE71" = 1'-0" EXCAVATE AND VERIFY EXISTING SEWER SERVICE INVERT. CONNECT NEW SCH 40 PIPING AND EXTEND TO BUILDING. COORDINATE WITH PLUMBING DRAWINGS. INSERTA-TEE CONNECTION CONNECT PIPE TO EXISTING BELLED END OR USE RIGID COUPLING COMPACTED BACKFILL FINISHED GRADE TYPICAL CLEANOUT DETAIL83/4" = 1'-0" PAVED OR OTHER SURFACE SEWER/STORM LINE-SEE PLAN FOR SIZE FLOW IF LINE DEAD ENDS, INSTALL WATERTIGHT PLUG COMPACTED BACKFILL FILL W/ SAND OR CRUSHED TOP COURSE SURFACING MATERIAL CAP WITHOUT GASKET BOLT-LOCKING CAST IRON RING & COVER, 14" MINIMUM OPENING DIA. H-20 RATED IN PAVED AREAS CONCRETE 45° BEND 2" 3" M I N 6" M A X 4" 12 " NOTES: 1. CAST IRON COVER SHALL READ "SEWER" 2. LOCKING BOLTS FOR COVER SHALL BE 5/8"-11 NC STAINLESS STEEL TYPE 304 3. 14" BOLT-LOCKING CAST IRON COVER SHALL BE EQUAL TO INLAND FOUNDRY NO. 209 24 " CONCRETE ADJUSTMENT RING, 2" MIN, 12' MAX 2' - 6" CONCRETE CATCH BASIN STORM PIPE, SEE PLAN FOR SIZE AND SLOPE NOTE: 1.ALL JOINTS BETWEEN CATCH BASIN, ADJUSTMENT RINGS, CASTING, AND SEWER PIPE SHALL BE WATER TIGHT. JOINING MATERIAL SHALL BE RAM-NEK OR EQUAL FOR ALL JOINTS OTHER THAN JOINTS BETWEEN SEWER PIPE AND CATCH BASIN. 2.ALL PIPE CONNECTIONS NOT CONSTRUCTIBLE AS DETAILED SHALL BE SUBMITTED TO CITY ENGINEER FOR REVIEW. FLEXIBLE GASKETED OR BOOTED JOINT, GROUT INTERIOR 6" OF 3" MINUS CRUSHED COMPACTED AGGREGATE FOUNDATION 6" CONCRETE APRON, PER CITY OF KALISPELL STANDARDS FOR DESIGN AND CONSTRUCTION 2'EDGE OF CONCRETE 3/8" BELOW PAVEMENT 24 " M I N . 9 NTS TYPICAL STORMWATER CATCH BASIN 24" MIN MH-37 FRAME AND SLOTTED COVER OR APPROVED EQUAL DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com PR O J E C T # : E No.14108 PE T LCE SEN DI P RIKD.GARBERG ANANOM** F O R ISS E LANO E REENIGN z:\ c l i e n t f i l e s \ 2 0 2 0 \ c i t y o f k a l i s p e l l \ 2 0 0 2 0 4 p o l i c e s e a r c h b u i l d i n g \ 6 d r a w i n g s \ 1 a u t o c a d \ C O K _ P S B _ C 2 . 0 0 . d w g FOR PERMIT C2.0020 0 2 0 4 4/1/2021 EDGJAC GENERAL NOTES AND DETAILS KA L S I P E L L M T 5 9 9 0 1 1S T A V E W . PO L I C E S E A R C H B U I L D I N G CI T Y O F K A L I S P E L L A A A A A C C B B R.R. 104 UTILITY / MECH 103 EVIDENCE / STOR. 102 STOR. 105 SHOP 101 2" FD-1 2" FD-1 4" W 4" W 2" W 2" W 2" V 2" V 2" V FCO 1" CW 4'' TWO-WAY CLEANOUT 3 4 4 1 1 2 2 3 3 4 4 4" W SCH 40 PVC @ 1/4'' PER 1' 0'' 5 3" OW 3" OW SCH 40 PVC @1/4'' PER 1' 0''3" W FCO (TYP.) 2 2" OW 2" V 3" W (TYP.) 1 1" CW UP 2" V UP2" V UP 2" V UP FCO 2" OW 3" FD-1 3" FD-1 3" FD-1 FCO FCO KEYNOTES 1 1/2" PEX TO PRIME TRAP FROM TRAP PRIMER DISTRIBUTION UNIT PER DETAIL 1/P7.00 2 INSTALL FLOOR CLEANOUT PER DETAIL 2/P7.00 3 INSTALL 2-WAY CLEANOUT PER DETAIL 4 SEE CIVIL PLANS FOR CONTINUATION OF PIPING 5 SEE DETAIL 6 /P7.00 FOR SAND OIL SEPERATOR DETAIL 8'16'4'03/8" = 1'-0"1 UNDERFLOOR PLUMBING PLAN DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t P1.00 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 UNDERFLOOR PLUMBING PLAN CLCMSM PR O J E C T # : P r o j e c t N u m b e r M ONTAN A COURTNEY CARRIER No.15309PE PRO F E S SIONA L E N GINEER LICEN S E D A ADDENDUM 7-2-21 A A C C B B R.R. 104 UTILITY / MECH 103 EVIDENCE / STOR. 102 STOR. 105 SHOP 101 1" CW WC-1A LAV-1A MS-1 DHW-1 EWS-1 3/4" NG 1/2" NG 1/2" NG METER: 150,000 BTU/H 14'' W.C. INLET PRESSURE 1 1 2 2 3 3 4 4 1 3/4" CW 1/2" HW 1" HW HB-1HYD-1 3/4" CW DN 1/2" CW DN 1/2" HW 1/2" CW 1/2" CW DN 1/2" CW