GENERAL CONDITIONS GENERAL NOTES
1. CONTRACTOR TO REVIEW AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO
COMMENCING WORK. ANY CONDITIONS NOT INDICATED ON CONTRACT DOCUMENTS ARE TO BE
REPORTED TO THE ARCHITECT PRIOR TO BEGINNING WORK.
2. CONTRACTOR TO CONTACT LOCAL UTILITIES, IF NECESSARY, SUBMIT ALL APPLICABLE PERMIT
DOCUMENTS, QUALIFICATIONS, ETC., AND BE RESPONSIBLE FOR ALL FEES ASSOCIATED WITH
PERMITS, UTILITY EXTENSIONS, TAP-INS, ETC.
3. THE CONTRACTOR SHALL REMOVE ALL DEBRIS AS A RESULT OF THIS PROJECT.
4. THE CONTRACTOR SHALL SCHEDULE HIS WORK AND MATERIAL AND EQUIPMENT DELIVERIES SO
AS NOT TO INTERFERE WITH THE DAILY OPERATIONS OF THE REMAINDER OF THE FACILITY.
5. THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, EQUIPMENT, FIXTURES, ETC. FROM
DAMAGE DURING THE COURSE OF CONSTRUCTION.
6. ALL SURFACES AND/OR FINISHES DAMAGED AS A RESULT OF AND ADJACENT TO THE WORK
SHALL BE REPAIRED AND FINISHED TO THEIR ORIGINAL CONDITION.
7. EACH SUBCONTRACTOR IS RESPONSIBLE TO COORDINATE AND SCHEDULE HIS WORK WITH THE
GENERAL CONTRACTOR AND ALL OTHER SUBCONTRACTORS WHOSE WORK WILL BE AFFECTED.
8. USE DETAILS MARKED 'TYPICAL' (TYP) WHEREVER APPLICABLE.
9. ALL ITEMS REQUIRED BY THE DRAWINGS AND SPECIFICATIONS SHALL BE PERFORMED IN A
WORKMANLIKE MANNER BY PERSONS SKILLED IN THEIR RESPECTIVE TRADE AND WHO NORMALLY
PARTICIPATE IN THE WORK OF THAT TRADE.
10. WORDS WHICH HAVE WELL KNOWN TECHNICAL OR TRADE MEANINGS ARE USED IN THE
DRAWINGS AND SPECIFICATIONS IN ACCORDANCE WITH SUCH RECOGNIZED MEANINGS.
11. WITHIN THE DRAWINGS AND RELATED SPECIFICATIONS THERE SHALL BE THE FOLLOWING
PRECEDENCE:
A) ADDENDA OR MODIFICATIONS TO THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE OVER
THE ORIGINAL, WHEN ISSUED BY THE ARCHITECT.
B) SPECIFICATIONS SHALL TAKE PRECEDENCE OVER DRAWINGS.
C) WITHIN THE DRAWINGS THE LARGER SCALE TAKES PRECEDENCE OVER THE SMALLER, FIGURED
DIMENSIONS OVER SCALED AND NOTED MATERIALS OVER GRAPHIC INDICATIONS.
12. THE ARCHITECT OR ENGINEER SHALL BE IN THE FIRST INSTANCE THE SOLE INTERPRETER OF THE
DRAWINGS AND SPECIFICATIONS WITH REGARD TO THEIR MEANING OR INTENT.
13. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS,
TECHNIQUES AND PROCEDURES.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ASPECTS OF SAFETY DURING BUILDING
CONSTRUCTION.
THE GENERAL CONTRACTOR IS TO GUARANTEE ALL WORK
INCLUDING WORK DONE BY SUBCONTRACTORS FOR A PERIOD
COMMENCING WITH THE SUBSTANTIAL COMPLETION OF THE
CONTRACT. ALL GUARANTEES/WARANTIES BEGIN AT SUBSTATIAL
COMPLETION AND EXTEND FOR THE IDENTIFIED DURATION FROM
FINAL ACCEPTANCE. BUILDING 1 YEAR, ROOF 2 YEARS
ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL GOV-
ERNING CODES, ORDINANCES AND AUTHORITIES HAVING
JURISDICTION. GENERAL CONTRACTOR IS RESPONSIBLE FOR
OBTAINING AND PAYING FOR ALL REQUIRED BUILDING PERMITS.
THE GENERAL CONTRACTOR IS TO HAVE A FULL TIME QUALIFIED
SUPERVISOR ON THE SITE AT ALL TIMES WHILE WORK IS BEING
PERFORMED.
ALL MATERIAL SPECIFIED IS TO BE NEW & INSTALLED IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND
SPECIFICATIONS. GENERAL CONTRACTOR IS TO CONSTRUCT
PROJECT IN ACCORDANCE WITH THE DOCUMENTS. ANY DEVIATION
FROM THE INTENT OF THE DOCUMENTS, WITHOUT ARCHITECT OR
ENGINEER'S APPROVAL, ARE AT THE CONTRACTOR'S OWN RISK AND
MAY RESULT IN THE WORK BEING DONE OVER AT CONTRACTOR'S
EXPENSE (MATERIALS AND LABOR).
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
T0.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
TITLE SHEET
MSHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
POLICE SEARCH BUILDING
PROJECT INFORMATION:
SHEET INDEX
NUMBER NAME ISSUE DATE REVISION
TITLE
T0.00 TITLE SHEET 4/1/2021
T0.10 CODE REVIEW 4/1/2021
CIVIL
C0.10 EXISTING SITE SURVEY AND DEMO PLAN 4/1/2021
C1.10 COMBINED SITE AND UTILITY PLAN 4/1/2021
ARCHITECTURAL
A0.0 ARCHITECTURAL NOTES 4/1/2021
A1.00 LEVEL 1 FLOOR PLAN 4/1/2021
A1.20 MEZZANINE LEVEL PLAN 4/1/2021
A2.00 LEVEL 1 REFLECTED CEILING PLAN 4/1/2021
A2.10 MEZZANINE LEVEL REFLECTED CEILING PLAN 4/1/2021
A3.00 ROOF PLAN 4/1/2021
A3.10 ROOF DETAILS 4/1/2021
A4.00 EXTERIOR ELEVATIONS 4/1/2021
A5.00 BUILDING SECTIONS 4/1/2021
A6.00 WALL SECTIONS 4/1/2021
A7.00 FLOOR FINISH PLAN 4/1/2021
A7.10 INTERIOR ELEVATIONS 4/1/2021
A8.00 DOOR AND WINDOW SCHEDULE AND DETAILS 4/1/2021
STRUCTURAL
S0.00 STRUCTURAL NOTES 4/1/2021
S1.00 FOUNDATION PLAN 4/1/2021
S2.00 MEZZANINE FLOOR FRAMING PLAN 4/1/2021
S2.10 ROOF FRAMING PLAN 4/1/2021
S3.00 SHEAR PLAN 4/1/2021
S4.00 FOUNDATION DETAILS 4/1/2021
S4.10 FRAMING DETAILS 4/1/2021
S4.20 SHEAR DETAILS 4/1/2021
MECHANICAL
M0.00 MECHANICAL TITLE SHEET 4/1/2021
M1.10 LEVEL 1 HVAC PLAN 4/1/2021
M7.00 MECHANICAL DETAILS 4/1/2021
M8.00 MECHANICAL SCHEDULES 4/1/2021
PLUMBING
P0.00 PLUMBING TITLE SHEET 4/1/2021
P1.00 UNDERFLOOR PLUMBING PLAN 4/1/2021
P1.10 LEVEL 1 PLUMBING SUPPLY PLAN 4/1/2021
P2.10 LEVEL 1 WASTE & VENT PLAN 4/1/2021
P3.00 ROOF PLUMBING PLAN 4/1/2021
P7.00 PLUMBING DETAILS 4/1/2021
P8.00 PLUMBING SCHEDULES 4/1/2021
ELECTRICAL
E0.00 ELECTRICAL TITLE SHEET 4/1/2021
E0.10 ELECTRICAL SITE PLAN 4/1/2021
E1.10 LEVEL 1 LIGHTING PLAN 4/1/2021
E1.20 LEVEL 2 LIGHTING PLAN 4/1/2021
E2.10 LEVEL 1 POWER AND SYSTEMS PLAN 4/1/2021
E2.20 LEVEL 2 POWER AND SYSTEMS PLAN 4/1/2021
E5.00 ELECTRICAL DIAGRAMS 4/1/2021
E7.00 ELECTRICAL DETAILS 4/1/2021
E8.00 ELECTRICAL SCHEDULES 4/1/2021
S I T E
OWNER/DEVELOPER DESIGN PROFESSIONAL BUILDING DEPARTMENT
KALISPELL BUILDING DEPARTMENT
201 1ST AVE E
KALISPELL, MT 59901
ATTN: JEFF CLAWSON
EMAIL: JCLAWSON@KALISPELL.COM
TEL: (406) 785-7730
JACKOLA ENGINEERING & ARCHITECTURE, P.C.
2250 HWY. 93 SOUTH
PO BOX 1134
KALISPELL, MT 59903
ARCHITECT: MELISSA STEINER
CIVIL ENGINEER: ERIK GARBERG
STRUCTURAL ENGINEER: ERIK GARBERG
MECHANICAL ENGINEER: COURTNEY CARRIER
SURVEYOR: SAM DUGUAY
CITY OF KALISPELL
312 1ST AVE E
KALISPELL, MT 59901
ATTN: DOUG OVERMAN
EMAIL: doverman@kalispell.com
TEL: (406) 253.4633
CITY OF KALISPELL
1ST AVE WEST
KALISPELL, MT 59901
SITE LOCATION:
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
A
A
1 1
C
C
4 4
12" MIN
EXIT
EATD = 75'-0"
FEC
STORAGE / MECH:
380 SF/300 = 2 OCCS
VEHICLE STORAGE/BUSINESS USE:
1180 SF/150 = 8 OCCS
HAND RAIL EXTENSION
OCCUPANCY: S-1
CPET (COMMON PATH
OF EGRESS TRAVEL)
EATD (EXIT ACCESS
TRAVEL DISTANCE)
30"
48"
ø 6 0 "
TURN AROUND SPACE
CIRCULAR T-SHAPE
CLEAR FLOOR SPACE
LEGEND
BLOCKING
HORIZONTALLY @ TOP &
BOTTOM OF CABINET
5/8" TYPE"X" GWB
ALL SIDES OF
RECESSED AREA
RECESSED CABINET
TRIM BY INTERIORS
A
A
1
C
C
4
B
B
MOST REMOTE POINT
STORAGE:
450 SF/300 = 2 OCCS
HAND RAIL EXTENSION
12"
12"
HA
N
D
R
A
I
L
E
X
T
E
N
S
I
O
N
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
T0.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
CODE REVIEW
MKSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
BUILDING REQUIREMENTS FROM THE
INTERNATIONAL BUILDING CODE 2018
USE AND OCCUPANCY CLASSIFICATION (CHAPTER 3):
WAREHOUSE/STORAGE: S-1 (MOTOR VEHICLE GARAGE/STORAGE)
(NOT A VEHICLE REPAIR GARAGE. VEHICLES WILL NOT BE RUNNING WHILE INSIDE BUILDING)
SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY (CHAPTER 4):
SECTION 406: MOTOR VEHICLE STORAGE
FLOOR SURFACE TO BE CONCRETE OR OTHER SIMILIAR NON-ABSORBANT MATERIAL AND SLOPED TO DRAIN.
SLIP RESISTANT NON-ABSORBANT FINISH COMPLYING WITH ASTM E648 OR NFPA 253 IS PERMITTED.
GENERAL BUILDING HEIGHTS AND AREAS (CHAPTER 5):
CONSTRUCTION TYPE: VB
BUILDING HEIGHT ALLOWED: 40FT (ACTUAL: 23FT)
ALLOWED STORIES: 1 (ACTUAL: 1)
ALLOWED AREA: 9,000 SF (ACTUAL: 1610SF)
503.1.2 TWO OR MORE BUILDINGS ON THE SAME LOT CAN BE CONSIDERED PORTIONS OR AGGREGRATES OF A
SINGLE BUILDING IF BUILDING HEIGHT, STORAGE AND AREAS ARE WITHIN THE LIMITATION REQUIREMENTS.
TYPE OF CONSTRUCTION (CHAPTER 6): VB
MINIMUM FIRE SEPARATION DISTANCE: >10FT = 0 HR RATING
(ACTUAL DISTANCE TO EXISTING BUILDING ON SAME LOT: 12'-0") - NO SEPERATION REQUIRED
FIRE AND SMOKE PROTECTION FEATURES (CHAPTER 7): N/A
INTERIOR FINISHES (CHAPTER 8):
INTERIOR EXIT STAIRWAYS/RAMPS, EXIT PASSAGEWAYS (IF PRESENT): CLASS B
CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS/RAMPS (IF PRESENT): CLASS B
ROOMS AND ENCLOSED SPACES: CLASS C
FIRE PROTECTION SYSTEMS (CHAPTER 9):
TABLE: 903.2 - FIRE AREA < 2,500 SF = NO FIRE SPRINKLER REQUIRED.
906 - PORTABLE FIRE EXTINGUISHERS
TABLE 906.3 - PROVIDE (1) 2-A FIRE EXTINGUISHER, CENTRALLY LOCATED.
MEANS OF EGRESS (CHAPTER 10):
1004.1.2 OCCUPANT LOAD: 12 OCCUPANTS TOTAL (SEE PLAN)
1005.3.2 EGRESS COMPONENTS (OTHER THAN STAIRS) SHALL BE SIZED BASED ON 0.2 INCH PER OCCUPANT.
468*0.2=93.6" OF EXIT WIDTH
1005.5 DISTRIBUTION OF EGRESS CAPACITY: WHERE MORE THAN ONE EXIT IS REQUIRED, THE MEANS OF
EGRESS SHALL BE CONFIGURED SUCH THAT THE LOSS OF ANY ONE EXIT SHALL NOT REDUCE THE AVAILABLE
CAPACITY TO LESS THAN 50% OF REQUIRED CAPACITY
1014.2.4.2.1-4 EGRESS THROUGH INTERVENING SPACES:
1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH ADJOINING OR INTERVENING ROOMS OR
AREAS, EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE ACCESSORY TO ONE
OR THE OTHER AND PROVIDE A DISCERNABLE PATH OF EGRESS TRAVEL TO AN EXIT.
2. MEANS OF EGRESS SHALL NOT PASS THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
3. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS, OR SPACES USED FOR SIMILAR
PURPOSES.
COMMON PATH OF EGRESS TRAVEL: S-1 (NON-SPRINKLED): 100' MAX (ACTUAL 75') = 1 REQUIRED EXIT
1009 ACCESSIBLE MEANS OF EGRESS -
MEZZANINE FOR EMPLOYEES ONLY AND NOT REQUIRED TO BE ACCESSIBLE - NO ACCESSIBLE MEANS OF EGRESS
REQUIRED FROM MEZZANINE.
1011.2 - EXCEPTION 1: WIDTH OF STAIRWAY TO BE NOT LESS THAN 36"
ACCESSIBILITY (CHAPTER 11):
1104.1 ACCESSIBLE ROUTES ARE REQUIRED FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
PARKING/LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE BUILDING ENTRANCE SERVED.
1104.3 WHEN A BUILDING IS REQUIRED TO BE ACCESSIBLE, AN ACCESSIBLE ROUTE SHALL BE PROVIDED TO
EACH PORTION OF THE BUILDING.
EXCEPTIONS: 1104.4.1 EMPLOYEE WORK SPACES. EXCEPTION 1 - MEZZANINES < 3000 SF
1109.2 TOILET AND BATHING FACILITIES SHALL BE ACCESSIBLE. AT LEAST ONE OF EACH FIXTURE TYPE SHALL BE
ACCESSIBLE.
INTERIOR ENVIRONMENT (CHAPTER 12):
1202 - VENTILATION: CROSS VENTILATION IN ENCLOSED ATTIC REQUIRED. NET FREE VENTILATION SHALL BE
1/150 OF THE AREA VENTILATED IN CLIMATE ZONE 6, USING GABLE END VENTS ON BOTH END WALLS.
TOTAL ROOF AREA= 1850 SF
NET-FREE VENTILATED AREA ≥ 1/150 AREA OF VENTILATED SPACE
TOTAL VENTILATION REQUIRED = 1850 SF/150 =12.33 SF
12.33 SF ~~ 12.50 SF/ 2 GABLE END VENTS = 6.25 SF VENTILATION PER GABLE END.
1208 - ATTIC SPACES: ACCESS NOT LESS THAN 20" X 30" INTO ATTIC SPACE WHERE HEAD ROOM IS GREATER
THAN 30", IS REQUIRED.
1208 INTERIOR SPACE DIMENSIONS: MINIMUM CEILING HEIGHT IS 7'-6".
1210.2.1 TOILET AND BATHROOM FINISHES: FLOORING SHALL BE SMOOTH, HARD, NONABSORBENT AND
EXTEND UPWARDS ONTO THE WALLS NOT LESS THAN 4". WALLS WITHIN 2' OF SERVICE SINKS, URINALS, AND
WATER CLOSETS SHALL HAVE A SMOOTH, HARD NONABSORBENT SURFACE TO A HEIGHT OF 4' ABOVE THE
FLOOR.
ENERGY EFFICIENCY (CHAPTER 13):
2012 IECC
WALL R-VALUE: (WOOD FRAMED) R-21 (MT ARM)
ROOF: (INSULATION IN ATTIC SPACE) R-49
UNHEATED SLAB: R-10 FOR 24" BELOW SLAB
WINDOW U-VALUE:
(FIXED OR OPERABLE)U=- 0.32
SHGC: NA (MT ARM)
SWINGING: U-0.37
ROLL UP: R-4.75
(ENTRANCE DOORS) 0.77
GLASS AND GLAZING (CHAPTER 24):
2406.4 HAZARDOUS LOCATIONS:
1. GLAZING IN DOORS
2. GLAZING WITHIN 2' HORIZONTALLY OF A DOOR WITH EXPOSED EDGE OF GLAZING LESS
THAN 60" ABOVE WALKING SURFACE.
3. GLAZING IN WINDOWS MEETING ALL OF THE FOLLOWING CONDITIONS: INDIVIDUAL PANE
GREATER THAN 9 SF, BOT EDGE OF GLAZING LESS THAN 18" AFF, TOP EDGE OF GLAZING GREATER THAN 36"
ABOVE THE FLOOR, AND WALKING SURFACE WITHIN 36" HORIZONTALLY FROM THE PLANE OF GLAZING.
PLASTIC (CHAPTER 26):
2603.4 THERMAL BARRIER: FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
APPROVED THERMAL BARRIER OF 1/2" GYPSUM WALL BOARD OR APPROVED MATERIAL MEETING
TEMPERATURE TRANSMISSION AND FIRE TEST AND INTEGRITY FIRE TEST OF NFPA 275.
PLUMBING SYSTEMS (CHAPTER 29):
PLUMBING FIXTURE COUNT:
OCCUPANT LOAD: STORAGE/BUSINESS = 12 OCCUPANTS TOTAL
1 WC/25 OCCUPANTS = 1 RESTROOM REQUIRED (1 RESTROOM PROVIDED)
3/16" = 1'-0"2 LEVEL 1 CODE REVIEW PLAN
1" = 1'-0"3 FIRE EQUIP. CABINET WALL RECESS
3/16" = 1'-0"1 MEZZANINE LEVEL CODE REVIEW PLAN
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
C0.00 GENERAL CIVIL INFORMATION
INDEX OF DRAWINGS
SHEET #SHEET TITLE
ABBREVIATIONS
C0.10 EXISTING SITE SURVEY AND DEMO PLAN
C1.10 SITE AND UTILITY PLAN
GENERAL NOTES
A
AHJ AGENCY HAVING JURISDICTION
B
BLDG BUILDING
BVCE BEGIN VERTICAL CURVE ELEVATION
BVCS BEGIN VERTICAL CURVE STATION
C
CATV CABLE TV
COS CERTIFICATE OF SURVEY
CJ CONSTRUCTION JOINT
D
DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DIV DIVISION
DWG DRAWING
E
E EAST
EA EDGE OF ASPHALT
ELEC ELECTRIC
ELEV ELEVATION
EQ EQUAL
EQUIP EQUIPMENT
EVCE END VERTICAL CURVE ELEVATION
EVCS END VERTICAL CURVE STATION
EXIST EXISTING
F
FO FIBER OPTIC
G
G GAS
H
HT HEIGHT
HORIZ HORIZONTAL
HR HOUR
I
IBC INTERNATIONAL BUILDING CODE
M
MAX MAXIMUM
MIN MINIMUM
MPWSS MT PUBLIC WORKS STANDARD
SPECIFICATIONS
N
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
O
OPP OPPOSITE
OHP OVERHEAD POWER
P
PVI POINT OF VERTICAL INTERSECTION
PROP PROPERTY
R
REF REFERENCE
REQ'D REQUIRED
REV REVISION
ROW RIGHT-OF-WAY
S
SCH SCHEDULE
SIM SIMILAR
S SOUTH
SPEC SPECIFICATION
STD STANDARD
T
TYP TYPICAL
TBC TOP BACK OF CURB
U
UP UNDERGROUND POWER
UT UNDERGROUND TELEPHONE
UNO UNLESS NOTED OTHERWISE
V
VERT VERTICAL
W
w/WITH
LEGEND
X X X
UP
TELEPHONE PEDESTAL
FENCE
UNDERGROUND POWER
TRAFFIC SIGN
UTILITY POLE
WATER GATE VALVE
W WATER MAIN
TREE LINE
UT UNDERGROUND TELEPHONE
DECIDUOUS TREE
OHP OVERHEAD POWER
SD STORM DRAIN
SS SANITARY SEWER MAIN
3031.40
3040.38(e)
SEWER MANHOLE
CATCH BASIN
FIRE HYDRANT
CAP WITH THRUST BLOCK
STORM MANHOLE
EXISTING CONTOUR
EXISTING SPOT GRADE
DESIGN SPOT GRADE
TRANSFORMER
TBC DESIGN SPOT GRADE(3031.90)
DESIGN CONTOUR
WATER METER PIT
ELECTRICAL JUNCTION BOX
M
(SD)(SD)EXISTING STORM DRAIN
(SS)(SS)EXISTING SANITARY SEWER
(UT)(UT)EXISTING UNDERGROUND PHONE
(W)(W)EXISTING WATER
(UP)EXISTING UNDERGROUND POWER
(G)(G)EXISTING GAS
(FO)EXISTING FIBER OPTIC
WATER CURB STOP
THRUST BLOCK
WATER TEE
IRR IRRIGATION VALVE BOX
FROST FREE YARD HYDRANTYHD
3030
3025EXISTING BUILDING
EXISTING ASPHALT
EXISTING SIDEWALK
(OHP)EXISTING OVERHEAD POWER
EXISTING PROPERTY LINE
DRAINAGE SWALE
PROPOSED ASPHALT
PROPOSED BUILDING
PROPOSED SIDEWALK
STANDARD CURB AND GUTTER
TOP OF POND
SPILL CURB AND GUTTER
PROPOSED PROPERTY LINE
DRIVE OVER CURB AND GUTTER
CURB INLET
STORM DRAIN DRYWELL
TV TV UNDERGROUND CABLE
G G GAS MAIN
fdc FIRE DEPARTMENT CONNECTION
SS
co CLEAN OUT
PIPE CAP
SD
DW
CB
LIGHT POLE
T
E
C
J
CABLE PEDESTAL
ELECTRICAL PEDESTAL
(TV)(TV)EXISTING UNDERGROUND CABLE
FO FO UNDERGROUND FIBER OPTIC
EXISTING LIGHT POLE
1.ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL GOVERNING CODES, ORDINANCES AND AUTHORITIES
HAVING JURISDICTION. GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL REQUIRED
PERMITS. THE GENERAL CONTRACTOR IS TO HAVE A FULL TIME QUALIFIED SUPERVISOR ON THE SITE AT ALL TIMES
WHILE WORK IS BEING PERFORMED.