DN 1" HW 1" CW 2 1" DCV 4 5 1" CW 6 KEYNOTES 1 PROVIDE RECESSSED WALL CABINET FOR THERMOSTATIC MIXING VALVE (S19-2150 OR EQUIVELANT) 2 ROUTE GAS PIPING ALONG CEILING 3 SEE DETAIL 8/P7.00 FOR UNIT HEATER GAS CONNECTION 4 SEE DETIAL 9/P7.00 FOR WATER RISER DIAGRAM 5 SEE WATER HEATER DETAIL 10/P7.00 6 INSTALL MECHANICAL TRAP PRIMER VALVE AND DISTRIBUTION UNIT PER DETAIL 1/P7.00 8'16'4'03/8" = 1'-0"1 LEVEL 1 PLUMBING PLAN DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t P1.10 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 LEVEL 1 PLUMBING SUPPLY PLAN CLCMSM PR O J E C T # : P r o j e c t N u m b e r 3 3 M ONTAN A COURTNEY CARRIER No.15309PE PRO F E S SIONA L E N GINEER LICEN S E D A ADDENDUM 7-2-21 (2) PVC COMBINATION WYE-1/8" BENDS BACK TO BACK (TYP.) OR (1) 2-WAY CLEANOUT TEE GRADE PVC FITTING, TYPICAL ALL FITTINGS PVC THREADED PLUG, TYP6" M A X FLANGED WITH FLASHING COLLAR AS REQ'D FLOOR LINE BRONZE SCORATED TOPCENTER SECURING SCREW THREADED PLUG FITTING TYPE AS REQ'D TO SUIT FLASHING COLLAR FLASHING PAN FLOORING PER FINISH SCHEDULE 9" (225) DIA. TWO-PIECE NICKEL BRONZE FLASHING STRAINER LOOSE GRAVEL AT WEEP HOLES CAULKED, NO-HUB OR THREADED CONNECTION CLEANOUT TEE CLEANOUT PIPE ACCESS COVER FINISHED WALL MIXING VALVE FLOW SWITCH WALL BRACKET INLET PLUGGED NIPPLE EYEWASH DRAIN FLANGE WITH 3 BOLT HOLES ANCHOR WITH EXPANSION BOLTS EYE-FACE WASH WITH STAINLESS STEEL BOWL DELUGE HEAD 1" BALL VALVE 7' -0" FLOW ALARM ANNUNCIATOR HW SUPPLY CW SUPPLY BALL VALVE WITH MEMORY STOP AND LABELING TO PREVENT UNAUTHORIZED SHUT-OFF EYEWASH VALVE NOTE: 1. PROVIDE A LOOSE-KEY LOCKSHIELD TYPE SHUT-OFF VALVE IN DOMESTIC WATER SUPPLY DROP TO EYEWASH. LABEL VALVE TO PREVENT UNAUTHORIZED SHUT-OFF. WATER DEPTHMODEL No. DIM "B" DIM "F"WEIGHTDIM "E" DIM "D"DIM "C" DIM "A" 2'-10"2'-0"11,6315004'-0"6'-0"2'-2"3'-0"4113-SO CAPACITY GALLON GROUT ALL AROUND INLET SIZE PER PLANS OUTLET SIZE PER PLANS ADJUST TO GRADE 24" DIA. TRAFFIC RATED, WATER TIGHT BOLT DOWN LIDS CLEAR ACCESS OPENINGS PRECAST BAFFLE 2" DIA. VENT HOLE DI M " F " DI M " C " . 1' -0" DI M " D " DI M " E " 1/3 LENGTH2/3 LENGTH 2/ 3 W A T E R T A B L E VA R I E S DIM "B" DI M " A " . . SAMPLE PORT RING AND LID (TRAFFIC RATED) CLEAN OUT/VENT FLOATING OIL ADSORBENT SKIMMER OLD CASTLE PRECAST (BASIS OF DESIGN) SEE SAMPLE PORT DETAIL PLUG . CLEAN OUT VENT G SHUT-OFF COCK (4)-1/2"DIA. STEEL RODS WITH TURN BUCKELS UNION SEE MECHANICAL FLOOR PLANS FOR CONTINUATION AND SIZE 1' -0" M I N . DRIP LEG 1" POLY SERVICE LINE SWEEP SLEEVE THROUGH FLOOR AND SEAL 1"X1" POLY SWEAT COPPER ADAPTER 1" COPPER LINE 1" WATTS LF007 (OR EQUAL) BACKFLOW PREVENTER SHUT-OFF VALVE DRAIN VALVE PRESSURE GAUGE TYP. 1" CW TO FIXTURES CODED NOTES 1 2 3 4 5 6 7 8 9 6 7 5 4 3 2 1 9 P P 10 10 CW COLD WATER SERVICE, SIZE AS SHOWN ON PLANS CHECK VALVE SIZE TO PIPE SIZE WATTS POTABLE WATER EXPANSION TANK, PLT-5, INSTALL PER MFR. RECOMMENDATION AND STATE & LOCAL CODES. UNION, DIELECTRIC IF REQ'D WATER HEATER, SEE SCHEDULE BALL VALVE T&P RELIEF VALVE , AND DRAIN PAN TO BE PIPED TO BATHROOM BELOW SEISMIC STRAP TO WALL PER UPC, HOLDRITE HR-80-180 120°F WATER SERVICE LOOP, SIZE AS SHOWN ON PLANS CODED NOTES 1 7 2 8 4 5 4 8 11 1 2 3 4 5 7 8 9 10 11 9 HW CW TO FIXTURES, SIZE PER PLANS 3 TM V THERMOSTATIC MIXING VALVE (CALEFFI TANK MIXER 520) OR EQUAL 12 12 10 10 FLOOR SLAB FLOOR DRAIN DISTRIBUTION UNIT, FOR 5 LINES TRAP PRIMER VALVE DOMESTIC