2.ALL MATERIAL SPECIFIED IS TO BE NEW AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS
AND SPECIFICATIONS. GENERAL CONTRACTOR IS TO CONSTRUCT PROJECT IN ACCORDANCE WITH THE DOCUMENTS.
ANY DEVIATION FROM THE INTENT OF THE DOCUMENTS, WITHOUT ENGINEER'S APPROVAL, ARE AT THE
CONTRACTOR'S OWN RISK AND MAY RESULT IN THE WORK BEING DONE OVER AT CONTRACTOR'S EXPENSE
(MATERIALS AND LABOR).
3.CONTRACTOR TO REVIEW AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO COMMENCING WORK.
ANY CONDITIONS NOT INDICATED ON CONTRACT DOCUMENTS ARE TO BE REPORTED TO THE ENGINEER PRIOR TO
BEGINNING WORK.
4.THE CONTRACTOR SHALL REMOVE ALL DEBRIS AS A RESULT OF THIS PROJECT.
5.THE CONTRACTOR SHALL SCHEDULE HIS WORK AND MATERIAL AND EQUIPMENT DELIVERIES SO AS NOT TO
INTERFERE WITH THE DAILY VEHICLE TRAFFIC.
6.THE CONTRACTOR SHALL PROTECT EXISTING SITE IMPROVEMENTS, FACILITIES, EQUIPMENT, FIXTURES, ETC. FROM
DAMAGE DURING THE COURSE OF CONSTRUCTION.
7.ALL SURFACES AND/OR FINISHES DAMAGED AS A RESULT OF, AND ADJACENT TO THE WORK, SHALL BE REPAIRED
AND FINISHED TO EQUAL OR BETTER THAN ORIGINAL CONDITION.
8.ALL ITEMS REQUIRED BY THE DRAWINGS AND SPECIFICATIONS SHALL BE PERFORMED IN A WORKMANLIKE MANNER
BY PERSONS SKILLED IN THEIR RESPECTIVE TRADE AND WHO NORMALLY PARTICIPATE IN THE WORK OF THAT
TRADE.
9.THE ENGINEER SHALL BE IN THE FIRST INSTANCE THE SOLE INTERPRETER OF THE DRAWINGS AND SPECIFICATIONS
WITH REGARD TO THEIR MEANING OR INTENT.
10.CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES AND
PROCEDURES. CONTRACTOR SHALL COORDINATE WORK WITH OWNER TO ALLOW FOR CONTINUED OPERATION OF
THE EXISTING FACILITY WHERE APPLICABLE.
11.CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ASPECTS OF SAFETY AND TRAFFIC CONTROL DURING CONSTRUCTION.
12.CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING NECESSARY PERMITS INCLUDING, BUT NOT LIMITED TO,
SWPPP.
13.ALL WORK IS TO BE COMPLETED PER THE CURRENT EDITION OF MONTANA PUBLIC WORKS STANDARD
SPECIFICATIONS (MPWSS) AND MOST CURRENT CITY OF KALISPELL CODE.
RD RD ROOF DRAIN
C1.30 SITE GRADING PLAN
C2.00 GENERAL NOTES AND DETAILS
C2.01 GENERAL NOTES AND DETAILS
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN:CHECKED:
info@jackola.com jackola.com
PR
O
J
E
C
T
#
:
E
No.14108 PE
T
L
CE S EN DI
P
RIKD.GARBERG
A
NANOM**
F
O
R
ISS
E
LANO E
REENIGN
Z:
\
C
l
i
e
n
t
F
i
l
e
s
\
2
0
2
0
\
C
i
t
y
o
f
K
a
l
i
s
p
e
l
l
\
2
0
0
2
0
4
P
o
l
i
c
e
S
e
a
r
c
h
B
u
i
l
d
i
n
g
\
6
D
r
a
w
i
n
g
s
\
1
A
u
t
o
c
a
d
\
C
O
K
_
P
S
B
_
C
0
.
0
0
.
d
w
g
FOR PERMIT
C0.0020
0
2
0
4
4/1/2021
EDGJAC
GENERAL CIVIL
INFORMATION
KA
L
S
I
P
E
L
L
M
T
5
9
9
0
1
1S
T
A
V
E
W
.
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
GM
GM
SS
CB
CB
CB
SD
6" PVC
SD
CB
CB
W
SD
XSDCB-1
XSDMH-01
XSDCB-02
XOS-01
XSDCB-03
XSSMH-02
C
C
EM
CP
#
2
CP
#
5
CP
#
4
CP
#
3
CP
#
1
6"
S
T
O
R
M
P
V
C
8" ST
O
R
M
P
V
C
8" STORM P
V
C
6
"
S
T
O
R
M
P
V
C
6
"
S
T
O
R
M
P
V
C
4"
S
T
O
R
M
P
V
C
30" SEWER RCP
30" SEWER RCP
30" SEWER RCP
EXISTINGBUILDING
EXISTINGBUILDING
29
3
0
2930
2
9
3
0
2930
2
9
3
0
2931
29
3
1
293
1
2
1
1
POINT COORDINATE TABLE
POINT
1
2
3
5
NORTHING
1470504.07
1470586.48
1470358.74
1470571.83
EASTING
795854.26
795857.86
795844.96
795788.25
ELEVATION
2930.63
2930.98
2930.26
2930.62
DESCRIPTION
NAIL
NAIL
NAIL
NAIL
BASIS OF SURVEY:
BASIS OF BEARINGS IS PER CITY OF KALISPELL UTILITY MAP UTILZING
SEWER MANHOLES XSS-1 & XSS-2 AS A BASIS.
ELEVATION DATUM IS PER CITY OF KALISPELL UTILITY MAP ELEVATION
AT SEWER MANHOLE XSS-2.
COORDINATE SYSTEM IS PER CITY OF KALISPELL UTILITY MAP UTILIZING
SEWER MANHOLES XSS-1 & XSS-2 AS A BASIS.
SURVEY NOTES:
1.UTILITIES ARE SHOWN BASED ON THE SITE SURVEY
PERFORMED BY JACKOLA ENGINEERING AND ARCHITECTURE
ON 02/04/2020. UNDERGROUND CABLE, GAS, AND ELECTRIC
UTILITIES WERE SURVEYED BASED ON UTILITY MARKINGS
PROVIDED BY OTHERS. OVERHEAD POWER WAS MARKED
BASED ON OBSERVABLE POLES AND WIRES. SEWER, WATER,
AND STORM ON FIRST AVE. WEST WERE NOT MARKED PRIOR
TO THE FIELD SURVEY. THESE UTILITIES ARE SHOWN AS
APPROXIMATE AND ARE BASED ON OBSERVABLE MANHOLES,
HYDRANTS, AND VALVES AS WELL AS GIS DRAWINGS PROVIDED
BY THE CITY OF KALISPELL.
2.PRIVATE UTILITIES WERE NOT LOCATED PRIOR TO THE FIELD
SURVEY.
DEMO NOTES:
1.NEATLY SAWCUT, REMOVE, AND PROPERLY DISPOSE OF
ASPHALT.
2.LOCATION OF PROPOSED BUILDING FOOTPRINT SHOWN FOR
REFERENCE.
#
SEWER STRUCTURE TABLE:
XSSMH-01
RIM: 2931.25'
IE OUT: 2925.74'
XSSMH-02
RIM: 2929.89'
IE IN:2923.84'
STORM STRUCTURE TABLE:
XSDCB-01
RIM: 2929.94'
XSDCB-02
RIM: 2930.17'
IE OUT:2926.34'
XSDCB-03
RIM: 2929.65'
IE IN:2925.88'
XSDMH-01
RIM: 2930.40'
XOS-01
RIM: 2930.21'
IE OUT:2927.38'
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN:CHECKED:
info@jackola.com jackola.com
PR
O
J
E
C
T
#
:
E
No.14108 PE
T
L
CE S EN DI
P
RIKD.GARBERG
A
NANOM**
F
O
R
ISS
E
LANO E
REENIGN
Z:
\
C
l
i
e
n
t
F
i
l
e
s
\
2
0
2
0
\
C
i
t
y
o
f
K
a
l
i
s
p
e
l
l
\
2
0
0
2
0
4
P
o
l
i
c
e
S
e
a
r
c
h
B
u
i
l
d
i
n
g
\
6
D
r
a
w
i
n
g
s
\
1
A
u
t
o
c
a
d
\
C
O
K
_
P
S
B
_
C
0
.
1
0
.
d
w
g
FOR PERMIT
C0.1020
0
2
0
4
4/1/2021
EDGJAC
EXISTING SITE
SURVEY AND
DEMO PLAN
KA
L
S
I
P
E
L
L
M
T
5
9
9
0
1
1S
T
A
V
E
W
.
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
EXISTING SITE SURVEY AND DEMO PLAN11" = 10'5-5 10 20
SCALE: 1" =
0
10'
ADDENDUM --/--/--A
REVISION --/--/--1
GM
GM
SS
CB
CB
CB
6" PVC
SD
CB
CB
W
SD
XSDCB-1
XSDMH-01
XSDCB-02
XOS-01
XSDCB-03
XSSMH-02
C
C
EM
CP
#
2
CP
#
5
CP
#
4
CP
#
3
CP
#
1
8" ST
O
R
M
P
V
C
8" STORM P
V
C
6
"
S
T
O
R
M
P
V
C
6
"
S
T
O
R
M
P
V
C
8" STORM PVC
4"
S
T
O
R
M
P
V
C
30" SEWER RCP
30" SEWER RCP
30" SEWER RCP
EXISTINGBUILDING
EXISTINGBUILDING
29
3
0
2930
2
9
3
0
2930
2
9
3
0
2931
29
3
1
293
1
NEW BUILDING
FF: 2930.8'
W
W
co
w
UPUPUPUPUP
UP
UPUP
UP
UP
FO
FO
FO
FO
EM
GGGGGGGGGGGGGGGG
G
G
CB
GM
SD
SD
SD
S
D
1
2
3
4
5
7
9
10
11
6
11
10 10 10
10
10
12
GM
GM
SS
SD
W
SD
XOS-01
XSSMH-02
C
EM
CP
#
4
8" STORM PV
C
4"
S
T
O
R
M
P
V
C
30" SEWER RCP
30" SEWER RCP
EXISTINGBUILDING
29
3
0
2930
2
9
3
0
2930
NEW BUILDING
FF: 2930.8'
co
w
UPUP
UP
FO
EM
GGGGGGGGGGGGG
G
CB
GM
SD
1
2
3
4
8
5
7
9
10
11
6
11
10 10 10
10
10
12
KEYNOTES:
1.1" WATER SERVICE.
2.WATER METER PIT PER DTL. 3/C2.00.
3.4" SEWER SERVICE PER DTL. 4/C2.00.
4.SANITARY SEWER CLEANOUT PER DTL. 5/C2.00.
5.4" STORM DRAIN.
6.NEW STORM CATCH BASIN PER DTL. 6/C2.00.
7.3/4" GAS WITH GAS METER.
8.NATURAL GAS SERVICE, COORDINATE WITH UTILITY.
9.3" UNDERGROUND POWER WITH ELECTRIC METER.
10.NEW BOLLARD PER DTL. 7/C2.00
11.NEW 5" CONCRETE SLAB.
12.2" CONDUIT FOR FUTURE COMMUNICATION
CONNECTION.
GENERAL NOTES:
1.PATCH ASPHALT AS REQUIRED FOR NEW UTILITY
CONNECTIONS.
2.CONTRACTOR TO FIELD VERIFY ELEVATIONS AND
NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO
INSTALLATION.
#
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN:CHECKED:
info@jackola.com jackola.com
PR
O
J
E
C
T
#
:
E
No.14108 PE
T
L
CE S EN DI
P
RIKD.GARBERG
A
NANOM**
F
O
R
ISS
E
LANO E
REENIGN
Z:
\
C
l
i
e
n
t
F
i
l
e
s
\
2
0
2
0
\
C
i
t
y
o
f
K
a
l
i
s
p
e
l
l
\
2
0
0
2
0
4
P
o
l
i
c
e
S
e
a
r
c
h
B
u
i
l
d
i
n
g
\
6
D
r
a
w
i
n
g
s
\
1
A
u
t
o
c
a
d
\
C
O
K
_
P
S
B
_
C
1
.
1
0
.
d
w
g
FOR PERMIT
C1.1020
0
2
0
4
4/1/2021
EDGJAC
COMBINED SITE
AND UTILITY
PLAN
KA
L
S
I
P
E
L
L
M
T
5
9
9
0
1
1S
T
A
V
E
W
.
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
COMBINED SITE AND UTILITY PLAN11" = 10'5-5 10 20
SCALE: 1" =
0
10'
ADDENDUM --/--/--A
REVISION --/--/--1
UTILITY CONNECTION PLAN21" = 30'15-15 30 60
SCALE: 1" =
0
30'
GM
GM
SS
CB
CB
CB
SD
6" PVC
SD
CB
CB
W
SD
XSDCB-1
XSDMH-01
XSDCB-02
XOS-01
XSDCB-03
XSSMH-02
C
C
EM
CP
#
2
CP
#
5
CP
#
4
CP
#
3
CP
#
1
6"
S
T
O
R
M
P
V
C
8" ST
O
R
M
P
V
C
8" STORM P
V
C
6
"
S
T
O
R
M
P
V
C
6
"
S
T
O
R
M
P
V
C
4"
S
T
O
R
M
P
V
C
30" SEWER RCP
30" SEWER RCP
30" SEWER RCP
EXISTINGBUILDING
EXISTINGBUILDING
NEW BUILDING
FF: 2930.8'
CB
2930
2930
2930
29312931293129312931
29
3
1
293
1
2930
293
1
293
0
.
8
0
293
0
.
8
0
293
0
.
8
0
293
0
.
8
0
29
3
0
.
3
0
-1
0
.
3
%
-3.5%
-3
.
3
%
29
3
0
.
6
6
29
3
0
.
6
6
293
0
.
6
8
29
3
0
.
6
8
29
3
0
.
1
5
293
0
.
4
0
2
9
3
0
.
1
0
VA
L
L
E
Y
29
3
0
.
7
0
293
0
.
7
0
293
0
.
8
0
293
0
.
8
0
-6.2%
-2
.
0
%
-0
.
6
%
-
1
.
2
%
RIM ELEV. = 2930.30'
IE OUT WEST = 2926.77'
IE IN SOUTH = 2926.87'
MA
T
C
H
E
X
I
S
T
I
N
G
MAT
C
H
E
X
I
S
T
I
N
G
MA
T
C
H
E
X
I
S
T
I
N
G
MA
T
C
H
E
X
I
S
T
I
N
G
MA
T
C
H
E
X
I
S
T
I
N
G
LEGEND:
EXISTING SPOT GRADE
DESIGN SPOT GRADE
DESIGN TBC SPOT GRADE
2979.04(e)
2979.73
(2980.23)
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN:CHECKED:
info@jackola.com jackola.com
PR
O
J
E
C
T
#
:
E
No.14108 PE
T
L
CE S EN DI
P
RIKD.GARBERG
A
NANOM**
F
O
R
ISS
E
LANO E
REENIGN
Z:
\
C
l
i
e
n
t
F
i
l
e
s
\
2
0
2
0
\
C
i
t
y
o
f
K
a
l
i
s
p
e
l
l
\
2
0
0
2
0
4
P
o
l
i
c
e
S
e
a
r
c
h
B
u
i
l
d
i
n
g
\
6
D
r
a
w
i
n
g
s
\
1
A
u
t
o
c
a
d
\
C
O
K
_
P
S
B
_
C
1
.
3
0
.
d
w
g
FOR PERMIT
C1.3020
0
2
0
4
4/1/2021
EDGJAC
SITE GRADING
PLAN
KA
L
S
I
P
E
L
L
M
T
5
9
9
0
1
1S
T
A
V
E
W
.
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
SITE GRADING PLAN11" = 10'10-10 20 40
SCALE: 1" =
0
20'
ADDENDUM --/--/--A
REVISION --/--/--1
4" PVC, TYP.
12"
MIN.
1. PRIMARY TRENCH
(UTILITY POLE TO VAULT: TRENCH TO
TRANSFORMER PAD/VAULT PER PLAN)
CONDUIT AMBIENT TEMP. SHALL START
@20°C (68°F) BEFORE ANY DERATE &
CONDUCTOR AMBIENT TEMP. SHALL
START @75°C (167°F) BEFORE ANY DERATE.
NOTES:
1.TRENCH CONTENTS SHALL CONFORM TO NEC ARTICLE 300 AND TABLES 300-5 & 310-60, AND APPENDIX B.
2.MULTIPLE ELECTRICAL POWER CONDUITS SHALL MAINTAIN 7.5" SPACING CL TO CL HORIZONTAL AND VERTICALLY
(2" MIN), AND SHALL MAINTAIN 12" SEPARATION FROM ALL GAS LINES, COMMUNICATION LINES, AND OPTIC LINES.
3.SLIGHT SERPENTINE LAY IS ALLOWED TO ADEQUATELY COMPENSATE FOR FROST HEAVE.
4.PROVIDE FULL LENGTH 1/4" POLY PULL LINE IN EMPTY CONDUIT SECTIONS. LABEL EACH END.
5.ALL DRY UTILITIES SHALL BE 5' MIN. FROM WATER AND SEWER MAINS
6.REFER TO E1.0 FOR DUCT BANK DESCRIPTIONS
EXISTING STREET
SURFACE
3'
-
0
"
N
T
S
GRADE
PHONE 2" PVC,
TYP.
CONDUITS AND WIRE
SIZE PER NEC AND SITE
ELECTRICAL PLAN
4" SPARE
EXCAVATEDMATERIAL
18"
MIN.
PROVIDE 12" MIN., SEPARATION
FROM ALL COMMUNICATION LINES
AND OPTIC LINES. PROVIDE 36"
SEPARATION FROM GAS LINES.
3. FEEDER TRENCH
(VAULT TO SERVICE PANEL & METERS)
TRENCH WIDTH=0.D. OF
PIPE + 24"
INSTALL DETECTABLE
WARNING TAPE 12" MAX.
DEPTH.
SUB GRADE OR GROUND SURFACE
RESURFACE TO MATCH ORIGINAL
1
1
3 3/4"
1"
3"1"
2. SITE ELECTRICAL
(LOT LIGHTS & SIGNS TO SERVICE PANEL)
36
"
M
I
N
.
40
"
M
A
X
.
4" PVC, TYP.
2" CATV
2" PHONE
2-
0
"
T
O
2
'
-
6
"
CATV
ELECTRICAL TRENCH SECTION11" = 1'-0"
12"
SANITARY SEWER SERVICE LINE41" = 1'-0"
EXCAVATE AND VERIFY EXISTING SEWER
SERVICE INVERT. CONNECT NEW SCH 40
PIPING AND EXTEND TO BUILDING.
COORDINATE WITH PLUMBING DRAWINGS.
NEW SANITARY WYE, OR CONNECT
TO GREASE INTERCEPTOR
CONNECT PIPE TO EXISTING BELLED
END OR USE RIGID COUPLING
COMPACTED BACKFILL
FINISHED GRADE
MUELLER SERIES 300
BALL STYLE CURB STOP VALVE
9" RADIUS
FINISHED GRADE
NOTES:
1.3/4" - 2" SERVICES SHALL BE INSTALLED WITH BR2 SERIES SERVICE SADDLES AND PE
SERVICE LINE.
2.4" AND LARGER SERVICES SHALL BE INSTALLED WITH A ROMAC SSTIII STAINLESS STEEL
TAPPING SLEEVE AND CLASS 150 PVC SERVICE LINE.
2 NTS
WATER SERVICE CONNECTION DETAIL
TO BUILDING
TYPICAL CLEANOUT DETAIL53/4" = 1'-0"
PAVED OR
OTHER
SURFACE
SEWER/STORM
LINE-SEE PLAN FOR
SIZE
FLOW
IF LINE DEAD ENDS, INSTALL
WATERTIGHT PLUG
COMPACTED BACKFILL
FILL W/ SAND OR CRUSHED
TOP COURSE SURFACING
MATERIAL
CAP WITHOUT GASKET
BOLT-LOCKING CAST IRON
RING & COVER, 14"
MINIMUM OPENING DIA.
H-20 RATED IN PAVED AREAS
CONCRETE
45° BEND
2"
3"
M
I
N
6"
M
A
X
4"
12
"
NOTES:
1. CAST IRON COVER SHALL READ "SEWER"
2. LOCKING BOLTS FOR COVER SHALL BE 5/8"-11 NC STAINLESS STEEL TYPE 304
3. 14" BOLT-LOCKING CAST IRON COVER SHALL BE EQUAL TO INLAND FOUNDRY NO. 209
METER PIT DETAIL3N.T.S.
W
W
W
MUELLER THERMAL COIL
METER BOX WITH DOMESTIC
METER WITH METER VALVES
AND CHECK VALVE
WATER SERVICE CURB STOP WITH
MUELLER H-10306 CURB BOX FOR
3/4" AND 1" SERVICES AND
H-10310 FOR 2" SERVICES
CLASS 200 PSI C901 PE PIPE
TO
B
U
I
L
D
I
N
G
NOTES:
1.CURB STOPS TO MUELLER 300 SERIES
BALL VALVE..
2.SERVICE FITTINGS TO BE MUELLER
INSTATITE OR 110 SERIES COMPRESSION
FITTINGS. USE STAINLESS STEEL INSERTS
PER MANUFACTURER
RECOMMENDATIONS ON FITTINGS
LARGER THAN 1".
TRAFFIC RATED LID REQUIRED
24
"
CONCRETE ADJUSTMENT RING,
2" MIN, 12' MAX 2' - 6"
CONCRETE CATCH
BASIN
STORM PIPE, SEE PLAN
FOR SIZE AND SLOPE
NOTE:
1.ALL JOINTS BETWEEN CATCH BASIN, ADJUSTMENT RINGS, CASTING, AND SEWER PIPE SHALL BE WATER TIGHT.
JOINING MATERIAL SHALL BE RAM-NEK OR EQUAL FOR ALL JOINTS OTHER THAN JOINTS BETWEEN SEWER PIPE
AND CATCH BASIN.
2.ALL PIPE CONNECTIONS NOT CONSTRUCTIBLE AS DETAILED SHALL BE SUBMITTED TO CITY ENGINEER FOR REVIEW.
FLEXIBLE GASKETED
OR BOOTED JOINT,
GROUT INTERIOR
6" OF 3" MINUS CRUSHED
COMPACTED AGGREGATE
FOUNDATION
6" CONCRETE APRON, PER
CITY OF KALISPELL STANDARDS FOR
DESIGN AND CONSTRUCTION
2'EDGE OF CONCRETE
3/8" BELOW PAVEMENT
24
"
M
I
N
.
6 NTS
TYPICAL STORMWATER CATCH BASIN
24" MIN
MH-37 FRAME AND
SLOTTED COVER OR
APPROVED EQUAL
STEEL PIPE BOLLARD7NTS
3'
1'-6" DIA.
3"
4'4" Ø CONC. FILLED STEEL PIPE
W/ YELLOW PLASTIC SHEATH
1/2" PRE-MOLDED
EXPANSION JOINT
WHERE CONCRETE
OCCURS PAVING
GRANULAR FILL
CONCRETE
SONNOTUBE
10x10x1/4" THICK PLATE
WELDED ALL AROUND
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN:CHECKED:
info@jackola.com jackola.com
PR
O
J
E
C
T
#
:
E
No.14108 PE
T
L
CE S EN DI
P
RIKD.GARBERG
A
NANOM**
F
O
R
ISS
E
LANO E
REENIGN
Z:
\
C
l
i
e
n
t
F
i
l
e
s
\
2
0
2
0
\
C
i
t
y
o
f
K
a
l
i
s
p
e
l
l
\
2
0
0
2
0
4
P
o
l
i
c
e
S
e
a
r
c
h
B
u
i
l
d
i
n
g
\
6
D
r
a
w
i
n
g
s
\
1
A
u
t
o
c
a
d
\
C
O
K
_
P
S
B
_
C
2
.