WATER LINE 1/2" TRAP PRIMER LINE 1/2" TRAP PRIMER SUPPLY SLEEVE THRU SLAB 6" MIN 10" MIN INSIDE . . FRONT SIDETOP 1 2 32 4 5 1 2 3 4 5 TRAFFIC RATED, WATER TIGHT BOLT DOWN LIDS INTERCEPTOR DISCHARGE LINE PIPE PENETRATION (EXTEND 1" PAST THE INSIDE WALL OF THE SAMPLE PORT -MUST BE SEALED TO PREVENT LEAKS. IF USING PVC, A SADDLE MUST BE USED) GROUT (SLOPED TO WASTE WATER CHANNEL -THE SAMPLE PORT MUST DRAIN COMPLETELY AND NOT HOLD WATER SAMPLE PORT DISCHARGE LINE **PER CITY OF KALISPELL STANDARDS 4 DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t P7.00 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 PLUMBING DETAILS CLCMSM PR O J E C T # : P r o j e c t N u m b e r N.T.S.4 2WAY CLEANOUT1 N.T.S.2 FLOOR CLEANOUT N.T.S.3 FLOOR DRAIN1 N.T.S.5 WALL CLEANOUT 3/32" = 1'-0"7 EMERGENCY EYEWASH PIPING DETAIL N.T.S.6 SAND/OIL INTERCEPTOR DETAIL N.T.S.8 UNIT HEATER-GAS N.T.S.9 WATER RISER DIAGRAM 1" = 1'-0"10 ELEC. WATER HEATER M ONTAN A COURTNEY CARRIER No.15309PE PRO F E S SIONA L E N GINEER LICEN S E D A ADDENDUM 7-2-21 N.T.S.1 TRAP SEAL PRIMER N.T.S.11 INTERCEPTOR SAMPLE PORT DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t P8.00 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 PLUMBING SCHEDULES CLCMSM PR O J E C T # : P r o j e c t N u m b e r DOMESTIC FIXTURE SCHEDULE TAG DESCRIPTION BASIS OF DESIGN TRIM SPECIFICATIONMANUFACTURER MODEL MANUFACTURER MODEL EWS-1 EMERGENCY EYEWASH/SHOWER STATION BRADLEY S193140A1AAAA00 INCLUDE TEPID WATER TMV S19-2150 FD-1 FLOOR DRAIN WATTS FD-300 EPOXY COATED CAST IRON AREA DRAIN WITH ANCHOR FLANGE WITH HEEL PROOF DUCTILE IRON GRATE, TRAP PRIMING PORT, AND NO HUB OUTLET. HB-1 HOSE BIBB WOODFORD 24 INTERIOR HOSE BIBB WITH VACUUM BREAKER, 3/4" HOSE THREAD OUTLET, LOCK SHIELD CAP, AND REMOVABLE "TEE" HANDLE. PROVIDE SHUTOFF VALVE IN COLD WATER SUPPLY AHEAD OF HOSE BIBB. HYD-1 EXTERIOR WALL HYDRANT WOODFORD 67 WOODFORD 67 NON-FREEZE TYPE WALL HYDRANT, WITH DOUBLE CHECK BACKFLOW PREVENTER, VALVE ON THE INSIDE OF THE WALL, SPOUT WITH BACKFLOW PREVENTER, AND LOOSE KEY SOCKET ON THE OUTSIDE OF THE WALL. MAKE ARRANGEMENTS WITH THE GENERAL CONTRACTOR TO PROVIDE THE NECESSARY RECESS IN THE WALL. WHERE A RISER TO A WALL HYDRANT OCCURS IN AN OUTSIDE WALL THE CONTRACTOR SHALL INSULATE THE CHASE WITH 2” STYROFOAM INSULATION ON ALL SIDES OF THE CHASE, EXCEPT THE INSIDE WALL OF THE CHASE. PROVIDE SHUTOFF VALVE IN ACCESSIBLE LOCATION. LAV-1A LAVATORY - WALL HUNG - ADA KOHLER K-1728 MOEN 8430F05 WALL HUNG LAVATORY WITH BACKSPLASH, FAUCET HOLES ON 4” CENTERS. MANUAL DECK-MOUNTED FAUCET, EXTERNAL ASSE 1070 COMPLIANT THERMOSTATIC MIXING VALVE, GRID DRAIN, LOOSE KEY ANGLE STOPS AND SUPPLIES. INSULATE WATER AND WASTE WITH INSULATION KIT. MOUNT AT ADA COMPLIANT HEIGHT. MS-1 JANITOR SINK EL MUSTEE 63M EL MUSTEE 63.600A SERVICE BASIN WITH CAP ON TWO SIDES, FAUCET SHALL INCLUDE PAIL HOOK AND ATMOSPHERIC VACUUM BREAKER SPOUT. INCLUDE HOSE AND HOSE HOLDER, MOP HANGER, AND STAINLESS STEEL BUMPER GUARDS, AND WALL GUARDS. WC-1A WATER CLOSET - FLOOR MOUNT - TANK TYPE - ADA KOHLER K-3979 TANK TYPE ELONGATED FLOOR MOUNTED TANK TYPE WATER CLOSET, WITH CHURCH 295CT ELONGATED OPEN FRONT SEAT. PROVIDE A 1/4" BRASS BALL VALVE AT WALL CONNECTION. INSTALL AT ADA COMPLIANT HEIGHT. ELECTRIC WATER HEATER SCHEDULE TAG BASIS OF DESIGN TYPE ELECTRIC HEAT EXCHANGER EF UNIT WEIGHT FLA VOLT PH REMARKSMANUFACTURER MODEL NO. HEATING CAP WATERSIDE STORAGE MAX TEMP RISERECOVERY VOL DHW-1 AO SMITH DEN-52 STORAGE 4.5 kW 18.6 gal/h 50.0 gal 95 °F 0 565 lb 37.5 A 240 V 1 PROVIDE ASSE 1017 COMPLIANT MIXING VALVE; POWERS SERIES LFSH OR EQUAL. PIPE ACCESSORY SCHEDULE TAG DESCRIPTION BASIS OF DESIGN VALVE PROPERTIES REMARKSMANUFACTURER MODEL FLOW PRESSURE DROP AT RATED FLOW DCV DOUBLE CHECK VALVE BACKFLOW PREVENTION DEVICE WATTS LF007 20.0 GPM 4.0 psi LEAD FREE, MOUNT VERTICAL M ONTAN A COURTNEY CARRIER No.15309PE PRO F E S SIONA L E N GINEER LICEN S E D A ADDENDUM 7-2-21 3 D OS4 D OS2 3 OS 3 A A C C B B R.R. 104 UTILITY / MECH 103 EVIDENCE / STOR. 102 STOR. 105 SHOP 101 1 1 2 2 3 3 4 4 WP2 P1-8 W1 WP1 P1-8 WP1 P1-8 P1 P1-4 P1-2 P1-7 1 2 E1 P1-4 E1 P1-7 L1 L1 L1 L1E L1 L1 L1E 3 3 4 P1-5 P1-12 WP2 P1-8 KEYNOTES 1 LIGHTING SWITCH TO CONTROL MEZZANINE AREA LIGHTS. SEE LEVEL 2 LIGHTING PLAN FOR MORE INFORMATION. 2 LIGHTING SWITCH TO CONTROL LEVEL 2 SHOP LIGHTING. SEE LEVEL 2 LIGHTING PLAN FOR MORE INFORMATION. 3 SWITCHES SHALL BE NLIGHT WIRED ENABLED DEVICES TO COMMUNICATE WITH OCCUPANCY SENSORS AND POWER PACKS. BASIS OF DESIGN DEVICES SHALL BE: NLIGHT- NPODM-DX-WH. 4 SWITCHES SHALL BE NLIGHT WIRED ENABLED DEVICES TO COMMUNICATE WITH OCCUPANCY SENSORS AND POWER PACKS. BASIS OF DESIGN DEVICES SHALL BE: NLIGHT- NPODM-WH. 0 2'4'6'3/8" = 1'-0"1 LEVEL 1 LIGHTING PLAN DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t E1.10 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 LEVEL 1 LIGHTING PLAN MIBJSJ PR O J E C T # : P r o j e c t N u m b e r LIGHTING GENERAL NOTES * CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY LIGHTING FIXTURES, CONTROL DEVICES, AND ACCESSORIES NEEDED TO ENSURE INSTALLED SYSTEM IS COMPLETE AND IN PROPER WORKING ORDER AS DESIGN INTENDED. * TYPICAL EMERGENCY AND EXIT LIGHTS SHALL BE WIRED TO NEAREST ROOM LIGHTING CIRCUIT AHEAD OF ANY CONTROLS OR SWITCHING. * ALL LAY-IN LIGHT FIXTURES ARE TO BE SUPPORTED INDEPENDENT OF NON-RATED GRID CEILINGS FROM THE STRUCTURE ABOVE FROM AT LEAST TWO CORNERS. ATTACH WITH GRID CLIPS OR TABS RATED FOR LAY-IN CEILINGS. * CONTRACTOR SHALL VERIFY EACH J-BOX HAS SUFFICIENT ATTACHMENT ANCHORAGE TO SUPPORT LIGHTING OR FAN WEIGHT LOADS * EXIT SIGNS SHALL BE FURNISHED WITH NUMBER OF FACES AND DIRECTIONAL ARROWS AS REQUIRED TO SUIT PLAN AND THE LOCAL AUTHORITY. * CONTRACTOR SHALL VERIFY ALL BULBS, COLORS, LENGTHS, TRIMS, CEILING TYPES, MOUNTINGS, FINISHES, ETC., WITH THE ENGINEER, PRIOR TO PLACING FINAL LIGHTING PURCHASE ORDER, INCLUDING THE INTENT OF ALL APPROVED REVISIONS OR PUBLISHED ADDENDUMS. * WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND SWITCHING CONNECTIONS SHOWN. * CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE. M ONTANA No.71878PE PRO F E S S IONA L E N GINEER LICEN S E D MIKI IKEMOTO BACKUS M ONTANA No.71878PE PRO F E S S IONA L E N GINEER LICEN S E D MIKI IKEMOTO BACKUS A ADDENDUM 7-2-21 A A 48"GFI 48 "GF I 48 "GF I 48"GFI 48 "GF I 48"GFI48"GFI ACGF I GFI GFI GFI GF I J GFI T T A A C C B B R.R. 104 UTILITY / MECH 103 EVIDENCE / STOR. 102 STOR. 105 SHOP 101 P1 1 2 DHW-1 1 1 2 2 3 3 4 4 EF-4 IT/SECURITY RACK EUH-1 EUH-1 P1-22 P1-17 P1-13 P1-24 P1-8 P1-6 P1-11 P1-19 P1-27 EF-3 P1-3 P1-1 EUH-1 P1-30 120/240V, 1Ø, 3W 200A SERVICE DISCONNECT P1-9 P1-18,20 3 BUILDING DMARK LOCATION 4 (TYP.) 5 36"x24" IL-1 EF-1 CO NO2 H.O.A. 6 7 P1-16 7 A A 0 2'4'6'3/8" = 1'-0"1 LEVEL 1 POWER AND DATA PLAN KEYNOTES 1 INCOMMING ELECTRICAL SERVICE FROM UTILITY. 