0
0
.
d
w
g
FOR PERMIT
C2.0020
0
2
0
4
4/1/2021
EDGJAC
GENERAL NOTES
AND DETAILS
KA
L
S
I
P
E
L
L
M
T
5
9
9
0
1
1S
T
A
V
E
W
.
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
WALL ASSEMBLY NOTES:
1. ALL WALL TO WALL, WALL TO FLOOR AND WALL TO CEILING
JOINTS TO HAVE ACOUSTICAL SEALANT. AT LOCATIONS WITH
DEFLECTION GAPS, PROVIDE BATT INSULATION BETWEEN
WALL PLATE AND ROOF TRUSS ASSEMBLY.
2. SEE FINISH SCHEDULE FOR GWB AND MDO FINISHES
VERTICAL METAL SIDING
WEATHER RESISTANT AIR BARRIER
(1) STRUCTURAL SHEATHING
WHERE REQ'D PER STRUCT.
2x6 WD STUDS @ 16" O.C.
R-21 BATT INSULATION
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
EXTERIOR WALL
SCALE: 1 1/2" = 1'
A.1
6 MIL VAPOR BARRIER
2x4 WD STUDS @ 16" O.C.
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
INT. 2X4 WALL
SCALE: 1 1/2" = 1'
B.1
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
2x6 WD STUDS @ 16" O.C.
R-11 SOUND BATTS (WHERE
NOTED)
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
INT. 2X6 WALL
SCALE: 1 1/2" = 1'
B.2
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
A.1X S
0'-0"
KEY FOR WALL TYPES
WALL ASSEMBLY
'X' INDICATES FIRE RATED
SOUND INSULATION
(WHERE OCCURS)
ASSEMBLY HT. (IF NOT FULL HT.)
VERTICAL METAL SIDING
WEATHER RESISTANT AIR BARRIER
(1) STRUCTURAL SHEATHING
WHERE REQ'D PER STRUCT.
2x6 WD STUDS @ 16" O.C.
R-21 BATT INSULATION
EXTERIOR WALL
SCALE: 1 1/2" = 1'
A.2
6 MIL VAPOR BARRIER
2x6 WD STUDS @ 16" O.C.
R-11 SOUND BATTS (WHERE
NOTED)
MDO PLYWOOD (UP TO 8'- 0")
PAINTED W/ (1) 5/8" GWB ABOVE
(8'-0") TO STRUCTURE ABOVE. TAPE,
TEXTURE, PAINT.
INT. 2X6 WALL
SCALE: 1 1/2" = 1'
B.5
MDO PLYWOOD TO FLOOR STRUCTURE
ABOVE, SEE FINISH SCHEDULE
2x6 WD STUDS @ 16" O.C.
R-11 SOUND BATTS (WHERE
NOTED)
(1) MDO PLYWOOD TO FLOOR
STUCTURE ABOVE, PAINTED
INT. 2X6 WALL
SCALE: 1 1/2" = 1'
B.3
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
2x6 WD STUDS @ 16" O.C.
R-11 SOUND BATTS (WHERE
NOTED)
INT. 2X6 WALL
SCALE: 1 1/2" = 1'
B.4
(1) 5/8" GYP. WALLBD. TAPE,
TEXTURE, & PAINT
MDO PLYWOOD (UP TO 8'- 0")
PAINTED W/ (1) 5/8" GWB ABOVE
(8'-0") TO STRUCTURE ABOVE. TAPE,
TEXTURE, PAINT.
MDO PLYWOOD (UP TO 8'- 0")
PAINTED W/ (1) 5/8" GWB ABOVE
(8'-0") TO STRUCTURE ABOVE. TAPE,
TEXTURE, PAINT.
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A0.0
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ARCHITECTURAL
NOTES
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
SHEET WHERE ITEM IS CUT
ITEM IDENTIFICATION
AX.X
XX
AX.X
XX
XX
AX.X
XX
AX.X
DETAIL
ELEVATION
ROUGH WOOD
SECTION XXX
X
UNDISTURBED EARTH
WALL TYPE
REVISION NUMBER
ROOM NUMBER
DOOR NUMBER
WINDOW TYPE
PLYWOOD
METAL
RIGID INSULATION
BATT INSULATION
FINISHED WOODSTRUCTURAL FILL
BLOCKING
SAND,
PLASTER,
GROUT
AND&
ANGLEL
AT@
CENTERLINECL
CHANNELu
DIAMETERO
PLATEPL
/
ABBREVIATIONS
SYMBOLS & MATERIALS
SYMBOLS USED AS
ABBREVIATIONS
A
AFF
ACT
ADJ
AB
ALUM
ALT
ANOD
APPROX
ARCH
B
BSMT
BATH
BM
BRG
BEDRM
BET
BLDG
BO
BOT
BN
BS
C
CPT
CLG
CT
CLR
CLST
COL
CONC
CONST
CONT
CONTR
CORR
CJ
CMU
D
DEMO
DTL
DIA
DIM
DW
DIV
DL
DR
DN
DS
DWG
DF
D
E
EA
E
ELEC
ELEV
EQ
EQUIP
EXIST
EXP
EJ
EXT
F
FOB
FOC
FOM
ABOVE FINISH FLOOR
ACOUSTICAL CEILING TILE
ADJUSTABLE
ANCHOR BOLT
ALUMINUM
ALTERNATE
ANODIZED
APPROXIMATE
ARCHITECT
BASEMENT
BATHROOM
BEAM
BEARING
BEDROOM
BETWEEN
BUILDING
BOTTOM OF
BOTTOM
BOUNDARY NAILING
BOTH SIDES
CARPET
CEILING
CERAMIC TILE
CLEAR
CLOSET
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
CONTRACT, CONTRACTOR
CORRIDOR
CONTROL JOINT
CONCRETE MASONRY UNIT
DEMOLISH, DEMOLITION
DETAIL
DIAMETER
DIMENSION
DISHWASHER
DIVISION
DEAD LOAD
DOOR
DOWN
DOWNSPOUT
DRAWING
DRINKING FOUNTAIN
DRYER
EACH
EAST
ELECTRIC
ELEVATION, ELEVATOR
EQUAL
EQUIPMENT
EXISTING
EXPANSION
EXPANSION JOINT
EXTERIOR
FACE OF BRICK
FACE OF CONCRETE
FACE OF MASONRY
FOS
FIN
FF
FEC
FL
FLR
FD
FT
FTG
FND
FURN
FUT
FBO
FRP
G
GA
GALV
GEN
GL
GWB
GYPC
H
HALL
HDW
HVAC
HT
HM
HORIZ
HWT
HR
I
IBC
INCL
INFO
ID
INSUL
INT
J
JAN
JC
JT
K
KIT
KO
L
LBL
LAM
LNDRY
LAV
LVL
LL
LR
LOC'N
M
MFR
MAS
MO
FACE OF STUDS
FINISH
FINISH FLOOR
FIRE EXTINGUISHER/AND
OR CABINET
FLASHING
FLOOR
FLOOR DRAIN
FOOT, FEET
FOOTING
FOUNDATION
FURNITURE
FUTURE
FURNISHED BY OTHERS
FIBER REINFORCED PANEL
GAUGE
GALVANIZED
GENERAL
GLASS
GYPSUM WALL BOARD
GYPCRETE
HALLWAY
HARDWARE
HEATING, VENTILATING, & AIR
CONDITIONING
HEIGHT
HOLLOW METAL
HORIZONTAL
HOT WATER TANK
HOUR
INTERNATIONAL BUILDING CODE
INCLUDE, INCLUDED (ING)
INFORMATION
INSIDE DIAMETER
INSULATE,INSULATION
INTERIOR
JANITOR
JANITOR'S CLOSET
JOINT
KITCHEN
KNOCK OUT
LABEL
LAMINATED
LAUNDRY
LAVATORY
LEVEL
LIVE LOAD
LIVING ROOM
LOCATION
MANUFACTURER
MASONRY
MASONRY OPENING
MATERIAL
MAXIMUM
MECHANICAL, MECHANICAL ROOM
METAL
MINIMUM
MIRROR
MISCELLANEOUS
NOMINAL
NORTH
NOT APPLICABLE
NOT IN CONTRACT
NOT TO SCALE
NUMBER
ON CENTER
OFFICE
OPENING
OPPOSITE
OUTSIDE DIAMETER
OUTSIDE FACE
OUT TO OUT
PAINT, PAINTED
PANEL
PHASE
PLASTIC
PLASTIC LAMINATE
PLATE
PLYWOOD
POLYVINYL CHLORIDE
PREFINISHED
PROPERTY
QUANTITY
RADIUS
RAIN WATER LEADER
REFERENCE
REINFORCE, REINFORCEMENT
REFLECTED CEILING PLAN
REQUIRED
REQUEST FOR INFORMATION
REVISION
RISER
ROOF DRAIN
ROOM
ROUGH OPENING
SCHEDULE
SECTION
SAFETY GLASS
SHEATHING
SIMILAR
SLAB ON GRADE
SOUTH
SPECIFICATION
SQUARE
STANDARD
STEEL
STORAGE
STRUCTURAL
SQUARE FEET
SUSPENDED
MATL
MAX
MECH
MTL
MIN
MIRR
MISC
N
NOM
N
NA
NIC
NTS
NO
O
OC
OFF
OPG
OPP
OD
OF
O/O
P
PNT
PNL
PH
PLAS
P-LAM
PL
PLYWD
PVC
PREFIN
PROP
Q
QUAN
R
RAD
RWL
REF
REINF
RCP
REQ'D
RFI
REV
R
RD
RM
RO
S
SCHED
SEC
SG
SHTG
SIM
SOG
S
SPEC
SQ
STD
STL
STOR
STRUCT
SF
SUSP
NORTH ARROW
STEEL
GRAVEL
BRICK VENEER
POURED CONCRETE
CONCRETE BLOCK VENEER
EIFS
KEY NOTE
DEMOLITION NOTE
FINISH TAG
XX
X
X
X
X
SPRAYFOAM INSULATION
DISTURBED EARTH
TELEPHONE
TELEVISION
TEMPERED, TEMPORARY
TONGUE AND GROOVE
TOP OF BRICK
TOP OF SLAB
TOP OF WALL
TOP OF MASONRY
TREAD
TYPICAL
UPWARD ACTING SECTIONAL DOOR
UNIFORM BUILDING CODE
UNLESS NOTED OTHERWISE
UTILITY
VAPOR BARRIER
VENEER
VERTICAL
VERTICAL GRAIN
VINYL COMPOSITION TILE
WAINSCOT
WATER CLOSET
WINDOW
WATERPROOF (ING)
WEATHER RESISTANT BARRIER
WELDED WIRE FABRIC
WELDED WIRE MESH
WEIGHT
WEST, WASHER
WITH
WASHER / DRYER
T
TEL
TV
TEMP
T&G
TOB
TOS
TOW
TOM
T
TYP
U
UAS
UBC
UNO
UTIL
V
VB
VNR
VERT
VG
VCT
W
WSCT
WC
WIN
WP
WRB
WWF
WWM
WT
W
W/
W/D
X.XX - S
X'-X"
1 1/2" = 1'-0"1 WALL TYPE ASSEMBLIES
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
UP
A
A
1
C
C
4
D4.1
2
D4.1
1
D4.0 1
B
B
2
3
1' - 4" 5' - 8"12' - 4"27' - 8"
SHOP
101
EVIDENCE /
STOR.
102
UTILITY / MECH
103
R.R.
104
STOR.
105
EXIT
A4.00
2
A4.001
A4.00 3
A4.00
4
1
A5.00
1
A5.00
2
A5.00
2
A5.00
40' - 0"
B.3
A.1
A.2
B.4
A.2
A.1
A.1A.2
B.1
B.2
108
106
105
104
101
102
103
6'
-
0
"
10
'
-
0
"
1'
-
3
"
10
'
-
0
"
1'
-
3
"
10
'
-
0
"
1'
-
6
"
40
'
-
0
"
5'
-
1
1
/
2
"
A.1
A.1
B.4
CL
CL
CL
CL
CL
0'
-
4
"
9'
-
8
"
10
'
-
0
"
1'
-
6
"
8'
-
6
"
1'
-
0
"
8'
-
8
"
0'
-
4
"
21
'
-
6
"
9'
-
6
"
9'
-
0
"
40
'
-
0
"
1
110111
B.5
CL
2' - 10"14' - 2"
2
2
2
2
B.1
6' - 9"
CL
3' - 5 1/2"
3
A5.00
3
A5.00
3 TYP
4
5
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A1.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1 FLOOR
PLAN
MSHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
LEVEL 1 FLOOR PLAN KEYNOTES
1 EMERGENCY SHOWER/ EYEWASH, SEE PLUMBING
2 BOLLARD, SEE CIVIL FOR EXACT LOACTION. PAINT RUST-OLEUM
SAFETY YELLOW
3 FLOOR DRAIN
4 MOP SINK
5 WATER HEATER
3/8" = 1'-0"1 FLOOR PLAN
GENERAL PLAN NOTES:
1. SEE PLUMBING SHEETS FOR ALL FIXTURES
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
ARCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
UP
A
A
1
C
C
4
B
B
2
3
CL
CL
CL
9'
-
6
"
9'
-
6
"
10
'
-
6
"
MEZZANINE
201
1
A5.00
1
A5.00
2
A5.00
2
A5.00
CL
2'
-
0
"
8'
-
6
"
40' - 0"
B
B
1
B.1
42" A.F.F
12' - 4"6' - 8"
CLCL
7' - 0"
CLCL
7' - 0"7' - 0"
B
A A A
A A A
A.2
A.2
A.1
A.1
A.1
A.1
40
'
-
0
"
B.1
SLOPE WALL 42" ABOVE STAIR TREADS
3
A5.00
3
A5.00
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A1.20
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
MEZZANINE
LEVEL PLAN
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
3/8" = 1'-0"1 MEZZANINE LEVEL PLAN
MEZZANINE KEYNOTES
1 PONY WALL AS GUARDRAIL, 42" AFF MIN. SEE FINISH PLAN
FOR CAP A7.00
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
MTL SOFFIT
GWB
CEILING TYPES LEGEND
1
A
A
1
C
C
4
B
B
2
3
EVIDENCE /
STOR.
102
UTILITY / MECH
103
R.R.
104
SHOP
101
STOR.
105
GWB W/ FRAMING
8' - 0"
GWB W/ FRAMING
8' - 0"
GWB W/ FRAMING
8' - 0 1/2"
7' - 7 5/8"
B.O. BEAM
2
2
3
3
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A2.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1
REFLECTED
CEILING PLAN
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
LEVEL 1 RCP KEYNOTES
1 SLOPED CEILING @ B.O. STAIR
2 SEE ELECTRICAL DRAWINGS FOR FINAL FIXTURE LOCATIONS
3 WESTERN STATES METAL SALES SOFFIT
3/8" = 1'-0"1 LEVEL 1 RCP
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
CEILING GENERAL NOTES:
1. SEE ELECTRICAL DRAWINGS FOR ALL LIGHTING FIXTURES
LOCATION.
2. SEE MECH DRAWINGS FOR ALL FIXTURES AND LOCATIONS
A
A
1
C
C
4
B
B
2
3
1
ATTACHED TO B.O. ROOF TRUSS
8'-0" (VFY)
GWB W/ FRAMING
22
2
2
3
GWB
CEILING TYPES LEGEND
MTL SOFFIT
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A2.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
MEZZANINE
LEVEL
REFLECTED
CEILING PLAN
MKSHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
3/8" = 1'-0"1 MEZZANINE LEVEL RCP
MEZZANINE RCP KEYNOTES
1 ACCESS HATCH. SEE STRU FOR DETAILS
2 WESTERN STATES METAL SALES SOFFIT
3 MECH UNIT.
CEILING GENERAL NOTES:
1. SEE ELECTRICAL DRAWINGS FOR ALL LIGHTING
FIXTURES LOCATION.
2. SEE MECH DRAWINGS FOR ALL FIXTURES AND
LOCATIONS
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
-24 GAUGE PRB PANEL (PURLIN BEARING R
PANEL) MATTE BLACK
-UDL-30 OR SIMILAR UNDERLAYMENT
-SHTG PER STRUCT.
-FRAMING PER STRUCT.
-R-30 MIN. INSULATION BLOW IN
-6 MIL. V.B.
-5/8" GWB B.O. TRUSSES
ROOF TYPE LEGEND
R-1
-24 GAUGE PRB PANEL (PURLIN BEARING R
PANEL) MATTE BLACK
-FRAMING PER STRUCT.
R-2
3"/12"
2"
/
1
2
"
1
A
A
1
C
C
4
3"/12"
2"/12"
R-1
R-2
R-2
TYP. OVRHNG
1' - 6"
40' - 0"
4' - 0"
6' - 0"
0' - 11"
1
A5.00
1
A5.00
2
A5.00
2
A5.00
ROOF BELOW
7' - 0 3/4"
40' - 0"
1 1
1
2
2
TYP
1
TYP. OVRHNG
1' - 6"40' - 0"
TYP. OVRHNG
1' - 6"
3
R-1
1
A3.10
6
A3.10
3
A3.10
3
A3.10
4
A3.10
4
A3.10
4
1
3
A5.00
3
A5.00
TYP
TYP. OVRHNG
1' - 6"
7
A3.10
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A3.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ROOF PLAN
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
ROOF PLAN KEYNOTES
1 GUTTER AND DOWNSPOUT, ROOF MANUF TO SUPPLY TO MATCH
2 ICE AND WATERSHIELD
3 SNOW GUARD
4 PLUMBING VENT, SEE MECH DRAWINGS FOR EXACT LOCATION
3/8" = 1'-0"1 ROOF PLAN
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
PREFINISHED METAL
ROOFING PANEL
ROOF SHTG.
30# FELT
UNDERLAYMENT
FASTENER
PREFINISHED
J-CHANNEL
SEALANT
PREFINISHED METAL
FLASHING
FASTENER
SIDING PER ELEV
PERPENDICULAR TO WALL
WRB, LAP OVER FLASHING
ROOF SHTG.
30# FELT UNDERLAYMENT (IF
APPLIED OVER WD SHTG), RUN
UNDER PHILEDALPHIA FLASHING
PREFINISHED METAL
ROOFING PANEL
PREFINISHED METAL
FLASHING
SIDING PER ELEV
PREFINISHED J-CHANNEL
FASTENER
FASTENER
SEALANT
SLOPED AT WALL
WRB, LAP OVER FLASHING
ROOF JACK
TYP. ROOF ASSEMBLY
PIPE OR FLUE
SEALANT BELOW JACK
FLANGES PER MFR
REQUIREMENTS
ROOF SHTG
PREFINISHED METAL
ROOFING PANEL
UNDERLAYMENT
SNOW GUARDS: S-5 COLOR GUARD SNOW
FENCE SYSTEM -ROOF MFR TO PROVIDE
MATCHING COLOR STRIP, SPACING PER
MFR'S RECOMMENDATION
ICE & WATER SHIELD SHALL BE APPLIED FROM
EAVES TO A LINE 24" INSIDE EXTERIOR WALL
LINE (36" MIN DISTANCE FROM EAVES @
SLOPES > 8/12), INSTALL PER MANUFACTURERS
INSTRUCTIONS
DRIP EDGE
SYNTHETIC UNDERLAYMENT
UDL-30 OR SIM. LAP PER MFR'S
RECOMMENDATION
PRE FINISHED METAL ROOFING PANEL (SEE ROOF PLAN A3.00)
4 "M I N
PRE-MANUF MTL
GUTTER TO MATCH
ROOFING PANEL
METAL PANEL
METAL PANEL
OUTSIDE CLOSURE
STITCH @ EVERY
RIB
TAPE SEALANT
UNIVERSAL RIB COVER
PRE-MANUFACTURED
TRUSSES
UNDERLAYMENT
SHEATHING PER
STRUCTURAL
EAVE ALONG RAKE
SHADOW BOARD
(IF PRESENT)
METAL DRIP EDGE
APPLIED OVER FELT
ALONG RAKE
ROOF SHTG
UNDERLAYMENT
FASCIA
ROOFING PER A3.0
ROOF SHTG
UNDERLAYMENT
DRIP EDGE, APPLIED
BELOW
UNDERLAYMENT, USE
DEEP LEG ON SLOPES
LOWER THAN 3:12.
FASCIA
ROOF PER A3.0
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A3.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ROOF DETAILS
MSMRC
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1 1/2" = 1'-0"2 ROOF BREAK PERP. TO WALL
1 1/2" = 1'-0"3 ROOF BREAK SLOPED AT WALL
1 1/2" = 1'-0"5 ROOF PENETRATION DTL-METAL ROOF
1 1/2" = 1'-0"6 SNOW GUARD
1 1/2" = 1'-0"4 ROOF EDGE FLASHING
1 1/2" = 1'-0"1 RIDGE CAP @ MTL ROOF (NON-VENTED)
1 1/2" = 1'-0"7 DRIP EDGE - RAKE
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
1 1/2" = 1'-0"8 DRIP EDGE
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
AC
MEZZANINE FF
9' -1 3/4"
2
2
2
6
6
7
8
B.O. BRACE
4' - 4"
B.O. BRACE
5' - 4"
8
8
A A A
12
10 10
3
10
11
2
A8.00
3
A8.00
4
A8.00
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
14
MEZZANINE FF
9' -1 3/4"
2
6
9
1
10 10
8
7
12
TYP
TYP
103 102
A.1
101
2
3
11
5
A8.00
6
A8.00
7
A8.00
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
1 4
MEZZANINE FF
9' -1 3/4"
1
2
3
3
4
5
8
10
8
B B B
10
10
TYP
TYP
TYP
2
11
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
A C
MEZZANINE FF
9' -1 3/4"
2
2
3
7
48
8
A A A
12
2
10
11
8
A8.00
9
A8.00
10
A8.00
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A4.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
EXTERIOR
ELEVATIONS
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1/4" = 1'-0"2 NORTH ELEVATION
1/4" = 1'-0"1 EAST ELEVATION
1/4" = 1'-0"3 WEST ELEVATION
1/4" = 1'-0"4 SOUTH ELEVATION
ELEVATION KEYNOTES
1 GABLE END VENT (24" x 42"), CONTRACTOR TO PROVIDE STANDARD
COLOR SAMPLES TO ARCH FOR APPROVAL.
2 WESTERN STATES MTL ROOFING PRB PANEL, MATTE BLACK, 24
GAUGE. INSTALLATION TO FOLLOW MANUF REQUIREMENTS TO
ENSURE NO OIL CANNING.
3 PREMANUFACTURED GUTTER AND DOWNSPOUT TO MATCH
ROOFING
4 VINYL WINDOW, SEE WINDOW SCHEDULE ON A8.00, TYP ALL.
5 COLUMN AND BEAM PER STRUCTURAL, STAIN MINWAX 'DARK
WALNUT' 2716 (OIL BASED)
6 KNEE BRACE PER STRUCTURAL, STAIN MINWAX 'DARK WALNUT' 2716
(OIL BASED)
7 WESTERN STATES PBR METAL SIDING PANEL, ASH GREY, 24 GAUGE.
INSTALLATION TO FOLLOW MANUF REQUIREMENTS TO ENSURE NO
OIL CANNING.
8 WESTERN STATES MTL FASCIA, MATTE BLACK TO MATCH ROOFING
PANEL.
9 SIGNAGE, BY OWNER
10 LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS, TYP ALL.
11 METAL TRIM PER METAL MANUF
12 MECH EQUIPMENT, SEE MECH DRAWINGS, TYP ALL
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
FOUNDATION
-4' -0"
14
T.O.P LEVEL 1
8' -1 1/8"
MEZZANINE FF
9' -1 3/4"
23
2
A5.00
106108
B B
R-49 BLOW IN INSULATION
B
110
SHOP
101 16 RISERS
9' - 1 3/4"
MAX
42" AFF
A6.00
2
A5.00
4
3
A5.00
8' - 0" A.F.F.MD
O
GW
B
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
FOUNDATION
-4' -0"
AC
T.O.P LEVEL 1
8' -1 1/8"
MEZZANINE FF
9' -1 3/4"
B
1
A5.00
42"
4' - 0"
A6.00
1
SHOP
101
R.R.
104
MEZZANINE
201
A6.00
3
A A A
R-49 BLOW IN INSULATION
MD
O
GW
B
8' - 0" A.F.F.
METAL SOFFIT TO MATCH
ROOFING, SEE 1/A2.10
WC
GW
B
A3.10
8
LAG BOLT INTO
WOOD BLOCKING IN
WOOD STUD WALL.
BLACK FINISH
NOTE: TOP OF HANDRAIL
TO BE A MIN. OF 34" AND
A MAX. OF 38"
HANDRAIL SUPPORT
NOT TO EXCEED 4'-0" O.C.
1 1/2" MIN 1 1/4" MIN TO 2" MAX
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
FOUNDATION
-4' -0"
A C
T.O.P LEVEL 1
8' -1 1/8"
MEZZANINE FF
9' -1 3/4"
B
MD
O
GW
B
R-49 BLOW IN INSULATION
1
A5.00
A35 (2) ON CENTER
STRINGER (1) ON
EDGE STRINGERS
SEE STRUCT.
FLOOR SHTG
JOISTS
2X12 TREAD
2X6 NAILER
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A5.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
BUILDING
SECTIONS
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1/4" = 1'-0"1 BUILDING SECTION 1
1/4" = 1'-0"2 BUILDING SECTION 2
NTS4HANDRAIL DTL
1/4" = 1'-0"3 BUILDING SECTION 3
1" = 1'-0"5 STAIR DTL
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
12
3
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
FOUNDATION
-4' -0"
C
HEADER, SEE
STRUCTURAL
OVERHEAD DOOR
PER PLAN
FOUNDATION,
SEE STRUCTURAL
CONCRETE DRIVE,
SEE CIVIL
CONCRETE SLAB,
SEE STRUCTURAL
A8.00
5
WALL TYPE
PER PLAN
GWB
5/8" GWB CEILING,
ATTACH TO B.O.
STRUCUTRE
R-49 BLOWN-IN
INSULATION
METAL SOFFIT TO
MATCH ROOFING, SEE RCP
METAL ROOFING,
SEE ROOF PLAN
ROOF TRUSSES,
SEE STRUCTURAL
MD
O
GW
B
8' - 0" A.F.F.
F.F.
0' -0"
T.O.PLATE
17' -2 7/8"
FOUNDATION
-4' -0"
4
T.O.P LEVEL 1
8' -1 1/8"
MEZZANINE FF
9' -1 3/4"
VENTED METAL SOFFIT
R-49 BLOW IN INSULATION
GUTTER
FASCIA
SUB FASCIA
SHEATHING PER STRUCTURAL
2X BLOCKING
WRB MEMBRANE
WALL TYPE PER PLAN
FOUNDATION,
SEE STRUCTURAL
CONCRETE SLAB,
SEE STRUCTURAL
108
SHOP
101
METAL ROOF, SEE ROOF PLAN
8' - 0" A.F.F.MD
O
GW
B
MAX
3' - 6"
WALL CAP, SEE 3/A6.00
GWB
5/8" GWB CEILING, ATTACH
TO B.O. STRUCUTRE
ALUMINUMN T-STRIP @
MDO TO GWB TRANSITION
F.F.
0' -0"
T.O.P LEVEL 1
8' -1 1/8"
MEZZANINE FF
9' -1 3/4"
B
2X6 WALL CAP, CLEAR FIR, HAND
SMOOTH W/ POLY TOP COAT, ATTACH
W/8d FINISH NAILS 6" O.C. STAGGERED
MAX
3' - 6"
CONCRETE SLAB PER STRUCTURAL
SHEATHING PER STRUCTURAL
10"
WALL TYPE PER PLAN
WC
GW
B
MEZZANINE
201
R.R.
104
WALL TYPE PER PLAN
GWB
8' - 0" A.F.F.
MDO
5/8" GWB CEILING, ATTACH
TO B.O. STRUCUTRE
LVP FLOOR FINISH, SEE FINISH PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A6.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
WALL SECTIONS
MKSHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
3/4" = 1'-0"1 WALL SECTION @ GRIDLINE C
3/4" = 1'-0"2 WALL SECTION @ GRIDLINE 4
3/4" = 1'-0"3 WALL SECTION @ GRIDLINE B
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
UP
PT
B-1
LVP
PLY
PLY
PLY
PLY
PT
B-1
SC
PT
PT
PT
PT
PT
B-1
LVP
WC/PT
WC/PT
WC/PT
WC/PT
PT
B-1
SC
PT
PT
PT
PT
A7.10
3
24
EVIDENCE /
STOR.
102
SHOP
101
UTILITY / MECH
103
R.R.
104
LVP SC
LVP SC
SC
PT
B-1
LVP
PT
PT
PT
PT
OPEN TO BELOW
UP
CAP
CAP
MEZZANINE
201
TREADSLVP
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A7.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
FLOOR FINISH
PLAN
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
FINISH SCHEDULE
TAG KEY COLOR MANUFACTURER STYLE NOTE
B-1 BASE 48 GREY TRADITIONAL VINYL 1/8" (TYPE TV) TARKETT RESILIANT BASE 4" WITH TOE TARKETT 960 WALL BASE ADHESIVE
CAP RAILING CAP CLEAR GRADE 2X6 DOUGLAS FIR ANY WOOD SAND TO HAND SMOOTH, POLY FINISH
LVP LUXURY VINYL PLANK ZURICH NOLV0206 TAS FLOORING WF TAYLOR 2091 ADHESIVE
PT-1 PAINT AGREEABLE GREY SW7029 SHERWIN WILLIAMS
SC SEALED CONCRETE
ST-1 STAIN PROVINCIAL MW 211 MINWAX
TREADS TREADS 48 GREY TARKETT .080" GAUGE TARKETT 965 FLOORIING AND TREAD ADHESIVE
WC WAINSCOATING BRUSHED ALUMINUM KOROGUARD PROTECTIVE WALL
COVERINGS
.040" TRIM W/ ALUMINUM STRIPPING. KOROSEAL JC12, IC12, AND DB12
CLG
BASE
FLOOR
SOUTH
WALL
EAST
WALL
NORTH
WALL
WEST
WALL
NOTES:
1/4" = 1'-0"1 FINISH FLOOR PLAN
ROOM FINISH KEY
1/4" = 1'-0"2 MEZZANINE FINISH FLOOR
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
39"- 41"
33" -36"
12" MAX.18" MIN
39"- 41"
42"
CL
12"24"
36"
33" -36"
1' - 6 1/2"16"-18"
17
"
-19
"
FINISH FLOOR
CL
GRAB BARS TOILET PAPER DISPENSER SINK/LAV
THE FRONT OF
LAVATORIES AND SINKS
SHALL BE 34" MAXIMUM
ABOVE THE FLOOR
MEASURED TO THE
HIGHER OF THE RIM OR
COUNTER SURFACE
SOAP DISPENSER MIRROR
40" MAX.
IF
O
V
E
R
A
SI
N
K
,
3
5
"
MA
X
I
F
NO
T
TOWEL
DISPENSER
48" MAX
COAT HOOK
LEVER TO BE
ON THE SIDE
OPPOSITE TO
A WALL
CLEAR
AREA
34" MAX
27" MIN 6"
9"
17"
8"
REST
....
60" MAX
....
48" MIN
ROOM
BRAILLE SHALL BE
POSITIONED BELOW THE
CORRESPONDING TEXT
NOTE: SIGNS SHALL COMPLY WITH CHAPTER
7: COMMUNICATION ELEMENTS AND
FEATURES, 703 SIGNS -'ADA STANDARDS
FOR ACCESSIBLE DESIGN'
CHARACTER HEIGHT OF
SIGNAGE IS BASED ON
THE VIEWING DISTANCE
AND HEIGHT OF THE
SIGN AFF. MIN. 5/8".
MAX
44"
17"
1 1/2" MIN.
TO TOWEL PULL
48" MAX
2
3
5 WC
PT-1
5' - 0"
B-1
PT-1
45' - 0"
WC
B-1
1
5
PT-1
5' - 0"
WC
B-1
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A7.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
INTERIOR
ELEVATIONS
MSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
INTERIOR ELEVATION KEYNOTES
1 TOILET PAPER DISPENSER
2 SOAP DISPENSER
3 MIRROR
4 PAPER TOWEL DISPENSER
5 GRAB BARS
1/4" = 1'-0"1 BATHROOM ACCESSORIES - ADA
1/2" = 1'-0"3 RESTROOM NORTH
1/2" = 1'-0"2 RESTROOM EAST
1/2" = 1'-0"4 RESTROOM WEST
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
A B C D
"WAYNE-DALTON"
CLASSIC STEEL GARAGE DOOR
CONTEMPOARY STYLE
TAUPE
INTERIOR SOLID CORE
WOOD DOOR
STAIN: DARK WALNUT
MW2716 WITH SATIN
POLYURETHANE TOP COAT
HOLLOW METAL DOOR
"STEELCRAFT" B SERIES FLUSH DOOR
PAINT TO MATCH OVERHEAD DOOR
INSULATED HOLLOW METAL DOOR
"STEELCRAFT" B SERIES FLUSH DOOR
PAINT TO MATCH OVERERHEAD DOOR
PELLA 350 SERIES VINYL
W/CENTER SET GLAZING.
COLOR: DUAL COLOR BLACK EXTERIOR, WHITE
INTERIOR
GLAZING: 1" THICK INSULATING GLASS, LOW-E
SAFETY GLAZING REQUIRED LOCATIONS:
-ALL DOORS
-GLAZING IN FIXED OR OPERABLE PANELS ADJACENT TO A DOOR WHERE THE
NEAREST VERTICAL IS WITHIN 24" ARC OF EITHER VERTICAL EDGE OF DOOR IN A
CLOSED POSITION AND WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS
LESS THAN 60" ABOVE WALKING SURFACE.
-GLAZING ADJACENT TO STAIRWAYS, LANDINGS AND RAMPS WITHIN 36"
HORIZONTALLY OF WALKING SURFACE WHEN EXPOSED SURFACE OF GLASS IS
LESS THAN 60" ABOVE THE WALKING SURFACE (EXCEPTION: IF HANDRAIL OR
GUARD IS INSTALLED , POSITIONED BETWEEN 34"-38" ABOVE WALKING
SURFACE, CAPABLE OF WITHSTANDING 50 LBS OF FORCE/ FT WITHOUT
TOUCHING THE GLASS)
-GLAZING ADJACENT TO STAIRWAYS WITHIN 60" HORIZONTALLY OF THE
BOTTOM TREAD OF THE STAIRWAY IN ANY DIRECTION WHEN THE EXPOSED
SURFACE OF THE GLASS IS LESS THAN 60" ABOVE THE NOSE OF THE TREAD.
B
A
5' - 0"
2' - 0"
7' - 0"
4' - 0"
4' - 0"
4' - 0"
EQ
EQ
3' - 0"
AL -ALUMINUM
FG -FIBERGLASS
HM -HOLLOW METAL, WELDED STEEL
KD -KNOCKDOWN METAL
MDF -MEDIUM DENSITY FIBERBOARD
MPD -MOLDED PANEL DOOR (MASONITE)
MTL -METAL, STEEL
SC WD -SOLID CORE WOOD
WD -WOOD
SHTG PER STRUCTURAL
SIDING PER ELEV
HM DOOR
GWB
FLASHING
VB
INTERIOR EXTERIOR
WRB, LAP OVER HD FLASHING
WALL TYPE PER PLAN
SEALANT, TYP.TRIM & SIDING PER ELEV
HM DOOR
CAULKING, TYP.
WRB WRAP INTO OPENING
VB
INTERIOR
EXTERIOR
SHTG PER STRUCTURAL
WALL TYPE PER PLAN
HM DOOR
EXTERIOR CONCRETE SLAB
WEATHERING
DOOR SWEEP
THRESHOLD, 1/2" MAX HGT.
INTERIOR EXTERIOR
WALL BEYOND
UPWARD ACTING
SECTIONAL DOOR
INTERIOR CONCRETE SLAB THERMAL BREAK
THRESHOLD, 1/2" MAX HGT.
INTERIOR EXTERIOR
WALL TYPE PER PLAN
HDR PER STRUCTURAL
P.T. 2X6
WEATHER SEAL
UPWARD ACTING
SECTIONAL DOOR
J-METAL TRIM
PAD OUT AS REQUIRED
MTL TRIM
SIDING PER ELEV
SHTG PER STRUCTURAL
UPWARD ACTING
SECTIONAL DOOR
P.T. 2X6
WEATHER SEAL
J-METAL TRIM
WALL TYPE PER PLAN
WRB
WOOD STOP
MOULDING
TRIM
INTERIOR
EXTERIOR
INSTALLED
FENESTRATION UNIT
APPLY WEATHER
RESISTANT BARRIER / AIR
BARRIER PER MFR
INSTRUCTIONS
STEP 1.
INSTALL FLEXIBLE SILL
FLASHING
STEP 2.
APPLY SEALANT AT JAMBS
AND HEAD
STEP 3.
INSTALL FLANGED
WINDOW
STEP 4.
INTERIOR
EXTERIOR
6" MIN.
LAP PAST SILL
FLASHING
1" MIN
INSTALL STRAIGHT
FLASHING OVER
WINDOW FLANGE
AT JAMBS
STEP 5.
INSTALL STRAIGHT
FLASHING OVER
WINDOW FLANGE
AT HEAD
STEP 6.
INSTALL WINDOW HEAD
TRIM AND CUT IN THRU-
WALL HEAD FLASHING OVER
TOP WINDOW TRIM
STEP 7.
REMOVE SILL FOR NEW
WINDOW INSTALLATION
VINYL WINDOW
METAL SIDING PER ELEV
APPLY 4" 'TARCO LEAKBARRIER'
DOOR AND WINDOW TAPE PER MFR
WRB OVER WINDOW
FLANGE AT HEAD
INTERIOR EXTERIOR
SHTG
SEALANT
J-METAL TRIM
SEALANT
APPLY 4" 'TARCO LEAKBARRIER'
DOOR AND WINDOW TAPE PER MFR
METAL SIDING PER ELEV
VINYL WINDOW
GWB
INTERIOR
EXTERIOR
WRB OVER WINDOW
FLANGE AT HEAD
J-METAL TRIM
SEALANT WINDOW EDGE
METAL SIDING PER ELEV
APPLY 4" 'TARCO
LEAKBARRIER' DOOR AND
WINDOW TAPE PER MFR
VINYL WINDOW
WRB UNDER WIN
FLANGE AT SILL
GWB J-METAL TRIM
FLEXIBLE SILL
FLASHING TYP. TURN
UP AT JAMB 3" MIN.
INTERIOR EXTERIOR
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
A8.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
DOOR AND
WINDOW
SCHEDULE AND
DETAILS
MKSHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
DOOR SCHEDULE
DOOR NO. FROM TO SIZE LABEL TYPE DOOR MAT. FRAME MAT. LITE HARDWARE
DOOR STOP
(W:WALL,
F:FLOOR)REMARKS
101 EXTERIOR SHOP 10'-0" x 12'-0" x 2" A OH NONE (none) HARDWARE BY MANUFACTURER (COORDINATE W/ELECTRICAL)
102 EXTERIOR SHOP 10'-0" x 14'-0" x 2" A OH NONE (none) HARDWARE BY MANUFACTURER (COORDINATE W/ELECTRICAL)
103 EXTERIOR SHOP 10'-0" x 10'-0" x 2" A OH NONE (none) HARDWARE BY MANUFACTURER (COORDINATE W/ELECTRICAL)
104 EXTERIOR SHOP 3-0" x 6'-8" x 1 3/4" B HM NONE HDW-1 SINGLE
ENTRANCE
105 STOR. SHOP 2'-6" x 6'-8" x 1 3/4" D HM NONE HDW-7 EVIDENCE
106 EVIDENCE / STOR. SHOP 3-0" x 6'-8" x 1 3/4" C MTL NONE HDW-4 OFFICE
108 SHOP R.R. 3'-0" x 6'-8" x 1 3/4" D HM NONE HDW-5 PRIVATE
RESTROOM
110 UTILITY / MECH SHOP 3'-0" x 6'-8" x 1 3/4" D HM NONE HDW-8 PASSAGE
DOOR
111 UTILITY / MECH EXTERIOR 3-0" x 6'-8" x 1 3/4" B HM NONE HDW-1 SINGLE
ENTRANCE
1/4" = 1'-0"
DOOR SCHEDULE
1/4" = 1'-0"
WINDOW SCHEDULE
DOOR HARDWARE
HDW HARDWARE
HDW-1 SINGLE ENTRANCE 1 CYLINDER LOCK
1 1/2 PR BUTTS
1 THRESHOLD
WEATHERSTRIPPING
HDW-4 OFFICE 1 1/2 PR BUTTS
1 LOCKSET ANSI F-82/
BHMA B
1 WALL STOP
1 SET SILENCERS
HDW-5 PRIVATE RESTROOM 1 1/2 PR BUTTS
1 LOCKSET F-76
1 WALL STOP
1 SET SILENCERS
KICK PLATE
HDW-7 EVIDENCE 1 1/2 PR BUTTS
1 LOCKSET ANSI F86/
BHMA D
1 WALL STOP
1 SET SILENCERS
HDW-8 PASSAGE DOOR 1 1/2 PR BUTTS
1 LOCKSET ANSI F-75/
BHMA N
1 WALL STOP
1 SET SILENCERS
GENERAL NOTES:
1. HARDWARE:
HINGES:BY STANLEY, HAGER OR APPROVED
EQUAL.
LOCKSETS:BY SARGENT, ADAMS-RITE,
SCHLAGE OR APPROVED EQUAL .
CLOSER:BY LCN, DORMA OR APPROVED
EQUAL.
WEATHERSTRIPPING, THRESHOLD, AND
SWEEP:BY PEMKO OR APPROVED EQUAL
KEY SYSTEM - -SARGENT (CY-1) CYLINDERS
FOR ALUMINUM ENTRANCES.
2. CONTRACTOR RESPONSIBLE TO NOTIFY
DESIGNER OF SUBSTITUTIONS FOR NOTED
HARDWARE.
3. DOOR & DOOR HARDWARE SUBMITTAL
REQUIRED.
4. HOLLOW METAL DOORS: 18 GAUGE
METAL. HOLLOW METAL DOOR FRAMES: 16
GAUGE AND WELD UP.
5. KNOCKDOWN FRAMES: 18 GA OR 20GA?
HARDWARE COLOR:
1 2
1 1/2" = 1'-0"2 HM DR DET
1 1/2" = 1'-0"3 HM DR JAMB DTL
1 1/2" = 1'-0"4 THRESHOLD AT HM DR
1 1/2" = 1'-0"7 THRESHOLD AT OH DR
1 1/2" = 1'-0"5 OH DR HD DTL-MTL SIDING
1 1/2" = 1'-0"6 OH DR JAMB DTL-MTL SIDING
3/4" = 1'-0"11 WIN FLASHING SEQUENCE
1 1/2" = 1'-0"8 VINYL WIN HD DTL-MTL SIDING
1 1/2" = 1'-0"9 VINYL WIN JAMB DTL-MTL SIDING
1 1/2" = 1'-0"10 VINYL WIN SILL DTL-MTL SIDING
MELISSA
KATHLEEN
STEINER
13707
SN
E D
ECIL
A RCHIT
E
C
T
ANS
T
AT
EOF M O N T A
BOZEMAN,
MT
0.783/0.221
0.62/0.288
115 MPH
100 PSF
II
LIGHT FRAMED WALL SYSTEM W/
WOOD STRUCTURAL PANELS
D
3.345 KIPS
1.0
2. FLOOR LIVE LOAD
3. ROOF LIVE LOAD -
4. ROOF SNOW LOAD
5. WIND LOAD
A. BASIC WIND SPEED (3-SECOND GUST) -
B. WIND IMPORTANCE FACTOR-
C. BUILDING CATEGORY -
D. WIND EXPOSURE -
6. EARTHQUAKE DESIGN DATA
A. SEISMIC IMPORTANCE FACTOR -
D. SPECTRAL RESPONSE COEFFICIENTS SDS / SD1 -
E. SITE CLASS -
H. BASE SHEAR
F. SEISMIC DESIGN CATEGORY
G. BASIC SEISMIC FORCE RESISTING SYSTEM-
20 PSF1. ROOF DEAD LOAD
B. OCCUPANCY CATEGORY-
C. MAPPED SPECTRAL RESPONSE ACCELERATIONS Ss / S1 -
I. SEISMIC RESPONSE COEFFICIENT Cs
J. RESPONSE MODIFICATION FACTOR
K. ANALYSIS PROCEDURE USED
II
0.095
6.5
EQUIVALENT LATERAL FORCE
B
NOTE: SEE DRIFTS &
UNBALANCED SNOW
LOADS ON 6/S0.00
B. DESIGN LOADS
STRUCTURAL DESIGN
A. GOVERNING CODES AND GENERAL NOTES
INTERNATIONAL BUILDING CODE (IBC) 2018
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)- MINIMUM DESIGN LOADS FOR BUILDINGS & OTHER STRUCTURES- ASCE 7-16
AMERICAN CONCRETE INSTITUTE (ACI) - BUILDING CODE & COMMENTARY ACI 318-14
AMERICAN CONCRETE INSTITUTE (ACI) - BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES ACI 530-14
AMERICAN INSTITUTE STEEL OF CONSTRUCTION (AISC) - STEEL CONSTRUCTION MANUAL FOURTEENTH EDITION AISC 360-16
AMERICAN FOREST & PAPER ASSOCIATION (AF&PA) - NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION NDS 2018
AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (AITC) 9TH EDITION
THE CONTRACTOR IS RESPONSIBLE FOR LOCATING OR HAVING LOCATED THE BUILDING ON THE SITE AND VERIFYING ALL
FOUNDATION DIMENSIONS, AND SETBACK REQUIREMENTS FROM EASEMENTS AND PROPERTY LINES WITH THE ARCHITECT PRIOR
TO CONSTRUCTION.
D
20 PSF
1.0
46 PSF
1.0
60.0 PSF A. THE GROUND SNOW LOAD, Pg -
B. AWNING SNOW LOAD, Pf -
C. SNOW EXPOSURE FACTOR, Ce -
D. SNOW LOAD IMPORTANCE FACTOR, I -
E. THERMAL FACTOR, Ct -
1
1.1
50.40 PSF
6. SOLE PLATE TO JOIST OR BLOCKING, TYPICAL FACE NAIL
DOUBLE TOP PLATES, SEE DETAIL FOR LAP SPLICE
SOLE PLATE TO JOIST OR BLOCKING, AT BRACED WALL PANELS
10. DOUBLED TOP PLATES, TYPICAL FACE NAIL
11. BLOCKING BETWEEN JOISTS OR RAFTERS TO TOP PLATE, TOE NAIL
1. JOIST TO SILL OR GIRDER, TOENAIL
2. BRIDGING TO JOIST, TOENAIL EACH END
3. 1"X6" SUBFLOOR OR LESS TO EACH JOIST, FACE NAIL
4. WIDER THAN 1"X6" SUBFLOOR TO EACH JOIST, FACE NAIL
5. 2" SUBFLOOR TO JOIST OR GIRDER, BLIND AND FACE NAIL
17. CEILING JOISTS, LAPS OVER PARTITIONS, FACE NAIL
18. CEILING JOISTS TO PARALLEL RAFTERS, FACE NAIL
20. 1" BRACE TO EACH STUD AND PLATE, FACE NAIL
21. 1"X8" SHEATHING OR LESS TO EACH BEARING, FACE NAIL
22. WIDER THAN 1"X8" SHEATHING TO EACH BEARING, FACE NAIL
26. WOOD STRUCTURAL AND PARTICLE BOARD
13. TOP PLATES, LAPS AND INTERSECTIONS, FACE NAIL
14. CONTINUOUS HEADER, TWO PIECES
15. CEILING JOIST TO PLATE, TOENAIL
16. CONTINUOUS HEADER TO STUD, TOENAIL
12. RIM JOIST TO TOP PLATE, TOENAIL
7. TOP PLATE TO STUD, END NAIL
8. STUD TO SOLE PLATE
9. DOUBLE STUDS, FACE NAIL
5/8"
29. INTERIOR PANELING
3/8"
1/4"
25/32"
28. FIBERBOARD SHEATHING:
1/2"
24. BUILT-UP GIRDER AND BEAMS
1/2" OR LESS
27. PANEL SIDING (TO FRAMING):
25. 2" PLANKS
19. RAFTER TO PLATE, TOE NAIL
23. BUILT-UP CORNER STUDS
16d @ 16" o.c.