2 PROPOSED ELECTRICAL UTILITY METER, CT CAN, SERVICE DISCONNECT LOCATION. 3 EF-4 TO BE CONTROLLED BY OCCUPANCY SENSOR LIGHT SWITCH. SEE LIGHTING PLANS FOR MORE INFORMATION. 4 PROVIDE NECESSARY CONNECTION FROM BUILDING DMARK TO IT/SECURITY RACK LOCATION. COORDINATE WITH OWNER/I.T. FOR ALL NECESSARY EQUIPMENT CONNECTION. 5 SECURITY CAMERAS AND MONITORING/RECORDING EQUIPMENT TO BE PROVIDED BY OWNER. CONTRACTOR SHALL PROVIDE SINGLE GANG J-BOX (WATERPROOF FOR EXTERIOR LOCATIONS SHOWN) FOR CAT6 CONNECTION. CAT6 SHALL BE ROUTED FROM EACH LOCATION SHOWN. BACK TO I.T. RACK, LOCATED IN MECHANICAL ROOM. COORDINATE WITH OWNER IT DEPARTMENT PRIOR TO ROUGH-IN FOR ADDITIONAL INSTALLATION REQUIREMENTS. 6 E.C. TO PROVIDE H.O.A. AND ALL ASSOCIATED BRANCH CIRCUIT WIRING AND CONDUIT TO GAS MONITOR, EF-1, AND IL-1 AS INDICATED ON SHEET E5.00 ELECTRICAL DETAILS. E.C. TO COORDINATE WITH M.C. PRIOR TO ROUGH-IN. 7 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY. SEE ARCHITECTURAL PLANS FOR EXACT MOUNTING HEIGHT. DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t E2.10 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 LEVEL 1 POWER AND SYSTEMS PLAN MIBJSJ PR O J E C T # : P r o j e c t N u m b e r POWER GENERAL NOTES * CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE. * RECEPTACLES RATED FOR WET LOCATIONS SHALL BE NEMA 5-20R. * PRIOR TO ROUGH-IN AND INSTALLATION, THE CONTRACTOR SHALL FIELD VERIFY THE LOCATON AND REQUIREMENTS OF ALL ELECTRICAL ITEMS. * GROUNDING AND BONDING SHALL BE IN STRICT ACCORDANCE WITH THE NEC AND UTILITY REGULATIONS. PROVIDE COPPER EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS. * RECEPTACLES ABOVE THE COUNTERTOPS WHERE INDICATED BY "AC". EXACT LOCATION SHALL BE COORDINATED WITH THE ARCHITECT. * WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND SWITCHING CONNECTIONS SHOWN. M ONTANA No.71878PE PRO F E S S IONA L E N GINEER LICEN S E D MIKI IKEMOTO BACKUS A ADDENDUM 7-2-21 A J J CLNG CLNG CLNG A A C C B B 1 1 2 2 3 3 4 4 P1-26 P1-15 P1-31 P1-28 UH-2 P1-23 P1-10 EF-1 UH-1 EF-2P1-12 1 36"x24" IL-1 2 2 0 2'4'6'3/8" = 1'-0"1 LEVEL 2 POWER AND DATA PLAN DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t E2.20 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 LEVEL 2 POWER AND SYSTEMS PLAN MIBJSJ PR O J E C T # : P r o j e c t N u m b e r POWER GENERAL NOTES * CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE. * RECEPTACLES RATED FOR WET LOCATIONS SHALL BE NEMA 5-20R. * PRIOR TO ROUGH-IN AND INSTALLATION, THE CONTRACTOR SHALL FIELD VERIFY THE LOCATON AND REQUIREMENTS OF ALL ELECTRICAL ITEMS. * GROUNDING AND BONDING SHALL BE IN STRICT ACCORDANCE WITH THE NEC AND UTILITY REGULATIONS. PROVIDE COPPER EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS. * RECEPTACLES ABOVE THE COUNTERTOPS WHERE INDICATED BY "AC". EXACT LOCATION SHALL BE COORDINATED WITH THE ARCHITECT. * WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND SWITCHING CONNECTIONS SHOWN. M ONTANA No.71878PE PRO F E S S IONA L E N GINEER LICEN S E D MIKI IKEMOTO BACKUS A ADDENDUM 7-2-21 KEYNOTES 1 EF-2 SHALL BE CONTROLLED DURING OCCUPANCY. SEE MECHANICAL SHEETS FOR MORE INFORMATION. PROVIDE NLIGHT NPP16 POWER PACK TO TIE INTO LIGHTING CONTROLS. 