2-16d
16d @ 16" o.c.
3-16d @ 16"
16d @ 24" o.c.
3-8d
4-8d,TOENAIL OR 2-16d, END NAIL
3-8d
2-8d
2-8d
3-8d
2-16d
8d
No. 11 ga.
No. 16 ga.
No. 11 ga.
No. 16 ga.
6d
4d
6d
8d
3-8d
2-8d
3-16d
2-8d
3-8d
16d @ 24" o.c.
BOTTOM AND STAGGERED 2-20d
AT ENDS AND AT EACH SPLICE
2-16d AT EACH BEARING
SEE STRUCTURAL PLANS
20d @ 32" o.c. AT TOP AND
6d
2-16d
3-8d
4-8d
3-16d
16d @ 16" o.c. ALONG EACH EDGE
8d @ 6" o.c.
1. COMMON OR BOX NAILS MAY BE USED EXCEPT WHERE OTHERWISE STATED.
2. CORROSION-RESISTANT SIDING OR CASING NAILS CONFORMING TO TABLE 2304.9.1 OF IBC.
3. CORROSION-RESISTANT ROOFING NAILS WITH 7/16" DIA. HEAD AND 1-1/2" LENGTH FOR 1/2" SHEATHING AND
1-3/4" LENGTH FOR 25/32" SHEATHING CONFORMING TO TABLE 2304.9.1 OF IBC.
4. CORROSION-RESISTANT STAPLES WITH NOMINAL 7/16" CROWN AND 1-1/8" LENGTH FOR 1/2" SHEATHING AND
1-1/2" LENGTH FOR 25/32" SHEATHING CONFORMING TO TABLE 2304.9.1 OF IBC.
5. PANEL SUPPORTS AT 16" (20" IF STRENGTH AXIS IN THE LONG DIRECTION OF THE PANEL, UNLESS OTHERWISE
MARKED). CASING OR FINISH NAILS SPACED 6" ON PANEL EDGES, 12" AT INTERMEDIATE SUPPORTS.
6. PANEL SUPPORTS AT 24". CASING OR FINISH NAILS SPACED 6" ON PANEL EDGES, 12" AT INTERMEDIATE
SUPPORTS.
7. WHEN 3X SOLE PLATE IS USED, END NAILING SHALL BE 2-30d BOX OR COMMON NAILS TO STUD.
CONNECTION NAILING 1
3
7
5
6
5
4
4
4
2
3
8
CONCRETE
A. SEE 7/S0.0 FOR SITE PREP AND STRUCTURAL FILL REQUIREMENTS ON THIS SHEET FOR SUBGRADE PREP.
B. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING OR HAVING LOCATED THE BUILDING ON THE SITE AND VERIFYING ALL
FOUNDATION DIMENSIONS, AND SETBACK REQUIREMENTS FROM EASEMENTS AND PROPERTY LINES WITH THE ARCHITECT PRIOR
TO CONSTRUCTION.
C. ALL CEMENT IN CONCRETE TO CONFORM TO ASTM C150 SPECIFICATION FOR PORTLAND CEMENT.
D. ALL AGGREGATE TO CONFORM TO ASTM C33 SPECIFICATION FOR CONCRETE AGGREGATES.
E. CONCRETE SUPPLIER TO MIX BASED ON THEIR TESTING TO ASSURE THIS MINIMUM COMPRESSIVE STRENGTH PER ACI 318 SECTION
5.3. IN THE ABSENCE OF SUFFICIENT TEST DATA, CONCRETE PROPORTIONING SHALL BE DONE IN ACCORDANCE WITH ACI 318
SECTION 5.3.1.2, 5.3.2.2, 5.3.3.2, & 5.4.
F. THE MAXIMUM NOMINAL AGGREGATE SIZE SHALL BE ONE FIFTH THE NARROWEST DIMENSION BETWEEN THE FORMS OR ONE
THIRD THE DEPTH OF THE SLAB, OR THREE-FOURTHS THE MINIMUM CLEAR SPACING BETWEEN INDIVIDUAL REINFORCING BARS
OR WIRES, WHICHEVER APPLIES. THESE PROVISIONS ARE TO ASSURE CONCRETE PLACEMENT WITHOUT VOIDS OR HONEYCOMBS
AND MAY BE WAIVED ONLY BY THE BUILDING OFFICIAL IF THEY JUDGE THAT LARGER SIZES ARE ADEQUATE BECAUSE OF
WORKABILITY AND METHODS OF CONSOLIDATION.
G. CONCRETE CURING (OTHER THAN HIGH-EARLY) SHALL BE MAINTAINED ABOVE A TEMPERATURE OF 50°F AND IN A MOIST
CONDITION FOR AT LEAST THE FIRST SEVEN DAYS AFTER PLACEMENT. HIGH EARLY CONCRETE SHALL BE CURED ABOVE 50°F AND
IN A MOIST CONDITION FOR AT LEAST THE FIRST THREE DAYS.
H. ADEQUATE EQUIPMENT SHALL BE PROVIDED FOR HEATING CONCRETE MATERIALS AND PROTECTING CONCRETE DURING
FREEZING OR NEAR-FREEZING WEATHER. ALL CONCRETE MATERIALS, REINFORCEMENT, FORMS, FILLERS, AND GROUND WHICH
THE CONCRETE IS TO BE IN CONTACT WITH IS TO BE FREE OF FROST. FROZEN MATERIALS OR MATERIALS CONTAINING ICE SHALL
NOT BE USED.
I. DURING HOT WEATHER, PROPER ATTENTION SHALL BE GIVEN TO INGREDIENTS, PRODUCTION METHODS, HANDLING, PLACING,
PROTECTION, AND CURING TO PREVENT EXCESSIVE CONCRETE TEMPERATURES AND EVAPORATION THAT MAY IMPAIR REQUIRED
STRENGTH OR SERVICEABILITY OF THE MATERIAL.
J. ALL WALLS & FOUNDATIONS SHALL BE MECHANICALLY CONSOLIDATED. VIBRATORS SHALL BE INSERTED IN PREVIOUS POURED
FRESH CONCRETE TO PREVENT COLD JOINTS WHEN MULTIPLE LAYER OF CONCRETE ARE PLACED IN A WALL.
K. CONDUITS, PIPES, AND SLEEVES SHALL BE ALLOWED ONLY WHERE NOTED ON THE PLANS. ANY ADDITIONAL ALTERATIONS ARE
NOT PERMITTED WITHOUT ENGINEER APPROVAL THAT IT WILL NOT COMPROMISE STRUCTURAL INTEGRITY.
L. THE SURFACE OF ALL CONSTRUCTION JOINTS SHALL BE CLEANED AND LAITANCE REMOVED. IMMEDIATELY BEFORE NEW
CONCRETE IS PLACED, JOINTS SHALL BE WETTED AND STANDING WATER REMOVED. PROVISIONS SHALL BE MADE TO TRANSFER
SHEAR FORCES THROUGH THE CONSTRUCTION JOINT.
M. INTERIOR SLAB ON GRADE SHALL BE CLASS 1 W/ A NORMAL STEEL TROWELED FINISH. TOTAL AIR CONTENT SHALL NOT EXCEED
3%. FLOOR SHALL BE WITHIN 1/8" PER 10 FT FOR FLATNESS REQUIREMENTS. SLAB SHALL BE SEALED WITH A HIGH SOLID CONTENT
SOLVENT BASED CURE & SEAL, EUCLID SUPER DIAMOND OR APPROVED EQUAL
N. CONCRETE IN SIDEWALKS OR EXTERIOR SLABS THAT WILL BE EXPOSED TO FREEZING/THAWING OR DEICING CHEMICALS SHALL
HAVE A MINIMUM 0.45 WATER/CEMENTITIOUS RATIO BY WEIGHT FOR NORMAL WEIGHT AGGREGATE CONCRETE AND BE 4000 PSI
MINIMUM.
O. ALL REINFORCING BARS SPECIFIED SHALL BE DEFORMED BARS AT LEAST GRADE 60.
P. ALL BENDING OF REINFORCING MATERIAL SHALL BE DONE COLD AND MINIMUM BEND DIAMETER SHALL BE 6 TIMES THE
NOMINAL BAR DIAMETER FOR #3-#8 BAR AND 8 TIMES THE NOMINAL BAR DIAMETER FOR #9-#11 BARS. REINFORCEMENT
PARTIALLY IMBEDDED IN CONCRETE MAY BE FIELD BENT.
Q. REINFORCEMENT, ANCHORS AND EMBEDDED ITEMS SHALL BE ACCURATELY PLACED AND SUPPORTED BEFORE CONCRETE IS
PLACED AND SHALL BE SECURED AGAINST DISPLACEMENT WITHIN TOLERANCES OF SECTION 1907.5 OF THE CURRENT VERSION OF
CURRENT IBC.
R. #5 BAR REQUIRED 2" CLEAR FROM TOP AND BOTTOM OF STEM WALLS AROUND FULL PERIMETER OF FOUNDATION, MIN.
S. STANDARD HOOK ON REINFORCING BAR SHALL BE:
1. 180° BEND PLUS 4d EXTENSION, BUT NOT LESS THAN 2 1/2" AT FREE END OF BAR.
2. 90° BEND PLUS 12d EXTENSION AT FREE END OF BAR.
3. FOR STIRRUP AND TIE HOOKS: SEE S3.0
T. MINIMUM REBAR LAPS - FOR #3-15", #4-20", #5-24 & #6-30" WITH A CLEAR SPACING OF NOT LESS THAN 2d AND CLEAR COVER OF
NOT LESS THAN d. ALL OTHER SPLICES CONDITIONS SHALL BE BY THE EOR AND ILLUSTRATED ON FOUNDATION PLAN & DETAIL
SHEETS.
U. REFER TO TABLE BELOW FOR MINIMUM COVER AND TOTAL AIR CONTENT FOR CONCRETE IN DIFFERENT SERVICE CONDITIONS.
SUCH AS A CONCRETE SLAB EXPOSED TO THE WEATHER:
No. 9 THRU No. 18 BAR
No. 8 BAR AND SMALLER
CONCRETE TILT-UP PANELS CAST AGAINST A RIGID HORIZONTAL SURFACE
SLABS, WALLS, AND JOISTS:
No. 14 AND No. 18 BAR
No. 11 BAR AND SMALLER
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE GROUND:
1-1/2
1
2
3/4
CAST-IN-PLACE CONCRETE (NON-PRESTRESSED)
CONCRETE EXPOSED TO EARTH OR WEATHER:
No. 6 THRU No. 18 BAR
No. 5 BAR, W31 OR D31 WIRE AND SMALLER
CONCRETE CAST AGAINST & PERMANENTLY EXPOSED TO EARTH 3
2
1-1/2
MINIMUM COVER (IN)DESCRIPTION
CONCRETE PROTECTION FOR REINFORCEMENT
FOOTINGS
FOUNDATION WALLS
INTERIOR SLAB
EXTERIOR SLAB
3000 PSI
3000 PSI
4000 PSI
4000 PSI
28 DAY COMPRESSIVE STRENGTH
3/1
3/1
3/1
3/1
SLUMP (IN) MAX/MIN
.5
.5
.45
.45
MAX W/C RATIO
6 +/- 1.5%
6 +/- 1.5%
3 MAX
6 +/- 1.5%
AIR CONTENT (%)
PREFABRICATED WOOD TRUSSES
A. CODES AND FABRICATION: MANUFACTURER'S APPROVED ICC PRODUCT EVALUATION REPORTS.
B. GRADE STAMPED DOUGLAS FIR/LARCH NO. 2 OR BETTER, OR AS REQ'D BY DESIGN.
C. DESIGN REQUIREMENTS:
1. TOP CHORD DEAD LOAD 12 PSF, BOTTOM CHORD DEAD LOAD 8 PSF
2. DEFLECTION: ROOF TOTAL LOAD DEFLECTION SHALL NOT EXCEED L/280, LIVE LOAD DEFLECTION SHALL NOT EXCEED
L/360.
D. CALCULATIONS & SHOP DRAWINGS: SUBMIT FOR REVIEW, SHOP DRAWINGS AND CALCULATIONS BY A LICENSED ENGINEER IN THE
STATE OF THE PROJECT, FOR THE DESIGN LOADS, INCLUDING MAXIMUM REACTION, SHEAR, MOMENT, AND DEFLECTION IN
COMPARISON TO THE ALLOWABLES. SIZE THE TOP CHORD FOR THE DIAPHRAGM NAILING AND A 2X MINIMUM NOMINAL WIDTH.
THE TRUSSES SHOWN ON THE DRAWINGS ARE SCHEMATIC AND MAY REQUIRE SIZE OR SPACING MODIFICATIONS. VERIFY WITH
BEARING LOCATIONS BEFORE MAKING ANY CHANGES.
E. BLOCKING, BRACING AND BRIDGING: AS REQUIRED BY THE MANUFACTURER'S APPROVED PRODUCT EVALUATION REPORTS, THE
IBC, ICC APPROVALS, THE CALCULATIONS AND THE DRAWINGS.
F. TRUSS CHANGES: OBTAIN WRITTEN CONSENT FROM THE TRUSS MFR ENGINEER TO CHANGE THE TRUSS TYPE, WIDTH, CHORD
DEPTH, TRUSS SHAPE OR SPACING.
G. TRUSS MARKINGS: EACH TRUSS SHALL BE LEGIBLY BRANDED, MARKED OR OTHERWISE HAVE PERMANENTLY AFFIXED THERETO THE
FOLLOWING INFORMATION WITHIN 2' OF THE CENTER OF THE SPAN ON THE FACE OF THE BOTTOM CHORD:
H. TRUSS MFR SHALL CERTIFY THAT ALL LOADING IS PER LOCAL CONDITIONS STATED ON 'STRUCTURAL LOAD INFORMATION' NOTE.
I. TRUSS MFR SHALL CERTIFY THAT THE CALCULATIONS REFLECT COMPLIANCE WITH THE LATEST EDITION OF IBC FOR UNBALANCED
SNOW LOADS, FOR DRIFT LOADING, FOR IMPACT LOADING AS NOTED ON THE PLANS. ALL EAVES SHALL BE DESIGNED FOR 2 TIMES
THE LIVE LOAD.
J. ALL TRUSS TO TRUSS CONNECTIONS SHALL BE THE SOLE RESPONSIBILITY OF THE TRUSS MANUFACTURER.
K. STAMPED SHOP DRAWINGS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL AND ENGINEER FOR REVIEW BEFORE ANY
FABRICATION.
L. TRUSS HANDLING AND JOB-SITE STORAGE SHALL BE PER TPI STANDARDS AND NOT AFFECT TRUSS PERFORMANCE.
M. CONFIRM WEIGHT, SIZE AND LOCATION OF MECHANICAL EQUIPMENT PRIOR TO DESIGN OF TRUSSES TO ENSURE POINT LOADS ARE
ACCOUNTED FOR IN TRUSS DESIGN.
STRUCTURAL COMPOSITE LUMBER (SCL)
A. PRODUCTS: STRUCTURAL COMPOSITE LUMBER (SCL)
1. I-JOIST PRODUCTS SHALL BE DESIGNED TO FIT THE DIMENSIONS AND LOADS INDICATED ON PLANS. JOISTS SHALL
BE MANUFACTURED WITH ORIENTED STRAND WEBS, LAMINATED VENEER LUMBER FLANGES AND WATERPROOF
STRUCTURAL AHDESIVES.
2. RIMBOARD SHALL BE BCI 1 1/2 VERSA STRAND 0.8 WITH A MINIMUM MODULUS OF ELASTICITY OF 800,000 PSI
3. LAMINATED VENEER LUMBER BEAMS SHALL BE VERSA-LAM 2.0 2800 AND 2.0 3100 OR APPROVED EQUAL.
MINIMUM MODULUS OF ELASTICITY OF 2,000,000 PSI AND BENDING STRENGTH OF 2,800 AND 3,100 PSI
DEPENDING ON SIZE.
4. GLU-LAMS - UNO ALL GLULAMS SHALL BE ARCHITECTURAL APPEARANCE BEAMS AND COLUMNS WITH VOIDS
GREATER THAN 3/4" FILLED. IF AVAILABLE HEADER BEAMS MAY BE USED IN CONCEALED APPLICATIONS.
A. SIMPLE SPAN GLULAM BEAMS SHALL BE BOISE GLULAM 24F-V4 UNBALANCED UNO WITH MINIMUM
MODULUS OF ELASTICITY OF 1,800,000 PSI, BENDING STRENGTH OF 2,400 TENSION ZONE IN TENSION,
1,850 PSI COMPRESSION ZONE IN TENSION. SIMPLE SPAN GLULAM BEAMS SHALL BE CAMBERED WITH A
3,500 RADIUS FOR SPANS OVER 25' UNLESS SPECIFIED OTHERWISE ON PLANS.
B. MULTIPLE SPAN GLULAM BEAMS SHALL BE BOISE GLULAM 24F-V8 BALANCED UNO WITH MINIMUM
MODULUS OF ELASTICITY OF 1,800,000 PSI, BENDING STRENGTH OF 2,400 PSI IN BOTH TENSION ZONE IN
TENSION AND COMPRESSION ZONE IN TENSION UNLESS SPECIFIED OTHERWISE ON PLANS.
C. GLULAM COLUMNS SHALL BE BOISE GLULAM COLUMNS UNO WITH MINIMUM MODULUS OF ELASTICITY
OF 1,900,000 PSI PERPENDICULAR AND PARALLEL TO THE GLUELINES, BENDING STRENGTH OF 2,000 PSI
PERPENDICULAR AND 2,100 PSI PARALLEL TO GLUELINES AND 2,300 PSI COMPRESSION STRENGTH
PARALLEL TO THE GRAIN. ARCHITECTURAL ACCENT COLUMNS CAN HAVE GLULAM BEAM SPECIFICATIONS
B. FOR JOIST & BEAM SUBSTITUTIONS: A COMPLETE SET OF DESIGN CALCULATIONS SHALL BE PREPARED BY THE
MANUFACTURER VERIFYING MEMBERS MEET OR EXCEEDING THE LOADS SPECIFIED AND THE GEOMETRY SHOWN.
CALCULATIONS AND LAYOUT DRAWING SHALL BE SEALED BY A PROFESSIONAL ENGINEER LICENSED TO PRACTICE IN THE
STATE OF THIS PROJECT.
C. FOR JOIST AND BEAM SUBSTITUTIONS. SHOP DRAWINGS SHOWING LAYOUT AND DETAIL NECESSARY FOR DETERMINING FIT
AND PLACEMENT IN THE BUILDING SHALL BE PROVIDED BY THE SUPPLIER TO THE EOR FOR APPROVAL ALONG WITH THE
DESIGN CALCULATIONS.
D. ALL SCL LUMBER SHALL BE MANUFACTURED IN ACCORDANCE WITH AN APPROVED ICC MATERIALS REPORT, AND PRODUCED
WITH MATERIALS SATISFYING THE APPROVED ICC-ES CODE REPORT, PRODUCTS SHALL BE PROVEN BY TESTING AND
EVALUATION IN ACCORDANCE WITH THE PROVISIONS OF ASTM D-5055.
E. IDENTIFICATION: EACH OF THE SCL MEMBERS EXCLUDING G/L'S SHALL BE IDENTIFIED BY A STAMP INDICATING THE JOIST
SERIES OR MEMBER PROPERTIES, ICC-ES REPORT NUMBER, MANUFACTURER'S NAME, PLANT NUMBER, DATE OF
FABRICATION AND THE INDEPENDENT INSPECTION AGENCY'S LOGO UNLESS ARCHITECTURAL GRADE IS SPECIFIED.
COORDINATE WITH ARCHITECT IN THIS CASE.
F. HANGERS AND HARDWARE : ANY HARDWARE SHOWN ON THE PLANS TO ATTACH THE MEMBERS TO APPROPRIATE WALLS,
BEAMS, HEADERS, ETC. SHALL BE SPECIFIED AND CERTIFIED TO MEET THE LOAD REQUIRED FOR THE APPLICATION. ALL
HARDWARE SHALL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS.
G. INSTALLATION: SCL, IF STORED PRIOR TO INSTALLATION, SHALL BE PROTECTED FROM THE WEATHER. THEY SHALL BE
HANDLED WITH CARE SO THEY ARE NOT DAMAGED. MEMBERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PLANS AND
ANY MANUFACTURER DRAWINGS AND INSTALLATION SUGGESTIONS. TEMPORARY CONSTRUCTION LOADS THAT CAUSE
STRESSES BEYOND DESIGN LIMITS ARE NOT PERMITTED, SAFETY BRACING IS TO BE PROVIDED BY THE INSTALLED TO KEEP THE
MEMBER STRAIGHT AND PLUMB AS REQUIRED, AND TO ENSURE ADEQUATE LATERAL SUPPORT FOR THE INDIVIDUAL
MEMBERS AND THE ENTIRE SYSTEM UNTIL THE SHEATHING MATERIAL IS APPLIED.
H. WARRANTY: THE PRODUCTS DELIVERED SHALL BE FREE FROM MANUFACTURING ERRORS OR DEFECTS IN WORKMANSHIP
AND MATERIAL. THE PRODUCTS, WHEN CORRECTLY INSTALLED AND MAINTAINED, SHALL BE WARRANTED TO PERFORM AS
DESIGNED FOR THE NORMAL AND EXPECTED LIFE OF THE BUILDING.
SUBMITTALS
SUBMITTALS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD (EOR) AND FORWARDED TO THE BUILDING OFFICIAL FOR REVIEW PRIOR TO
FABRICATION IN ACCORDANCE WITH IBC107.3.4.1. ALLOW 7-14 DAYS FOR REVIEW BY THE EOR.
A. SUBMIT MIX DESIGNS FOR:
a. CAST-IN-PLACE CONCRETE
B. SUBMIT SHOP DRAWINGS FOR:
a. REINFORCING STEEL
C. SUBMIT SHOP DRAWINGS , STAMPED BY A REGISTERED STRUCTURAL ENGINEER LICENSED IN THE STATE OF WASHINGTON, FOR:
a. PRE-FABRICATED WOOD TRUSSES
b. PRE-FABRICATED JOISTS
A. ALL STRUCTURAL FRAMING SHALL BE DESIGNED FOR BALANCED SNOW LOADING PER SNOW LOAD ABOVE AND UNBALANCED
LOADING AS SHOWN. BALANCED SNOW LOADING DOES NOT OCCUR CONCURRENTLY WITH UNBALANCED SNOW LOADING.
BOTH CASES MUST BE EXAMINED DURING DESIGN.