2 EQUIPMENT IS POWERED BY AND CONTROLLED BY H.O.A. LOCATED ON LEVEL 1. SEE SHEETS E2.10, E5.00, AND M8.00 FOR ADDITIONAL INFORMATION. A A A M I N 2 0' N GØ OUTLET BOX GROUNDING CONDUCTOR (GREEN) TAPPED HOLE IN BOX GROUND SCREW -#10 32 X 3/8" SLOTTED HEXAGON HEAD, WASHER FACE SCREW (TYP) WIRE NUT (TYP) CONDUIT NOTE: GROUNDING CONDUCTOR SHALL BE CONTINUOUS SO THAT REMOVAL OF DEVICE WILL NOT INTERFERE WITH CONDUCTOR CONTINUITY. STRIP INSULATION AND LOOP BARE CONDUCTOR AROUND PHASE SCREW WITHOUT CUTTING CONDUCTOR OR PROVIDE ADDITIONAL WIRE NUT TERMINATION EQUAL TO NEUTRAL. G N Ø RECEPTACLE GROUND LUG SCREW DETAIL KEY NOTES: 1. PROVIDE ENOUGH LENGTH TO TERMINATE DIRECTLY TO GROUND BUS. 2. INSTALL AN ELECTRODE ENCASED BY AT LEAST 2" OF CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 20 FT OF ZINC GALVANIZED OR OTHER ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS OF NOT LESS THAN 1/2" IN DIAMETER, OR CONSISTING OF AT LEAST 20 FT OF BARE COPER CONDUCTOR NOT SMALLER THAN #4 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS. 3. GROUND THE INTERIOR METAL WATER PIPE WITHIN 5 FEET OF THE WATER PIPE ENTRANCE TO THE BUILDING. GROUNDING PATH CONTINUITY, OR THE BONDING CONNECTION TO INTERIOR PIPING, MUST NOT RELY ON WATER METERS OR SIMILAR EQUIPMENT (NEC 250.53(D)). 4. MINIMUM OF (2) 5/8" X 8'-0" COPPER CLAD STEEL GROUND RODS, 25 OHMS OR LESS. CLAMPS SHALL BE RATED FOR DIRECT BURIAL. 5. BOND ALL METAL RACEWAYS CONTAINING GROUNDING ELECTRODE CONDUCTORS AT BOTH END AS REQUIRED BY NEC 250.64(E). PROVIDE GROUNDING TYPE BUSHINGS AND FITTINGS. 6. BONDING JUMPERS AND COPPER GROUNDING ELECTRODE CONDUCTORS SHALL BE SIZED BASED UPON ELECTRICAL SERVICE SIZE (NEC 250.66). 7. PROVIDE COPPER BONDING JUMPER SIZED PER NEC 250.28(D) OR FACTORY PROVIDED NEUTRAL TO GROUND BAR LINK. THIS IS THE ONLY PLACE IN THE BUILDING WHERE NEUTRAL TO GROUND SHALL BE BONDED TOGETHER. CONCRETE-ENCASED ELECTRODE NEC 250.52(A)(3) BUILDING STEEL NEC 250.52(A)(2) METAL WATER PIPE NEC 250.52(A)(1) GROUND ROD NEC 250.52(A)(5) 1 5 6 4 6 3 26 6 G N 7 METER/MAIN DISCONNECT EQUIPMENT 6 6 6 120V 120 VAC LOUVER IL-1 120V N GAS MONITOR (CO2/NO2) HOFFA RELAY 120V, 20A H.O.A. SWITCH RELAY 120V, 20A N 120V EF-1 NOTE:RELAY, H.O.A. SWITCH, AND ALL 120V WIRING BY E.C.; LOUVER, FAN, AND GAS MONITOR BY M.C. DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t E7.00 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 ELECTRICAL DETAILS MIBJSJ PR O J E C T # : P r o j e c t N u m b e r N.T.S.2 TYP. RECEPTACLE GROUNDING DETAIL N.T.S.1 GROUNDING DETAIL M ONTANA No.71878PE PRO F E S S IONA L E N GINEER LICEN S E D MIKI IKEMOTO BACKUS A ADDENDUM 7-2-21 N.T.S.3 HAND-OFF-AUTO DETAIL A DATE: JACKOLA ENGR. & ARCH., P.C. WITHOUT THE WRITTEN CONSENT OF MAY NOT BE USED OR REPRODUCED IS PROPRIETARY. THIS DOCUMENT THE INFORMATION CONTAINED HEREIN REVISIONS: FOR PERMIT KALISPELL 406-755-3208 # BOZEMAN 406-586-0707 VANCOUVER 360-852-8746 DRAWN:CHECKED: info@jackola.com jackola.com BIM 3 6 0 : / / A D 2 0 2 0 / C O K _ S e a r c h B u i l d i n g _ M E P 2 0 . r v t E8.00 4/1/2021 CI T Y O F K A L I S P E L L PO L I C E S E A R C H B U I L D I N G 1S T A V E W . KA L I S P E L L M T 5 9 9 0 1 ELECTRICAL SCHEDULES MIBJSJ PR O J E C T # : P r o j e c t N u m b e r OCCUPANCY SENSOR SCHEDULE TAG DESCRIPTION BASIS OF DESIGN POWER CONNECTION COVERAGE DELAY SENSITIVITY NOTESMANUFACTURER MODEL OS1 CEILING MOUNT DUAL TECH OCCUPANCY SENSOR NLIGHT NCM-6-RJB LOW VOLTAGE 1200 SF 20 MIN MAX PROVIDE NECESSARY NPP16 POWER PACK WITH DEVICE AS NEEDED. OS2 DUAL RELAY WALL