B. UNBALANCED SNOW LOADING IS PER CURRENT VERSION OF ASCE 7.
C. UNBALANCED AND BALANCED SNOW LOADING SHALL BE EXAMINED IN CONJUNCTION WITH SNOW DRIFT PLAN.
D. FIGURE ABOVE SHOWS UNBALANCED LOADING DUE TO WIND FROM THE LEFT, BOTH WIND DIRECTIONS MUST BE
ACCOUNTED FOR DURING DESIGN.
E. L = x 2.2 x √S 2.2 x 21.2
F. ROOF TRUSSES SHALL BE DESIGNED FOR SNOW DRIFT LOADING SHOWN IN ADDITION TO ALL OTHER LOADS INDICATED
ON THE PLANS, DETAILS AND NOTES.
G. ROOFS THAT DRAIN WATER OVER THE EAVES SHALL BE DESIGNED FOR 2XPF ON THE OVERHANGING PORTION OF THE EAVE.
THIS SHALL BE COMBINED WITH DEAD LOAD ONLY.
8
3 Pr=√S
L
Pa
LOAD = 0.3xPs
1
S
Ps
SNOW LOADING
SOILS AND FOUNDATIONS
A. FOUNDATIONS HAVE BEEN DESIGNED BASED ON ALLOWABLE BEARING PRESSURE OF1,500 PSF
B. CONSTRUCTION MATERIAL -EARTHWORK:
1. STRUCTURAL FILL SHALL CONSIST OF APPROVED ON-SITE SOILS OR BE FROM AN APPROVED MATERIAL SOURCE.
2. GRANULAR STRUCTURAL FILL SHALL MEET THE FOLLOWING GRADATION & COMPOSITION
SIEVE SIZE % PASSING BY WEIGHT
3 INCH 100
1 1/2"85-100
NO. 4 30-60
NO. 200 10 MAXIMUM
BOTH STRUCTURAL FILL & GRANULAR STRUCTURAL FILL SHALL MEET THE FOLLOWING:
a. PLACED IN NO GREATER THAN 8" THICK LIFTS COMPACTED TO A MINIMUM OF 95% OF MAXIMUM DRY
DENSITY AS DETERMINED BY ASTM D698
b. MOISTURE CONTENT OF THE STRUCTURAL FILL AT THE TIME OF COMPACTION SHOULD BE WITHIN 3% OF
OPTIMUM MOISTURE CONTENT AS DETERMINED BY ASTM 698
c. COBBLES AND BOULDERS LARGER THAN 4" MAXIMUM SIZE SHOULD NOT BE USED IN FILL MATERIALS
d. SAND & GRAVEL SIZE PARTICLES COMPRISING THE FILL SHOULD BE HARD DURABLE ROCK MATERIALS THAT
WILL NOT DEGRADE BY MOISTENING OR UNDER MECHANICAL ACTION OF THE COMPACTION EQUIPMENT; I.E.
NO SHALE OR OTHER CLAYEY ROCK TYPES
e. THE BINDER/FINES SHOULD HAVE MAXIMUM LIQUID LIMIT AND PLASTIC INDEX VALUES OF 25 & 10%
RESPECTIVELY
f. NO FROZEN, ORGANIC OR OTHER DELETERIOUS MATERIALS SHOULD BE PRESENT IN FILL MATERIAL.
g. GRANULAR STRUCTURAL FILL SHALL BE USED UNDER BUILDING FOUNDATION AND IF THE FILL OPERATIONS
ARE PLANNED FOR RELATIVELY WET FALL, WINTER & SPRING MONTHS.
3. OPEN GRADED ANGULAR CRUSH ROCK:
a. BETWEEN 1/4 TO 3/4" ANGULAR CRUSHED ROCK
b. COMPACTED USING VIBRATORY COMPACTION METHODS UNTIL WELL KEYED
4. 1/4 TO 1 1/2" OPEN GRADED DRAINAGE AGGREGATE
5. NON-WOVEN DRAINAGE GEOTEXTILE: MIRAFI 140N OR APPROVED EQUAL. EDGES SHALL BE OVERLAPPED AND HELD IN
PLACE DURING BACK FILL OPERATION TO ENSURE THE DRAIN AGGREGATE IS COMPLETELY ENCLOSED FOLLOWING
BACKFILL
6. WOVEN SEPARATION FABRIC: MIRAFI 500X OR APPROVED EQUAL.
7. VAPOR BARRIER: 10 MIL WR MEADOWS PERMIATOR, STEGO INDUSTRIES STEGO WRAP CLASS A OR APPROVED EQUAL.
ALL SEAMS SHALL BE OVERLAPPED & SEALED WITH MANUFACTURER APPROVED TAPE. ALL PROTRUSIONS &
PENETRATIONS SHALL BE SEALED. HOLES SHALL BE REPAIRED. SEAL THE VAPOR BARRIER TO THE VERTICAL FACE OF THE
STEM WALL WITH THE MANUFACTURER RECOMMENDED ATTACHMENT DETAIL. INSTALLATION SHALL MEET ASTM E
1643-C STANDARD PRACTICE FOR INSTALLATION OF VAPOR RETARDER USED IN CONTACT WITH EARTH OR FILL UNDER
CONCRETE SLAB
8. DAMPPROOFING: BASF HYDROCIDE 700B COLD APPLIED WATER BASED REINFORCED EMULSIFIED ASPHALTIC
DAMPPROOFING OR APPROVED EQUAL. HYDROCIDE 700B IS AN ASPHALT-BASED CLAY EMULSION WITH FIBERS.
APPLICATION SHALL BE APPLIED BY BRUSH, ROLLER, OR SPRAY WITH THE PROPER EQUIPMENT PER MANUFACTURER
RECOMMENDATIONS. MATERIALS AND INSTALLATION SHALL MEET ASTM D 1227, TYPE 2, CLASS 1, AND ASTM D 1187,
TYPE 1
9. FOUNDATION & SLAB INSULATION: USE DOW CHEMICAL BUILDING PRODUCT OR APPROVED EQUAL
a. VERTICAL SLAB INSULATION
• EXTERIOR APPLICATION -STYROFOAM BRAND PERIMATE INSULATION 2" THICK WITH A MINIMUM
COMPRESSIVE STRENGTH OF 30 PSI. TOP OF INSULATION SHALL BE PROTECTED DURING &
FOLLOWING CONSTRUCTION
• INTERIOR APPLICATION -STYROFOAM BRAND EXTRUDED POLYSTYRENE FOAM SQUARE EDGE
INSULATION 2" THICK UNO
b. HORIZONTAL INSULATION
• SUB SLABS NOT SUBJECT TO VEHICLE TRAFFIC STYROFOAM BRAND EXTRUDED POLYSTYRENE FOAM
SQUARE EDGE INSULATION 2" THICK UNO W/ MIN. COMPRESSIVE STRENGTH OF 25 PSI BEDDED IN
SAND. (THIS INCLUDES HEATED SLABS & FOOTINGS W/ INSUFFICIENT FROST PROTECTION.
• SUB SLABS SUBJECT TO VEHICLE TRAFFIC STYROFOAM HIGH LOAD 60 EXTRUDED POLYSTYRENE FOAM
SQUARE EDGE INSULATION 2" THICK W/ MIN. COMPRESSIVE STRENGTH OF 60 PSI, BEDDED IN
SAND
C. SITE PREPARATION:
1. THE REMOVAL OF TOPSOIL, OTHER ORGANIC MATERIAL & FILL, INCLUDING THE CLEARING AND GRUBBING OF SURFICIAL
VEGETATION AND ROOT ZONES, SHOULD BE ACCOMPLISHED WITHIN THE CONSTRUCTION ZONE PRIOR TO ANY
EARTHWORK CONSTRUCTION.
2. SURFACE DRAINAGE SHOULD BE ESTABLISHED TO DIRECT RUNOFF AWAY FROM THE CONSTRUCTION AREA
3. CARE SHOULD BE TAKEN TO MINIMIZE CONSTRUCTION TRAFFIC OVER MOISTURE SENSITIVE SUBGRADE SOILS DURING
WET WEATHER CONDITIONS.
4. THE STABILITY OF CONSTRUCTION EXCAVATIONS AND ASSOCIATED WORKER SAFETY ARE THE RESPONSIBILITY OF THE
CONTRACTOR IN ACCORDANCE WITH CURRENT OSHA REGULATIONS; THIS RESPONSIBILITY MAY REQUIRE DESIGN BY A
REGISTERED PROFESSIONAL ENGINEER BASED ON THE PREDOMINANT SOIL TYPES ENCOUNTERED. ACTUAL SUBSURFACE
CONDITIONS AT THE TIME OF EXCAVATION SHOULD BE OBSERVED BY A GEOTECHNICAL ENGINEER TO DETERMINE
WHETHER SLOPE FLATTENING, BRACING OR OTHER STABILIZATION IS NECESSARY DUE TO SEEPAGE OR OTHER
UNEXPECTED CONDITIONS.
5. FINAL EXCAVATIONS SHALL BE COMPLETED WITH A SMOOTH-LIPPED BUCKETS IN FINE GRAINED SOILS SUCH AS SILTS &
CLAYS. ANY AREAS OF RUTTING, EXCESSIVE DEFORMATION, OR OTHER NON-UNIFORM PERFORMANCE OF THE NATIVE
SURFACE OR THE BACKFILL SHALL BE REMOVED AND REPLACED BY GRANULAR STRUCTURAL FILL
D. FOUNDATION & SLAB PREPARATION:
1. CONTINUOUS WALL AND SPREAD FOOTING FOUNDATIONS SHALL BE ESTABLISHED ON UNDISTURBED NATIVE. NOTIFY
EOR IF ANY RUTTING, EXCESSIVE DEFORMATION, OR OTHER NON-UNIFORM PERFORMANCE OF THE NATIVE SURFACE IS
OBSERVED
2. ALL INTERIOR FOOTINGS SHOULD HAVE A MINIMUM EMBEDMENT OF 1.0 FT BELOW FINISHED INTERIOR SURFACES.
EXTERIOR WALL FOOTINGS SHOULD BE EMBEDDED TO ESTABLISH FROST PROTECTION.
3. BACKFILL COMPACTION WITHIN 5 FEET OF FOUNDATION WALLS SHOULD BE CONDUCTED USING HAND OPERATED
TAMPING EQUIPMENT ONLY.
4. INTERIOR SLAB PREPARATION: THE SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH ITEM C1. AREAS OF
UNSUITABLE FILL MATERIAL OR WHERE RUTTING, YIELDING, OR OTHER NON-UNIFORM SUBGRADE PERFORMANCE IS
OBSERVED SHALL BE REMOVED & GRANULAR STRUCTURAL FILL OR APPROVED COMPACTED NATIVE SHALL BE INSTALLED
TO GRADE ELEVATION. FOLLOWING THE SUBGRADE PREPARATION ANY SITE GRADING PER D6 BELOW SHALL BE
COMPLETED. A NOMINAL 6-INCH THICK LAYER OF OPEN-GRADED ANGULAR CRUSHED ROCK TO BE INSTALLED FOR A
CAPILLARY BREAK WITH 2 INCHES OF 3/4 INCH MINUS CRUSHED ROCK ABOVE TO PROVIDE A COMPACT SURFACE FOR
CONSTRUCTION ACTIVITIES. THE SLAB-ON GRADE BASE COURSE SHOULD BE COMPACTED USING VIBRATORY
COMPACTION METHODS UNTIL WELL KEYED. A VAPOR BARRIER PER B7 SHALL BE INSTALLED UNDER THE SLAB
5. EXTERIOR SLAB PREPARATION
a. EXTERIOR SLABS AT ENTRYWAYS FIXED TO THE BUILDING SHALL BE PROTECTED AGAINST FROST HEAVES
b. A MINIMUM OF 18" OF GRANULAR STRUCTURAL FILL SHALL BE INSTALLED UNDER A 6" LAYER OF OPEN
GRADED ANGULAR ROCK UNDERNEATH SLABS. ALL ITEMS SHALL BE COMPACTED PER THE ABOVE
SPECIFICATIONS.
6. IF GRADE NEEDS TO BE RAISED UNDER THE SLAB BETWEEN THE NATIVE & THE BASE OF THE CAPILLARY BREAK LAYER
EITHER STRUCTURAL OR GRANULAR FILL PER B1 & B2 ABOVE SHALL BE INSTALLED.
E. QUALITY CONTROL SHALL BE COMPLETED PER THE REQUIREMENTS OF THE TESTING AND OBSERVATION NOTES.
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S0.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
STRUCTURAL
NOTES
JTJHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1" = 1'-0"1 STRUCTURAL DESIGN INFORMATION
1" = 1'-0"3 NAILING SCHEDULE
1" = 1'-0"2 CONCRETE NOTES
1/2" = 1'-0"4 PREFABRICATED TRUSS NOTES
1" = 1'-0"5 STRUCTURAL COMPOSITE LUMBER
7 DEFERRED SUBMITTALS
1/4" = 1'-0"6 SNOW LOADING INFORMATION & NOTES
1" = 1'-0"8 SOILS & GEOTECHNICAL NOTES
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
FOUNDATION LEGEND
FOOTING
THICKENED SLAB
SAWCUT
CONTROL JOINT
HOLD-DOWN FROM
ABOVE, SEE SHEAR PLAN
A
A
1 1
C
C
4 4
SLOPE PER CIVIL
1
2
TOF: (FF) -4'-0"
4
5
5
5
5
5
7
T.O. PIER: (FF) 0'-6"
TYP
8
8
8
8
8
3
4"
4"
8' - 8"
8' - 6"
10' - 0"
9' - 8"
5' - 8"
B
B
2 2
3 3
1' - 6"
1' - 0"
9' - 6"
9' - 0"
21' - 6"
40' - 0"
12' - 4"27' - 8"
40' - 0"
3
T.O. FTG: (-) 4'-0"
9
1' - 4"
11' - 3"
C1
C1
C1
C1
C1
1
S4.00
1' - 4"
TOW: (FF) 0'-0"
TOW: (FF) -0'-5"
4
S4.00
2
S4.00
3
S4.00
TYP
8
S4.00
7' - 0"
9
4' - 0"
6' - 6"
6
S4.00
1' - 4"
3"
5' - 0"
10
8
S4.00
TYP
10
10
10
C2 C2
8"
TYP
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S1.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
FOUNDATION
PLAN
JTJHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
FOUNDATION KEYNOTES
1 5" SLAB, #4 BAR @ 24" O.C. E.W.
2 POUR THRU @ OVERHEAD DOOR, TYP
3 POUR THRU @ MAN DOOR
4 8" CONCRETE WALL W/ 16"W X 8" THICK FTG, TYP
5 FLOOR DRAIN, SLOPE SLAB TO DRAIN, COORDINATE
LOCATION WITH MECH
7 4" SLAB, COORDINATE LOCATION WITH CIVIL
8 12" SONOTUBE W/ 24" BIGFOOT, 4'-0" DEPTH, TYP
9 10" THICK, THICKENED SLAB
10 BOLLARD. SEE CIVIL FOR LOCATION
COLUMN SCHEDULE
TAG SIZE MATERIAL COLUMN BASE COLUMN CAP
C1 6X6 TIMBER ABU66Z CC66, CAP @ END
COLUMNS ECC66
C2 6X6 TIMBER
3/8" = 1'-0"1 FOUNDATION
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
A
A
1 1
C
C
4 4
B
B
2 2
3 3
1
2
H.
1
-1.
X
.
1
B.
1
B.
1
B.
1
B.
1
3
3
S4.10
3
6
S4.10
1
S4.10
4
S4.10
H.
3
-1.
X
.
1
H.
3
-1.
X
.
1
H.
3
-1.
X
.
1
H.
1
-1.
X
.
1
2
H.2-1.X.1
H.
1
-1.
X
.
1
H.
1
-1.
X
.
1
H.1-1.X.1
10
S4.10
TYP
FLOOR FRAMING LEGEND
JOIST
BEAM
HANGER
SHEATHING
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S2.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
MEZZANINE
FLOOR
FRAMING PLAN
JTJHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
3/8" = 1'-0"1 MEZZANINE FLOOR FRAMING
FLOOR FRAMING KEYNOTES
1 11 7/8 " BCI 6000 LVL @ 16" O.C.
2 2X8 DF/L NO.2 @ 2'-0" O.C.
3 5/8" EXP. 1 PLY
HEADER SCHEDULE
TAG HDR SIZE SPEC TRIMMERS
H.1 (2) 2X8 DF/L NO. 2
H.2 (3) 2X8 DF/L NO. 2
H.3 (2) 2X10 DF/L NO. 2
BEAM SCHEDULE
TAG Model SIZE
B.1 DF NO. 1 6X8
NOTE: NOT ALL HEADERS IN THIS VIEW
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
ROOF FRAMING LEGEND
TRUSS
BEAM, GIRDER OR HEADER
HANGER
SHEATHING
INT. BRG WALL
A
A
1 1
C
C
4 4
B
B
2 2
3 3
1
2
1
3
3
4
H.
1
-1.
X
.
1
H.
1
-1.
X
.
1
H.2-1.X.1 H.2-1.X.1 H.2-1.X.1
H.2-1.X.1 H.2-1.X.1 H.2-1.X.1
H.
1
-1.
X
.
1
5
5
S4.10
5
S4.10
4
S4.10
4
S4.10
S4.10
12
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S2.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ROOF FRAMING
PLAN
JTJHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
ROOF FRAMING KEYNOTES
1 2X OUTLOOKERS @ 24" O.C.
2 PRE-MANUFACTURED ROOF TRUSS @ 24" O.C.
3 DROP CHORD GABLE END TRUSS
4 5/8" EXP.1 ROOF SHEATHING
5 ACCESS HATCH
3/8" = 1'-0"1 ROOF FRAMING PLAN
HEADER SCHEDULE
TAG HDR SIZE SPEC TRIMMERS
H.1 (2) 2X8 DF/L NO. 2
H.2 (3) 2X8 DF/L NO. 2
H.3 (2) 2X10 DF/L NO. 2
NOTE: NOT ALL HEADERS IN THIS VIEW
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
UP
SHEAR WALL
SHEAR PLAN LEGEND
X
DIAPHRAGM TAG,
SEE DET. 5/S4.20
TOP PLATE CONN.
TAG, SEE DET. 2/S4.20
HOLD DOWN LOCATION
OR VERTICAL STRAP
X
X
SX.XX
XHOLD DOWN TAG,
SEE DET. 1/S4.20
SHEAR WALL TAG,
SEE DET. 5/S4.20
2X BLOCKING
HORIZONTAL STRAP
DRAG TRUSS
XA
A
1 1
C
C
4 4
B
B
2 2
3 3
A
A
A
A
1
2
1
2
3
3
5
S4.20
B
4
S4.20
A
TYP
TYP
TYP
TYP
A
A
A
A
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S3.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
SHEAR PLAN
JTJHH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
3/8" = 1'-0"1 SHEAR PLAN
SHEAR PLAN KEYNOTES
1 3/4" T&G FLOOR SHEATHING
2 5/8" EXP.1 SHEATHING
3 A 35 CLIPS @ 10' O.C.
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
WD STUDS
8"
(4)#5 HORIZ. EQ. SPACING
5/8" X 12"A.B. @ 32" O.C. MAX
FLASHING PER ARCH
#5 BAR 2" FROM TOP, TYPICAL
5" SLAB
IJ SEE 4/S4.00
FTG BACKFILL PER GEOTECHNICAL
RECOMMENDATION
W
SEE 4/S4.00 FOR TYP. SLAB PREP
DAMPROOFING
#4 LATERALS @ 16" O.C.
4" PERF. PIPE IN 3/8" TO 3/4"
OPEN GRADED DRAINAGE
AGGREGATE FOOTING DRAIN.
WRAP IN MIRAFI 140N
REBAR CONTINUOUS IN FOOTING
W<16" - (2) #4
16"≤W<24" - (3) #4
24"≤W<36" - (4) #4
PERIMETER INSULATION
SEE ARCH. FOR LOCATION & SIZE.
#4 @16" O.C. VERTS ALT.
BEND DIRECTION INTO FOUNDATION
3" MIN
SEE PLAN
SEE PLAN
FND WALL & FOOTING
PER PLAN/ DETAILS
DOOR OPENING PER PLAN
WALL BEYOND SLOPE SLAB @ DOOR FOR DRAINAGE
SLOPE PER SITE
1
1
SEE SOILS & GEOTECHNICAL NOTES
FOR EXTERIOR FLATWORK PREP.
12"
8"
5/8" POLYISO, LOCATE UNDER
DOOR THRESHOLD PER ARCH
(2) #4 @ EDGE
ASPHALT,
SIDEWALK OR
GRADE PER SITE
SEE SOILS &
GEOTECHNICAL NOTES
FOR FILL REQUIREMENTS
-
18
"
6"
#4 DOWEL @ 32" O.C.
#3 @ 18" O.C. EW
2'
2'
SEALANT NPI OR EQUAL
SEE PIJ A. FOR DOWEL DETAIL
BACKER ROD EJ MATERIAL
EJ @
SIDEWALK
SLOPE AWAY FROM BUILDING
APRON @ BUILDING
POUR THRU
4', 1/2" SMOOTH DOWELS @ 18" OC @ COLD JT
LOCATIONS. GREASE END IN SECOND POUR
T/
4
PLASTIC OR PREFORMED
HARDBOARD STRIP; IF SAWCUT
ONLY, FILL WITH SEALER
FREE END OF SMOOTH DOWELS TO BE
COATED WITH NON-BONDING AGENT
CONSTRUCTION COLD JOINT,
FILL WITH SEALER
CONTROL JOINT CONSTRUCTION JOINT
REBAR PER PLAN
TYPICAL SLAB
10 MIL VB TYP.
SLAB SEE PLAN FOR
THICKNESS & REBAR
LOCATE REBAR IN
CENTER OF SLAB
SEE 'TYPICAL SLAB' FOR
SUBGRADE
3/8" EXPANSION JOINT MATERIAL
WR MEADOW FIBRE EXPANSION
JOINT OR APPROVED EQUAL
3/8" WIDE X1/2" DEEP GROOVE
W/SEALANT WR MEADOWS SAFE
SEAL 3405 OR APPROVED EQUAL
VB SEAL TO WALL
SLAB
SEE 'TYPICAL SLAB'
FOR SUBGRADE
SEE 'TYPICAL SLAB' FOR SUBGRADE
6" OPEN GRADED ROCK
COMPACTED STRUCTURAL
FILL TO UNDISTURBED NATIVE
SEE 'TYPICAL SLAB' FOR SUBGRADE
3/8" EXPANSION JOINT MATERIAL WR
MEADOW FIBRE EXPANSION JOINT OR
APPROVED EQUAL
3/8" WIDE X1/2" DEEP GROOVE
W/SEALANT WR MEADOWS SAFE SEAL
3405 OR APPROVED EQUAL
VB SEAL TO WALL
PERIMETER ISOLATION JOINT PIJ A. PERIMETER ISOLATION JOINT PIJ B.
2" LEVELING COURSE
JOINT SPACING LIMITED TO
MAXIMUM OF +/- 15 FEET
4', 1/2" SMOOTH DOWELS @ 18" OC
ALTERNATE USE DIAMOND PLATE DOWEL BY
PNA OR APPROVED EQUAL
FRAMING FLUSH W/ INSIDE OF CONCRETE FRAMING FLUSH W/ OUTSIDE OF CONCRETE
GREASE END
9/16" Ø HOLE
2" MIN
4"
(3), #3 VERTICAL
12" SONO-TUBE
#3 STIRRUPS @12"
6X6 TIMBER COLUMN
SIMPSON ABU66 POST BASE
SLAB
IJ
PER PLAN
4' - 0"
(3) #3 STIRRUPS @2"
1' - 0 1/4"
BF 24
t+
1
1
/
2
"
PR
O
J
E
C
T
I
O
N
TREATED PLATE
ANCHOR BOLT PER
SCHEDULE. POSITION
@ C/L OF PLATE.
t=
T
H
I
C
K
N
E
S
S
PLATE WASHERS
REQUIRED AT SHEAR
WALLS, SEE SIZE TABLE
SPLICE OR CORNER,
WHERE OCCURS
12" MAX
6" MIN -
12" MAX
6" MIN -
SPACING AS SCHEDULED
8" MIN.
2 3/4"
6"
COMPACTED STRUCTURAL FILL TO NATIVE
9/16"Ø HOLE 4" DEEP
3/8" EXPANSION
JOINT MATERIAL
PER 3/ S1.1
1/2" SMOOTH DOWEL 24" LONG,
MATCH BOTTOM BAR LAYOUT,
GREASE END IN WALL
THICKENED SLAB BOTTOM BARS
THICKENED SLAB @ FOUNDATION WALLS
PROVIDE #4 DROP BAR LATERALS
@ 32" O.C. & TIE OFF TO #4 SLAB
STEEL AS SHOWN.
#4 BAR HORIZONTAL, (1) BAR
FOR EACH 12" OF WIDTH
SLAB THICKNESS PER PLAN
RUN SLAB BARS THRU
#5 BAR
5/8" SIMPSON TITEN HD BOLTS
@ 32" O.C. 4" MIN. EMBED,
MAX 8" FROM END AT PLATES
2X4 OR 2X6 FRAMED
WALL PER PLAN
PER PLAN
PE
R
P
L
A
N
P.T. PLATE
1
1
SEE NOTES FOR SUBSLAB
RECOMMENDATIONS
COUNTERSUNK 1/2"X3" TITEN HD
L-3X3X1/4"-6" ANGLE
PER PLAN
PER PLAN
STAIR STRINGER
BAR
SIZE
HOOKED REINFORCEMENT TENSION
DEVELOPMENT LENGTH SCHEDULE
TENSION DEVELOPMENT LENGTH, (ldh), INCHES
f'c = 3 KSI
#3
#4
#5
#6
9"
#7
#8
#9
#10
#11
4db
2 1/2" MIN.
ldh
db
12
d
b
SEE NOTES BELOW FOR BAR YIELD STRENGTH FACTOR
f'c = 4 KSI
11"
14"
17"
20"
22"
25"
28"
31"
8"
10"
12"
15"
17"
19"
22"
24"
27"
BENDING RADIUS 3db FOR #3
THROUGH #8 AND 4db FOR
#9 THROUGH #11 MEASURED
TO THE INTERIOR OF THE BARFACE OF SUPPORT,
HORIZONTAL OR
VERTICAL JOINT OR
POTENTIAL CRACK LINE
db
BENDING DIAMETER 6db FOR
#3 THROUGH #8 AND 8db
FOR #9 THROUGH #11
MEASURED TO THE INTERIOR
OF THE BAR
ldh
NOTES:
1. TABULATED DEVELOPMENT LENGTHS ARE BASED ON REINFORCING YIELD
STRENGTH FY = 60 KSI AND NORMAL WEIGHT CONCRETE.
2. ALL TABULATED VALUES ARE MINIMUM LENGTHS. IN CASE OF CONFLICT WITH THE
PLANS, SECTIONS OR DETAILS, USE THE LONGER LENGTH.
3. ADJUST TABULATED LENGTHS BY THE FOLLOWING FACTOR WHERE APPLICABLE.
A. REINFORCING BAR YIELD STRENGTH OTHER THAN 60 KSI: ( fy/ 60,000)
STRAIGHT SPLICE LENGTH SCHEDULE
SEE NOTES BELOW FOR COVER AND SPACING
FACTORS
DEV.LENGTH LAP LENGTH
<6" AND ld/5
DEV.LENGTH REINFORCING DOWELS OR BARS
CONTINUOUS THROUGH JOINT
FACE OF SUPPORT, HORIZONTAL OR VERTICAL
JOINT OR POTENTIAL CRACK LINE
DEVELOPMENT
REFER TO "HOOKED REINFORCEMENT TENSION DEVELOPMENT LENGTH
SCHEDULE" WHEN THE STRAIGHT DEV. LENGTH IN TENSION CANNOT BE
ACCOMMODATED IN THE CONCRETE SECTION.
LAP SPLICE
LAP SPLICES IN ADJACENT BARS SHALL BE STAGGERED A
MINIMUM OF 24 INCHES.
NOTES:
1. ALWAYS USE TENSION DEVELOPMENT LENGTH AND TENSION LAP
SPLICE LENGTH VALUES, EXCEPT WHEN THE PLANS OR DETAILS NOTE
SPECIFICALLY COMPRESSION LENGTHS.
2. TABULATED DEVELOPMENT AND LAP SPLICE LENGTHS ARE BASED ON
REINFORCING YIELD STRENGTH FY = 60 KSI, NORMAL WEIGHT CONCRETE
AND CLASS B LAPS.
3. TOP BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 12
INCHES OF FRESH CONCRETE CAST IN THE MEMBER BELOW THE
DEVELOPMENT LENGTH OR SPLICE.
4. WHEN DIFFERENT BAR DIAMETERS ARE SPLICED, USE LARGER BAR LAP
SPLICE LENGTH.
5. ALL TABULATED VALUES AREA MINIMUM LENGTHS. IN CASE OF
CONFLICT WITH THE PLANS, SECTIONS OR DETAILS, USE THE LONGER
LENGTH.
6. TABULATED VALUES FOR DEVELOPMENT AND LAP LENGTHS IN
TENSION SHALL BE FACTORED BY 1.5 WHEN THE CLEAR COVER IS LESS
THAN db AND THE CLEAR SPACING IS LESS THAN db (AND THERE ARE
STIRRUPS OR TIES ALONG ld) OR IS LESS THAN 2db (AND THERE ARE NO
STIRRUPS OR TIES ALONG ld).
7. ALL STRAIGHT BAR DEVELOPMENTS AND SPLICES SHALL BE IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 318.
8. db = BAR DIAMETER
LAP SPLICE LENGTH, INCHES
FOOTINGS
TOP BOTTOM
#3
BAR SIZE
#4
#5
#6
FDN WALLS
VERTS HORIZ.
SLABS
SINGLE MAT DOUBLE MAT
28"
37"
46"
56"
21"
28"
36"
43"
28"
37"
46"
56"
21"
28"
36"
43"
MINIMUM 60 KSI STEEL
MINIMUM 3000 PSI CONCRETE
28"
37"
46"
56"
STD ACI HOOK
PER TYP. DTL
1. CORNER BARS MAY BE OMITTED IF
BOTH WALL STEEL BARS HAVE 90
˚HOOKS WITH MINIMUM LAPS AS
SCHEDULED.
2. MATCH SIZE, SPACING, NUMBER, AND
LOCATION OF HORIZONTAL WALL,
FOOTING, OR GRADE BEAM BARS.
3. USE AT ALL CONCRETE CORNERS
INCLUDING THICKENED SLAB ON GRADE,
WALLS, CURBS, BEAMS, GRADE BEAMS,
AND SLABS UNLESS INDICATED
OTHERWISE.
SINGLE REINFORCING MAT
1. ALL 90˚ HOOKS SHALL EXTEND TO
FAR SIDE REINFORCING OF WALL OR
FOOTING.
DOUBLE REINFORCING MAT
STD ACI HOOK
FOR TYP. DTL
VERTICAL BARS
REQ'D @ CORNER
AND LAP -3"
WALL JOINT VFY JOINT
LOCATIONS W/ STRUCTURAL
ENGINEER IN ADVANCE
WATERSTOP RQ'D
WHEN EXTERIOR GRADE
IS ABOVE F.F.
2x4 KEYWAY
LAP PER SCHED
LAP PER SCHED
LAP PER SCHED
LAP PER SCHED LAP PER SCHED
LAP PER SCHED
SCHED
LAP PER
LAP PER SCHED
LAP PER SCHED
LAP PER SCHED
VERTICAL BARS
REQ'D @ CORNER
AND LAP -3"
MIN CLEARANCES
SEE TABLE FOR
SCHED
LAP PER
1/2" PREMOLDED
EXP. JT. WHERE
CONC. OCCURS
SONO TUBE FDN EXTEND TO GRADE
WHEN NOT IN PAVEMENT
GRANULAR FILL
4"Ø CONC. FILLED STEEL
PIPE -PAINT PER ARCH
ROUNDED CONC.
TOP 1/2" CROWN
3' - 0"
COORDINATE W/ MANUFACTURER
4' - 0" TYP.
MIN
1' - 6"
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S4.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
FOUNDATION
DETAILS
JTJHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1" = 1'-0"1 TYP. 8" FOUNDATION WALL DTL
1" = 1'-0"2 TYP. POUR THRU & APRON
1" = 1'-0"4 SLAB AND CONTROL JOINTS
1" = 1'-0"3 SONOTUBE FOUNDATION
1" = 1'-0"5 ANCHOR LOC'NS
1" = 1'-0"6 TYP. THICKENED SLAB
1" = 1'-0"8 STAIR STRINGER CONN. TO FLOOR
1" = 1'-0"9 STANDARD REINFORCEMENT SCHEDULES
3/4" = 1'-0"7 TYP. CORNER REINFORCING DET.
3/4" = 1'-0"10 TYP. PIPE BOLLARD
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
A35 (2) ON CENTER
STRINGER (1) ON
EDGE STRINGERS
FLOOR SHTG PER PLAN
JOISTS PER PLAN
PREFORMED WOOD STAIR TREAD
W/ ROUNDED NOSING TREAD
2X4 WALL
JOIST PER PLAN
STAGGER EN, TYP.
(1) 8d INTO T&B CHORDS
RIM BOARD PER PLAN
STAGGER EN, TYP.
8d @ 6" O.C. TOE NAIL
(2) 10d 3 1/2" SCREWS &
BLOCKING B/W JOISTS
10d BOX NAIL
EACH SIDE
FLOOR SHTG PER PLANA
H1
COLUMN CAP PER SCHED.
BEAM PER SCHED.
COLUMN PER SCHED.
HU28 HANGER
2X10 LEDGER W/ (2) SDWS22500
SCREWS IN EA STUD
SHEATHING PER SHEAR PLAN
FASCIA PER ARCH
SHEATHING PER PLAN
FINISH PER ARCH
R.O.
HEADER, SEE PLANS AND HEADER SCHEDULE
DBL TOP PL.
DENOTES HEADER
SCHEDULE #
# OF LEFT CRIPPLES (H=HANGER)
H.1-1.X.2
# OF INTERMEDIATE BRG (X=NONE)
# OF RIGHT CRIPPLES (H=HANGER - SEE REMARKS)
NOTE: KING STUD NOTATIONS ONLY FOR
NON SHEAR WALL LOCATIONS. REFER TO
SHEAR PLAN AND H.D. DTLS FOR KING
STUD RQ'MTS @ SHEAR
WALL ENDS.
BACK NAIL W/ 16d IN
SUCCESSIVE LAYERS AS SHOWN
> 3'-6" SINGLE KING STUD
3'-6" < 6'-0" DBL KING STUD
6'-0" > 10'-0" TRIPLE KING STUD
10'-0" < SEE PLAN
INTERIOR WALLS
CAN DOUBLE SPANS NOTED
FOR KING STUD RQ'MTS.
ELEVATION AS VIEWED FROM EXTERIOR
OR LABEL SIDE ON INTERIOR HEADER
2X
SECTION
DOUBLE TOP PLATE
HEADER
2X FLAT
INSULATION
OR CRIPPLE TO
DOUBLE TOP PLATE
---
PER PLAN
NOTE: SEE PLANS FOR HEADER
LOCATIONS
WALL BUILDUP PER ARCH
FOUNDATION SEE S1.00
EDGE NAIL, STAGGERED
WALL SHEATHING PER SHEAR WALLS, IF NO SHEAR
WALL NAILING PROVIDED FOR WALL, USE 6" O.C. EN,
12" O.C. FN
HEADER SEE FRAMING PLAN
2X8 / 2X6 / 2X4 PER PLAN
WINDOW FRAMING
SHOW DOOR SIM
EN @ 6" OC
EN @ 6" OC
2X STUDS TO DBL TOP PLATE, BASED ON PLATE HEIGHT/
HEADER NO CRIPPLES MAY BE RQUIRED
DBL TOP PLATE
STAGGERED EN
HURRICANE TIES ON
ALL TRUSSES H1 UNO
DIAPHRAGM NAILING INTO
BLOCKING
FULL HEIGHT SOLID BLOCKING
VENT PER ARCH
2X8 SUB FASCIA
(3) 12 D NAILS
FASCIA PER ARCH
EXTEND SHTG TO BASE
OF RAKED OR FLAT
SOFFIT
BLOCKING TO BE MIN 1 1/4"
LSL OR STACKED 2X
SEE ARCH FOR SOFFIT
TOP OF
FOUNDATION
2X6 WALL
I JOIST PER PLAN
STAGGER EN, TYP.
(1) 8d INTO T&B CHORDS
RIM BOARD PER PLAN
STAGGER EN, TYP.
8d @ 6" O.C. TOE NAIL
GRK RSS 5/16 X 4"
@ EACH JOIST
10d BOX NAIL
EACH SIDE
3/4" PLYWOOD
7/16" APA RATED OSB SHTG,
GRADE & NAIL PER SCHEDULE.
MAINTAIN MIN. 1/8" GAP AT SHTG
PER APA GUIDELINES FOR SWELL
WALL FRAMING
SIMPSON HANGER
PER PLAN
SOLID BLOCKING
OUTLOOKER @ 24" O.C.
PER PLAN
DROP CHORD GABLE
END TRUSS PER PLAN
SIMPSON H 1 @
EACH OUTLOOKER
SUB-FASCIA
CONTINUOUS EDGE NAILING
ON SHEATHING TO BLOCKING
MANUFACTURED
TRUSS PER PLAN
ROOFING
APA RATED EXPOSURE 1
SHEATHING
2X WIND BRACING @ 8'-0" O.C. TYP.
SIMPSON GBC CLIPS EACH
SIDE OF BRACE
4
0
°
-
6
0
°
ADJUST BETWEEN LIMITS FOR ANGLE BRACING TO
TERMINATE @ TRUSS TOP CHORDS
2X BLOCKING AT BRACE,
NAIL SHTG TO BLK'G
5 1/2" MIN
2"MIN.
A
WHERE DIM. "A" IS LESS THAN 1 1/2", A
GALVANIZED PROTECTION PLATE
EXTENDING 2" BELOW THE TOP PLATE,
FASTENED WITH 8-16d NAILS, IS REQUIRED.
"A"
DIM "A"
FROM EDGE OF PIPE TO
FACE OF FRAMING
WHERE DIM. "A" IS 1 1/2" OR MORE, A
GALVANIZED PROTECTION PLATE, FASTENED
WITH 8-16d NAILS, IS REQUIRED.
WHEREVER DIM. "A" IS LESS THAN 1 1/2", A
GALVANIZED PROTECTION PLATE EXTENDING
2" ABOVE THE BOTTOM PLATE, FASTENED
WITH 8-16d NAILS, IS REQUIRED.
WHEREVER DIM. "A" IS 1 1/2" OR MORE, A
GALVANIZED PROTECTION PLATE, FASTENED
WITH 8-16d NAILS, IS REQUIRED.
WHEREVER DIM. "A" IS 1/2" OR LESS, A
STUD SHOE OR SHALL BE INSTALLED TO
REPAIR THE STUD AND PROTECT THE PIPE.
AWHEREVER DIM. "A" IS 1 1/2" OR LESS, A
GALVANIZED PLATE EXTENDING AT LEAST 1 1/2"
ABOVE AND BELOW THE PIPE IS REQUIRED
MAXIMUM HOLE DIA OR NOTCH DEPTH
WITHOUT REPAIR OR PROTECTION:
FRMG BRG/NBRG HOLE DIA.NOTCH DPTH
2X4 INT-NBRG 2 1/8" 1 3/8"
EXT/BRG 1 3/8" 7/8"
3 1/4" 2 3/16"2X6 2 3/16" 1 3/8"
INT-NBRG
EXT/BRG
WHEREVER DIM. "A" IS 1 1/4" OR LESS, A
GALVANIZED PLATE EXTENDING AT LEAST 1 1/4"
ABOVE AND BELOW THE WIRE IS REQUIRED A
FOR (1) AND (2) FAMILY DWELLINGS ONLY, NO
REPAIR OR PROTECTION IS REQUIRED FOR
MAXIMUM HOLE DIAMETERS/NOTCH DEPTHS:
2X4 - 1 3/4"
2X6 - 2 3/4"
DIM "A" FOR PIPES MUST BE AT LEAST 1 1/2"
A
WHEREVER THE BOTTOM PLATE IS CUT FOR
DUCTWORK, A GALVANIZED 16 GA REPAIR
STRAP IS REQUIRED. FASTEN WITH (6) 16d
NAILS ON EACH SIDE OF CUT
WHEREVER THE TOP PLATE IS CUT FOR
DUCTWORK, A GALVANIZED 16 GA
REPAIR STRAP IS REQUIRED FOR EACH
PLATE. FASTEN WITH (6) 16d NAILS ON
EACH SIDE OF CUT
WHEREVER THE TOP PLATES ARE CUT FOR
DUCTWORK IN TWO ADJACENT STUD BAYS,
A 3" WIDE, 16 GA GALVANIZED REPAIR
STRAP IS REQUIRED. FASTEN WITH (6) 16d
NAILS ON EITHER END OF THE CUTS
WHEREVER THE BOTTOM PLATE IS CUT
FOR DUCTWORK IN TWO ADJACENT STUD
BAYS, A 3" WIDE, 16 GA GALVANIZED
REPAIR STRAP IS REQUIRED. FASTEN WITH
(6) 16d NAILS ON EITHER END OF THE CUTS
FOR (1) AND (2) FAMILY DWELLINGS ONLY,
MAXIMUM NOTCH DEPTHS IN TOP & BOTTOM PLATES ARE:
FRMNG BRG/NBRG NOTCH DPTH
2X4 INT-NBRG NO LIMIT
EXT/BRG 1 3/4"
NO LIMIT2X6
2 3/4"
INT-NBRG
EXT/BRG
1X WD TRIM ALL SIDES
GWB PER ARCH
5/8" GWB
1/2" PLYWOOD
1/4" PLYWOOD SIDES - 2" TALLER
THAN INSULATION STIFFEN AS
REQUIRED
BATT INSULATION
ATTACHED TO LID
CEILING
INSULATION
4X4 TIMBER
4X
4
T
I
M
B
E
R
4X4 TIMBER
3/8" LAG SCREW W/
WASHER CSK, TYPICAL
LAG SCREW INTO
2X BLOCKING, TYP
LAG INTO COLUMN IN WALL.
SEE PLAN FOR SIZING
1
1
2' - 0"
2' - 6"
30
"
M
I
N
MATCH BOTTOM CHORD HEIGHT
TRUSSES @ 24" O.C.
11
S4.10
HINGE @ 24" O.C., MIN 2
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S4.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
FRAMING
DETAILS
JTJHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1" = 1'-0"1 STAIR DETAIL
1" = 1'-0"6 RIM DETAIL (BEARING)
1" = 1'-0"3 FRAMING AT FRONT PORCH
3/4" = 1'-0"2 HEADER/BEAM DETAIL
1" = 1'-0"4 DETAILED WOOD FRAMED WALL
1" = 1'-0"7 RIM DETAIL (NON-BEARING)
1" = 1'-0"5 TYP. OUTLOOKER DETAIL
1/2" = 1'-0"8 PLBG/ELCTRCL REPAIRS & PRTCTN
1/2" = 1'-0"9 HVAC REPAIRS
1" = 1'-0"11 ATTIC ACCESS DETAIL
1" = 1'-0"10 KNEE BRACE DET - GABLE END
1" = 1'-0"12 ATTIC ACCESS PLAN
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
1. INSTALL HOLD-DOWN AFTER TIME HAS
PASSED TO ALLOW SHRINKAGE TO OCCUR.
2. HOLES IN FRAMING MEMBERS SHALL BE NO
GREATER THAN BOLT SIZE +1/16".
3. STEEL NYLON LOCKING NUTS OR THREAD
ADHESIVE SHALL BE USED ON ANCHOR BOLTS.
4. A FINAL CHECK ON ALL BOLTED HOLD-DOWN
CONNECTIONS SHALL OCCUR BEFORE CLOSING
IN THE WALL TO ASSURE TIGHT ANCHORS.
NUTS MAY LOOSEN WITH SHRINKAGE.
5. USE OVERSIZED WASHERS ON ALL HOLD-
DOWNS THAT ARE BOLTED TO THE FRAMING.
6. USE CARE TO DRILL STRAIGHT HOLES THRU
FRAMING MEMBERS WITH ONE PASS.
7. INSTALL ALL HOLD-DOWNS TO MFR
RECOMMENDATIONS, FILL ALL HOLES ON
NAILED/SCREWED HOLD-DOWNS.
8. ANCHOR BOLTS TO BE REPLACED BY ALL
THREADS FOR ABOVE GRADE DETAILS.
9. HTT 4 MAY BE REPLACED BY HTT5
CL
STAGGER EN TO PLATE
T.O. FND.
HD POST CONT.
TO TOP PLATE
HD SEE PLAN FOR LOC'N
TAG
NUMBER
DETAIL NUMBER
SHEET NUMBER
HOLD-DOWN
LOCATION
SUPPORT STUDS
PER DETAIL
DIA.
STAGGER EN TO POST
INSTALL ANCHOR PER
SIMPSON INSTRUCTIONS
HEX NUT
OFFSET
0'
-
2
"
EM
B
E
D
PR
O
J
.
# OF ROWS
NAIL/ SCREW QUANTITY
SPLICE LENGTH
NAIL/ SCREW QUANTITY
SPACING
DENOTATION KEY APA CERTIFICATION KEY
INDICATES SIDE
OF WALL TO BE
SHEETED
DENOTES
SCHEDULE
SPECIFICATION
APA CERTIFICATION
STAMP
DENOTES ROOF/
FLOOR SPAN RATING
DENOTES SHEATHING
THICKNESS
DENOTES SHEATHING
EXPOSURE RATING
DENOTES SHEATHING
STRUCTURAL RATING
DENOTES RATED
SHEATHING
X
APA
32/16
EXPOSURE 1
STRUCTURAL 1 RATED
WOOD ASSOCIATION
RATED SHEATHING
THE ENGINEERED
SIZED FOR SPACING
15/32 INCH
000
PRP-108 HUD-UM-40CPANELIZED ROOFS
HD POST PER
SCHEDULE
SHTG PER
SCHEDULEINSIDE FACE
OF FDN
GR
HD PER TAG
GR
SGL/DBL
TRIMMER
STAGGER EN
INTO POSTSHTG PER
SCHEDULE
GR
RO
HD PER TAG
INSIDE FACE OF FDN
HOLDOWN DTL.4HOLDOWN DTL.3
STAGGER EN
16
15
14 MAX UNREINFORCED HOLE SIZE 4 1/2"X 4 1/2",
NO OVERCUTTING PERMITTED
2X BLOCKING FOR HOLES LARGER THAN 4 1/2"X 4 1/2". MAX
ACCUMULATED LENGTH OF HOLE <20% OF SHEAR WALL LENGTH.
NO HOLES OR CUTTING OF SHEATHING WITHIN 16" OF CORNERS.
STAGGER END NAIL INTO ALL KING STUD/
HOLDDOWN POST ASSEMBLES ALONG
SHEAR WALLS @ WINDOWS AND DOORS.