SWITCH OCCUPANCY SENSOR NLIGHT NCM-10-RJB LOW VOLTAGE 500 SF 30 MIN MAX PROVIDE NECESSARY NPP16 POWER PACK WITH DEVICE AS NEEDED. OS3 OCCUPANCY SENSOR WALL SWITCH SENSOR SWITCH WSX 2P FAN-WH LINE VOLTAGE 20FT NA NA OS4 OCCUPANCY SENSOR WALL SWITCH SENSOR SWITCH WSX-WH LINE VOLTAGE 20FT NA NA ELECTRIC HEATER SCHEDULE TAG DESCRIPTION BASIS OF DESIGN MOUNTING WATTS VOLTAGE AMPS Ø POLE NOTESMANUFACTURER MODEL EUH-1 ELECTRIC UNIT HEATER CADET CSC101TW WALL 1100 W 120 V 9.2 A 1 1 NOTES: TOTAL EST. DEMAND:86.2 A RCPT 8700 VA 100.00% 8700 VA TOTAL CONN.:84.9 A LIGHTS 1225 VA 125.00% 1531 VA TOTAL EST. DEMAND:20681 VA HVAC 874 VA 100.00% 874 VA TOTAL CONN. LEAD:20375 VA HEAT 9576 VA 100.00% 9576 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS TOTAL AMPS:95.1 A 102.2 A TOTAL LOAD:11412 VA 12263 VA 41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42 39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40 37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38 35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36 33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34 31 S. GARAGE DOOR 101 20 A 1 800 VA 0 VA 1 20 A SPARE 32 29 SPARE 20 A 1 0 VA 1100 VA 1 20 A EUH-1 R.R.104 30 27 RCPT S. SHOP 101 20 A 1 540 VA 720 VA 1 20 A RCPT MEZ STORAGE 28 25 SPARE 20 A 1 0 VA 800 VA 1 20 A N. GARAGE DOOR 101 26 23 UH-2 S. SHOP 101 15 A 1 288 VA 360 VA 1 20 A RCPT S. UTILITY / MECH 103 24 21 SPARE 20 A 1 0 VA 720 VA 1 20 A RCPT EVIDENCE / STOR. 105 22 19 RCPT N. SHOP 101 20 A 1 900 VA 4500 VA 20 17 RCPT EVIDENCE / STOR. 105 20 A 1 540 VA 4500 VA 2 50 A DWH-1 UTILITY / MECH 103 18 15 MID. GARAGE DOOR 101 20 A 1 800 VA 816 VA 1 20 A H.O.A. / EF-1 SHOP 101 16 13 RCPT R.R. 104 20 A 1 360 VA 14 11 RCPT N. UTILITY / MECH 103 20 A 1 360 VA 688 VA 1 20 A LIGHTS/EF-2 SHOP 101 12 9 RCPT I.T. RACK 103 20 A 1 1800 VA 288 VA 1 15 A UH-1 N. SHOP 101 10 7 LIGHTS EVIDENCE / STOR. 105 20 A 1 131 VA 1100 VA 1 20 A EUH-1 UTILITY / MECH 103 8 5 LIGHTS MEZZANINE 20 A 1 105 VA 1100 VA 1 20 A EUH-1 EVIDENCE / STOR. 105 6 3 EF-3 EVIDENCE / STOR. 105 20 A 1 29 VA 75 VA 1 20 A LIGHTS UTILITY / MECH 103 4 1 EF-4 R.R. 104 20 A 1 29 VA 70 VA 1 20 A LIGHTS R.R. 104 2 CKT CIRCUIT DESCRIPTION TRIP POLE A B POLE TRIP CIRCUIT DESCRIPTION CKT NOTES: ENCLOSURE:NEMA 1 MCB RATING:225A MOUNTING:SURFACE WIRES:3 MAINS RATING:225A SUPPLY FROM:UTILITY MSD PHASES:1 MAINS TYPE:MCB LOCATION:UTILITY/MECH...VOLTS:120/240 A.I.C. RATING:10,000 AIC PANEL: P1 LIGHTING FIXTURE SCHEDULE TAG DESCRIPTION BASIS OF DESIGN MOUNTING VOLT WATTS LAMP NOTESMFR CATALOG SERIES COLOR TEMP LUMENS E1 CEILING EXIT LIGHT LITHONIA LES 1 R 120/277 EL N SD CEILING/SURFACE 120 V 5 W 90 MIN BATTERY BACKUP INCLUDED. L1 LED WRAPAROUND FIXTURE LITHONIA BLWP4-40L-ADSM-120-EZ1-LP840 SURFACE 120 V 35 W 4000K 4099 lm L1E LED WRAPAROUND FIXTURE LITHONIA BLWP4-40L-ADSM-120-EZ1-LP880 SURFACE 120 V 35 W 4000K 4099 lm BATTERY BACKUP INCLUDED. LB1 SUSPENDED LED LOW BAY FIXTURE LITHONIA MSL-10000LM-SBL-120-GZ10-40K-80CRI-CS1W- WH SURFACE 120 V 86 W 4000K 9798 lm LB1E SUSPENDED LED LOW BAY FIXTURE LITHONIA MSL-10000LM-SBL-120-GZ10-40K-80CRI-CS1W- WH SURFACE 120 V 86 W 4000K 9798 lm BATTERY BACKUP INCLUDED. W1 LED WRAPAROUND FIXTURE LITHONIA BLWP2-40L-ADSM-120-EZ1-LP830 WALL 120 V 17 W 3000K 1200 lm WP1 LED WALL PACK LITHONIA ARC1LED-P3-40K-MVOLT-E4WH-PE-DBLXD WALL 120 V 24 W 4000K 3021 lm WP2 DECORATIVE LED WALL SCONCE LITHONIA OLLWU LED-P1-40K-MVOLT-DDB WALL 120 V 24 W 4000K 500 lm FIXTURE TO BE EQUIPPED WITH EGRESS BATTERY BACKUP. PROVIDE AND INSTALL COMPATIBLE EMERGENCY REMOTE DRIVER. BASIS OF DESIGN: BODINE BSL17 SERIES. COORDINATE WITH MANUFACTURER TO ENSURE MAKE AND MODEL NUMBER IS CURRENT AND REMAINS APPLICABLE TO APPLICATION. M ONTANA No.71878PE PRO F E S S IONA L E N GINEER LICEN S E D MIKI IKEMOTO BACKUS A ADDENDUM 7-2-21 Com-Check Info: 9.4.1.1 -Automatic controls to shut off all building lighting installed: Occupancy sensors are installed in all areas. 9.4.1.2 -Indepent lighting controls installed per approved lighting plans and all manual controls are readily accessible and visible to occupants. 9.4.1.3 -Parking garage lighting is equipped with required lighting controls and daylight transition zone lighting. Not applicable. 9.4.1.4 -Primary sidelighted areas >=250 ft2 are equipped with required lighting controls. Not applicable. 9.4.1.5 -Enclosed spaces with daylight area under skylights and rooftop monitors >900 ft2 are equipped with required lighting. Not applicable. 9.4.1.6 -Separate lighting control devices for specific uses installed per approved lighting plans. Occupancy sensors, photocells, and digital controls are to be used for specific uses as shown. 9.4.1.7 -Automatic lighting controls for exterior lighting installed. Exterior lighting shall be controlled via photocell as indicated on drawings and in lighting fixture schedule Catalog #. 9.4.3 -Exterior grounds lighting over 100 W provides >60 lm/W unless on motion sensor of fixture is exempt from scope of code or from external LPD. Not exterior lighting fixtures are >60 lm/W. Code article is not applicable. 9.7 -Plans, specificiations, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical systems and equipment and documant where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers, and control devices. Exterior Lighting: Tradable Wattage 120W Main door/Back Door -Allowed 120W WP2 LED fixture -2 fixture @ 24W = 48W Total Proposed Wattage = 48W COMPLIES WITH ENERGY REQUIREMENTS. 4.2.2,9.4.4,9.7 -Plans, specificiations, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and documant where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers, and control devices. See lighting fixture schedule, occupancy sensor schedule and electrical sheets for device and fixture information. Interior Lighting: Warehouse (~1610 sq ft) Allowed Wattage -1063 L1/E LED fixture -10 fixtures @ 35W = 350W W1 LED fixture -1 fixture @ 17W = 17W LB1 LED low bay fixture -8 fixtures @ 86W = 688W Total Proposed Wattage = 1055W COMPLIES WITH ENERGY REQUIREMENTS. 8.7.1 -Furnished asbuilt drawings for electric power systems within 30 days of system acceptance. Contractor shall furnish asbuilts drawings for electric power systems within 30 days of system acceptance as required by code. 8.7.2 -Furnished O&M instructions for systems and equipment to the building owner or designated representative. Contractor shall provide programming instructions associated with digital lighting controls as required by code. 9.4.2 -Exit signs do not exceed 5 watts per face. Basis of design Exit sign is rated for 5W. Any lighting substitutions for Exit signs shall be <=5W. 9.6.2 -Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting. All lighting controls are automatically controlled and are separate from general lighting. A A