EXTEND NAILING FROM SILL PLATE TO
DOUBLE TOP PLATE. NAIL TRIMMER W/ FIELD
NAIL
STAGGER EDGE NAIL (EN) SHTG TO HOLD-DOWN POSTS @
EACH BOUNDARY OF SHEAR WALL PER SCHEDULE
APA RATED SHEATHING PER THE SHEAR WALL SCHEDULE
BLOCKING REQUIRED (SIZE PER SCHEDULE) AT ALL
HORIZONTAL SEAMS
SPECIAL FRAMING MEMBER(S) AT PANEL EDGES PER SCHEDULE
1/8" GAP AT ALL PANEL EDGES - TYPICAL
SHEAR WALL NAILS PLACED NOT LESS THAN 3/8" FROM PANEL
EDGE AND FIRMLY DRIVEN FLUSH INTO FRAMING MEMBER
WITHOUT CRUSHING THE SURFACE OF THE SHEATHING
EDGE NAIL PER SCHEDULE
DBL TOP CHORDS, MIN. 6' LAP - SPLICE PER SCHEDULE
FIELD NAILING PER SCHEDULE
HOLD-DOWN AND ANCHORS PER SCHEDULE
ANCHOR BOLT SIZE & SPACING PER SCHEDULE; PLATE WASHERS REQUIRED
FRAMING PER SCHEDULE, DOUGLAS FIR/ LARCH NO. 2+
CRIPPLES PER H.D. DTLS AND HEADER SCHEDULE
ELEVATION VIEW
1
2
3
4
5
6
7
8
9
10
11
12
13
1
2
13
3
4
9
711
10
7812
14 15
7
3 6
4
5
BOUNDARY NAIL TO WALL BLOCKING PER SCHEDULE
EXTERIOR WALL OR INTERIOR SHEAR WALL
TYPICAL FRAMING MEMBERS ON LAYOUT
BOUNDARY NAIL SHTG TO ALL COLLECTORS
PER PLAN
EDGE NAIL EACH SHEET TO COMMON FRAMING
MEMBER
STAGGER SHEETS ACROSS FRAMING
BLOCK LONGITUDINAL SEAMS WHEN SCHEDULED
FIELD NAILING PER SCHEDULE
GAP SHEETS 1/8" FOR SWELLING
NAILS TO BE DRIVEN FLUSH W/ NO CRUSHING OF
SHEETING AND A MIN OF 3/8" FROM EDGE.
STRUT, TIE, OR COLLECTOR ELEMENT PER PLAN
PLAN VIEW
1
2
3
4
5
6
7
8
9
10
11
2
5
3
487
6
5
1
10
8
9
11
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
S4.20
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
SHEAR DETAILS
JTJHMH
PR
O
J
E
C
T
#
:
2
0
0
2
0
4
1" = 1'-0"1 HOLD DOWN TAG TABLE
1/2" = 1'-0"2 TOP PLATE CONNECTION SCHEDULE
1/8" = 1'-0"5 SHEAR WALL SCHEDULE/ DIAPHRAGM SCHEDULE
1/2" = 1'-0"6 SHEAR WALL DETAIL
1/2" = 1'-0"7 HORIZONTAL DIAPHRAGM
SHEAR WALL SCHEDULE
TAG APA RATED SHTG. SHTG. TYPE SIDES SHTD. SILL BLK'G PANEL EDGE NAILS EDGE NAIL FIELD NAIL STUD SPACING A.B. SIZE A.B. SPACING
SILL TO WOOD
NAILING
A 7/16" EXP.1 1 2X 2X 8d 6" 1'-0" 1'-4" 5/8" X 10" 4'-0"O.C. 6" O.C.
1. ALL NAILS ARE COMMON WIRE UNLESS NOTHED OTHERWISE
2. REFER TO TYPICAL SHEAR WALL FRAMING DETAIL FOR FURTHER REQUIREMENTS
HORIZONTAL DIAPHRAGM NAILING SCHEDULE
TAG BLOCKING APA RATED SHTG SPAN RATING NAILS EDGE NAIL BOUNDARY NAIL FIELD NAIL NOTES
1 NONE 5/8" EXP.1 40/24 8d 6" 6" 12"
2 NONE 3/4" EXP.1 40/20 10d 6" 6" 12"
NOTE: BOLD LINES ON SHEAR PLAN DENOTE REGION
TOP PLATE CONNECTION SCHEDULE
TAG
MIN
SPLICE # ROWS SPACING PLATE GRADE NAIL/SCREW
MIN # OF NAILS/ SCREWS
PER SPLICE COMMENTS
A 4' 2 12" DF/L NO.2+ OR
HEM FIR SS
16d 12
HOLD DOWN SCHEDULE
TAG HOLD DOWN HD POST OFFSET PROJ. DIA.
SIMPSON
CONCRETE
ANCHOR
A HDU4-DFD2.5 (3)2X6 1 3/8" 6" 7/8" SB5/8"X24"
B HDU4-DFD2.5 (2) 2x6 1 3/8" 6" 7/8" SB5/8"X24"
M O NTAN
A
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
ERIC D. GARBERG
No. 14108 PE
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
CHWS
CDR
CWR
CWS
HWR
HWS
STM
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
STEAM
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
CAP
REF-HG REFRIGERANT-HOT GAS
PLUMBING AND PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL DRAWING SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPE RISE
PIPE DROP
PIPE TEE
1
-
---
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
Room
1
16"x8"
16"/8"
(E)
F
S
M
B
D
C
16"Ø
E/A
O/A
T/A
L/A
R/A
S/A
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
THROW-150FPM/ 100FPM/ 50FPM
NECK SIZE / MODULE SIZE
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE)NUMBER OF SLOTS /
ACTIVE SLOT LENGTH (PLENUM LENGTH) /
NECK SIZE
DUCT BEING DEMOLISHED
ELEVATION (CENTER OF FACE)
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
GE/A GREASE EXHAUST AIR
SE/A SMOKE EXHAUST AIR
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL INFORMATION)
EXISTING EQUIPMENT
TO REMAIN
FLUE EXHAUST GAS FLUE
C/A COMBUSTION AIR
S-O/A CONDITIONED OUTSIDE AIR
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
AC AIR CONDITIONING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
BP BOILER PUMP
CC COOLING COIL
CH CHILLER
CT COOLING TOWER
CU CONDENSING UNIT
CWP CONDENSER WATER PUMP
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DCP DOMESTIC WATER CIRCULATING PUMP
DF DUCT FURNACE
DH DUCT HEATER
EF EXHAUST FAN
EH ELECTRIC HEATER
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
F FURNACE
FC FAN COIL
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HP HEAT PUMP
HS HYDRAULIC SEPARATOR
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HRV HEAT RECOVERY VENTILATOR
MAU MAKE-UP AIR UNIT
P PUMP
RF RETURN FAN
RTU ROOF TOP UNIT
SD SLIM DUCT
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SP SUMP PUMP
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
WH WATER HEATER
WM WALL MOUNT
EQUIPMENT ABBREVIATIONS
400
48"x2 1/2"
LS-1
300
8" / 24x24
S-2
400
12" / ---
S-3
LINEAR BAR GRILLE
LINEAR SLOT DIFFUSER
PERFORATED DIFFUSER
WITH DEFLECTORS
ROUND DIFFUSER WITH
ADJUSTABLE PATTERNS
LOUVERED DOUBLE
DEFLECTION GRILLE
500
12"x10" / ---
S-4
TYPE (SEE SCHEDULE)
H-5/7/1422
400
10" / 24x24
S-1
3-CONE DIFFUSER
THROW PATTERN
MAX NC RATING
200
1 / 4' - 0" / 8"
LS-2
8' - 0" AFF
200
1 / 4' - 0" / 8"
LS-2
18' - 0"200
1 / 4' - 0" / 8"
LS-2
SECTION TOTAL TRACK LENGTH
500
12"x10" / 24x12
R-2
LOUVERED GRILLE
18
500
12"x10" / 24x24
R-1
EGGCRATE RETURN
GRILLE
BOTTOM OF EQUIPMENT
ELEVATION
590 lb
RTU-XX
4.0 ton
RTU-XX
115000 Btu/h
115 CFH
RTU-XX
HEATING COIL FLOW OPERATING WEIGHT
NOT INCLUDING CURB
FUEL INPUT
GAS PIPE FLOW
NOMINAL COOLING
CAPACITY
ROOFTOP UNIT
PIPE ACCESSORY TAGS
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
DATA DEVICE TAGS
DAMPER TAGS
VAV-XX
RTU-XX
EQUIPMENT ID
SYMBOL
BBB INLET COLLAR DAMPER
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
PIPE SYMBOLS
VAV-XX
10' - 0"
(E)VAV-XX
VAV-XX
Htg: 3.7 GPM
VAV-XX
GWR GEOTHERMAL WATER RETURN
GWS GEOTHERMAL WATER SUPPLY
STM-HP STEAM -HIGH PRESSURE
1-M1.02D
DENOTES BUILDING NUMBER
(OMIT ON SINGLE BUILDING PROJECTS)
DENOTES SPECIFIC DISCIPLINE
DENOTES SHEET TYPE
DENOTES DEMO PLANS
(OMIT ON NON DEMO SHEETS)
DENOTES SHEET COUNT
DENOTES BUILDING LEVEL
(0 IS BASEMENT/CRAWLSPACE LEVEL 1 IS 1 ETC.)
BUILDING MECHANICAL SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES:
• 2018 INTERNATIONAL MECHANICAL CODE
• 2018 UNIFORM PLUMBING CODE
• 2012 IECC INTERNATIONAL ENERGY CONSERVATION CODE
• ANSI/ASHRAE/IESNA STANDARD 90.1-2019 ENERGY STANDARD FOR BUILDINGS EXCEPT FOR
LOW-RISE RESIDENTIAL BUILDINGS
• ANSI/ASHRAE STANDARD 62.1-2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
• ASHRAE STANDARD 62.2-2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY IN LOW-
RISE RESIDENTIAL BUILDINGS
CODE COMPLIANCE
KALISPELL, MONTANA
ANNUAL DESIGN CONDITIONS: ASHRAE FUNDAMENTALS 2017
WEATHER STATION - KALISPELL, MT WMO# 727790
ELEVATION: 2957' LAT: 48.304N LONG: 114.264W
WINTER: -6.0 (99.6%)
SUMMER: 90.0 DRY BULB (0.4%)
62.6 WET BULB (0.4%)
INDOOR DESIGN CONDITIONS:
WINTER: 70 ± 2º F
SUMMER: 75 ± 2º F
HVAC DESIGN CRITERIA
1. INSTALLATION OF THE MECHANICAL SYSTEM SHALL BE BY A
LICENSED CONTRACTOR PER THE STATE BUILDING, MECHANICAL
ENERGY, FIRE, PLUMBING AND HEALTH CODES, AND
REGULATIONS AS ADOPTED BY LOCAL JURISDICTIONS.
2. ALL EQUIPMENT SHALL BE THE CAPACITY AND TYPE AS SHOWN
ON THE EQUIPMENT SCHEDULE AND SHALL BE THE LISTED
MANUFACTURER AND MODEL NUMBER OR SHALL BE AN EQUAL
APPROVED BY THE OWNER/ENGINEER.
3. CONTRACTOR IS TO BRING UP THE DISCREPANCIES AND ITEMS
WHICH ARE NOT SPECIFICALLY CALLED FOR OR SHOWN BUT ARE
REQUIRED FOR A COMPLETE MECHANICAL SYSTEM. ALL SUCH
ITEMS REQUIRED FOR A COMPLETE SYSTEM READY FOR THE
OWNER'S BENEFICIAL USE SHALL BE FURNISHED AND INSTALLED
INCLUDING ALL SUCH DISCREPANCY ITEMS MENTIONED ABOVE,
AT NO ADDITIONAL COST TO THE OWNER AND PER LOCAL CODES,
MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE
STANDARDS WITH THE ARCHITECT/ENGINEER'S APPROVAL.
4. ALL EQUIPMENT SUPPLIED FOR THESE SPECIFICATIONS SHALL BE
FREE FROM DEFECTS IN MATERIAL, WORKMANSHIP, AND TITLE,
AND SHALL BE OF THE KIND AND QUALITY DESCRIBED HEREIN. IF
IT APPEARS WITHIN ONE YEAR FROM DATE OF FINAL ACCEPTANCE
THAT EQUIPMENT DOES NOT MEET THE WARRANTIES ABOVE, THE
CONTRACTOR SHALL IMMEDIATELY CORRECT ANY DEFECT AND
SHALL RESTORE THE SYSTEM TO THE ORIGINAL SATISFACTORY
CONDITIONS AT HIS EXPENSE. THE FOREGOING WARRANTY IS
EXCLUSIVE AND IN LIEU OF OTHER WARRANTIES, WHETHER
WRITTEN, ORAL, IMPLIED, OR STATUTORY. NO WARRANTY OR
MERCHANT ABILITY OF FITNESS FOR PURPOSE SHALL APPLY (THE
WARRANTY SHALL START FROM THE TIME OF
ARCHITECT/ENGINEER'S FINAL ACCEPTANCE).
5. COORDINATE THE CONSTRUCTION SCHEDULE WITH THE GC AND
PERFORM ALL REQUIRED WORK IN STRICT ACCORDANCE WITH
THE OWNER'S SCHEDULE.
6. MECHANICAL CONTRACTOR SHALL PAY FOR AND OBTAIN ALL
REQUIRED PERMITS AND CERTIFICATES REQUIRED BY THE
AUTHORITIES HAVING JURISDICTION.
7. HVAC NOTES:
A. PROVIDE FLEXIBLE CONNECTION IN ALL DUCTS CONNECTING
TO AIR MOVING EQUIPMENT AS CLOSE TO FAN AS POSSIBLE.
FLEXIBLE CONNECTION SHALL CONSIST OF 6" OR MORE OF
AIR TIGHT, FIRE PROOF FLEXIBLE NEOPRENE COATED WOVEN
FIBROUS GLASS MATERIAL. VENT FABRICS, INC. OR
APPROVED EQUAL.
B. ALL MAIN TRUNK AND BRANCH TAKEOFF DUCTWORK SHALL
BE SHEET METAL. FLEXIBLE DUCT IS ALLOWED ON LAST 6'
SERVING GRDs. FIBERGLASS DUCTWORK SHALL NOT BE
USED.
C. ALL SUPPLY & RETURN FLEXIBLE DUCTS CONNECTING TO
GRILLES, REGISTERS AND DIFFUSERS SHALL BE CONSTRUCTED
OF DOUBLE LAMINATION OF POLYESTER ENCAPSULATED
STEEL WIRE HELIX FOR INNER CORE HIGH DENSITY
FIBERGLASS INSULATION AND GRAY POLYESTER FILM WITH
SPIRAL REINFORCEMENTS, EQUAL TO ATCO-70 SERIES (MIN.
POS. PRESS. = 6' W.C. NEG. PRESS. = 0.75" W.C. & R=5.79).
D. SEAL ALL DUCTWORK JOINTS PER SMACNA CLASS C FOR
SYSTEMS UP TO 2 IN W.G. AND SEAL ALL JOINTS AND SEAMS
PER SMACNA CLASS B FOR SYSTEMS GREATER THAN 2 IN
W.G.
E. ALL EQUIPMENT, DUCTWORK AND PIPING SHALL BE
STRUCTURALLY SUPPORTED AND SECURELY FASTENED TO
BUILDING STRUCTURE IN AN ACCEPTABLE MANNER TO
OWNER, ARCHITECT, ENGINEER AND LOCAL JURISDICTION
AND SHALL BE SEISMICALLY BRACED PER THE SMACNA
AND/OR REQUIRED BY LOCAL JURISDICTIONS.
F. PROVIDE LOCKABLE VOLUME DAMPERS IN ALL TAKEOFFS.
G. DUCT HANGERS, SUPPORTS AND METHODS OF INSTALLATION
SHALL CONFORM TO ASHRAE & SMACNA
RECOMMENDATIONS.
H. DUCT SIZES SHOWN ON PLANS INDICATE INSIDE FREE AREA.
I. ALL DUCTWORK SHALL BE CLASS-1 AIR DUCT AS APPROVED
BY U.L.-181.
J. ALL SQUARE ELBOWS SHALL HAVE TURNING VANES.
K. DUCT INSULATION SHALL BE PROVIDED AS FOLLOWS:
a. ALL SUPPPLY DUCT IN UNCONDITIONED SPACES TO BE
INSULATED WITH MIN. R-8 INSULATION (2" THICKNESS,
0.24 K VALUE).
b. ALL RETURN DUCT IN UNCONDITIONED SPACES TO BE
INSULATED WITH MIN. R-8 INSULATION (2" THICKNESS,
0.24 K VALUE).
c. ALL CONCEALED SUPPLY DUCT TO BE INSULATED WITH
MIN. R-6 INSULATION (1 1/2" THICKNESS, 0.24 K VALUE).
d. ALL OUTDOOR AIR TO BE INSULATED WITH MIN. R-6
INSULATION (1 1/2" THICKNESS, 0.24 K VALUE).
e. THE 6' OF EXHAUST DUCT NEAREST TO THE EXTERIOR TO
BE INSULATED WITH MIN. R-6 INSULATION (1 1/2"
THICKNESS, 0.24 K VALUE).
8. ALL FIRE RATED STRUCTURE SHALL BE FIRE DAMPERED AS
REQUIRED BY THE JURISDICTION.
9. FLEXIBLE DUCTS SHALL HAVE MAXIMUM 6 FEET LENGTH UNLESS
SHOWN OTHERWISE AND SHALL NOT PENETRATE THROUGH ANY
FIRE RATED WALLS. DO NOT INSTALL FLEXIBLE DUCTS WITHIN 6
FEET OF HEATING ELEMENT.
10. HVAC SYSTEM SHALL BE STARTED UP AND FUNCTIONALLY TESTED
BY MECHANICAL CONTRACTOR. MECHANICAL CONTRACTOR
SHALL CONFIRM THAT ALL HVAC SYSTEMS ARE READY FOR
TESTING, ADJUSTING, AND BALANCING. HVAC SYSTEMS SHALL BE
TESTED, ADJUSTED, AND BALANCED (TAB) BY CONTRACTOR
CERTIFIED BY THE AABC, NEBB, OR OTHER APPROVED AGENCY.
REFRIGERATION PIPING SHALL BE TESTED UNDER PRESSURE AND
PROVEN TO BE LEAK FREE. REFRIGERATION SYSTEM SHALL BE
STARTED UP AND BROUGHT DOWN TO DESIGN TEMPERATURE.
11. MECHANICAL, HVAC, AND PLUMBING ELEMENTS SHALL AT NO
TIME COME IN CONTACT WITH CEILING CONSTRUCTION EXCEPT
AS NECESSARY PENETRATIONS MAY REQUIRE. ESCUTCHEONS
SHALL BE USED ON ALL VISIBLE PENETRATIONS
12. ACCESS SHALL BE PROVIDED BY GC AS REQUIRED FOR
INSTALLATION AND MAINTENANCE OF MECHANICAL,ELECTRICAL,
AND OTHER ELEMENTS WITHIN CEILING SPACE AND AS REQUIRED
BY CODE. LOCATIONS FOR SPECIAL ACCESS DOORS, HATCHES,
ETC. SHALL BE COORDINATED WITH OTHER TRADES.
13. INSPECTIONS, AS REQUIRED BY LOCAL AUTHORITIES, SHALL BE
COORDINATED BY GC PRIOR TO CLOSING OF CEILING.
14. SHOP DRAWINGS FOR ALL RELATED TRADES (PLUMBING, HVAC)
SHALL BE SUBMITTED FOR REVIEW/APPROVAL PRIOR TO
MANUFACTURING AND INSTALLATION.
15. ALL HVAC ELEMENTS SHALL MATCH ADJACENT WALL OR CEILING
FINISH COLOR, INSTALLED FLUSH AND TRUE AND CENTERED
WITHIN THE CEILING GRID. LOCATIONS SHALL BE PER APPROVED
MECHANICAL PLANS.
16. INSULATION OF COLD WATER LINES SHALL BY PROVIDED TO
PREVENT CONDENSATION DAMAGE AND IN OBSERVANCE OF
ENERGY CONSERVATION PRACTICES, HOT WATER HEATING LINES
SHALL BE INSULATED - SEE SPECIFICATIONS.
17. THERMOSTATS SHALL BE MOUNTED AT 4'-0" A.F.F. LOCATIONS
PER MECHANICAL PLAN AND TO BE COORDINATED BY GC WITH
OTHER TRADES. MOUNT TO ALIGN VERTICALLY WITH LIGHT
SWITCHES.
18. ALL BROCHURES, OPERATING MANUALS, CATALOGS, SHOP
DRAWINGS, ETC. SHALL BE TURNED OVER TO THE OWNER AT JOB
COMPLETION. ALL PRODUCT WARRANTY REGISTRATION CARDS,
APPLICATIONS, AND CERTIFICATES SHALL BE COMPLETED AND
TURNED OVER TO THE OWNER.
GENERAL MECHANICAL NOTES
HVAC GENERAL NOTES
* CONTRACTOR SHALL LOCATE THERMOSTATS AND
TEMPERATURE SENSORS AT 4'-0" AFF, A MAXIMUM OF 8"
FROM LIGHT SWITCH.
* PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF
MECHANICAL EQUIPMENT. COORDINATE SIZES WITH
MECHANICAL EQUIPMENT SELECTED.
* ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE
RATED FOR PRESSURE CLASS OF 2" W.G. UNLESS NOTED
OTHERWISE.
* THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS
ON HVAC EQUIPMENT AFTER ALL DUST PRODUCING
CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE
FINAL PUNCH.
PROJECT GENERAL NOTES
* REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES.
* THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
FIELD VERIFYING, PRIOR TO FINAL BID, ALL EXISTING
CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS
WITHIN TENANT SPACE AND WITHIN CLOSE PROXIMITY OF
TENANT SPACE.
* WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF
CONSTRUCTION, PREVENT CONSTRUCTION DEBRIS FROM
ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO
START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
* COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT,
LIGHTS, CABLE TRAY, STRUCTURE, AND EQUIPMENT TO
PREVENT CONFLICTS.
* THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE
CONDITIONS BOTH EXISTING AND THOSE ILLUSTRATED BY
THESE DOCUMENTS AS WELL AS THOSE WHICH CAN BE
REASONABLY ANTICIPATED INCLUDING, BUT NOT LIMITED TO
ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND
OTHER SYSTEMS INVOLVED ON THIS PROJECT.
* FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING
SYSTEM, AND SHALL CONFORM TO ALL REQUIREMENTS OF
APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING
BUT NOT LIMITED TO THE INTERNATIONAL BUILDING CODE
AND INTERNATIONAL MECHANICAL CODE.
* ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0"
FROM EDGE OF ROOF.
* LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT
AWAY FROM THE SPACE ABOVE ELECTRICAL PANELS.
TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.
* FIRE SEAL AROUND DUCT AND PIPING PENETRATIONS OF FIRE
RATED WALLS. REFER TO SPECIFICATION.
* PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND
DUCTS THROUGH FOUNDATIONS, FLOORS, WALLS, AND ROOF.
* ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT
TO MECHANICAL EQUIPMENT.
* REFER TO PLUMBING SERIES DRAWINGS FOR GAS AND A.C.
CONDENSATE DRAIN PIPING.
* PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF
FLOW UNTIL ANOTHER SIZE IS SHOWN.
* FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT
SHOWN ON THE SEGMENTS, REFER TO DETAILS, SCHEDULES,
AND SPECIFICATIONS.
* INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE
RESPECTIVE MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS, AT A LEVEL OF QUALITY AND WORKMANSHIP
CONSISTENT WITH THE SPECIFICATIONS.
* LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS
INDICATED ON THE DRAWING, ARE APPROXIMATE AND
SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL
BE COORDINATED WITH ALL OTHER TRADES TO AVOID
INTERFERENCE IN THE FIELD.
* INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS
PRACTICAL IN ROOMS WITHOUT CEILINGS U.N.O.
MECHANICAL SHEET INDEX
MECHANICAL
M0.00 MECHANICAL TITLE SHEET
M1.10 LEVEL 1 HVAC PLAN
M7.00 MECHANICAL DETAILS
M8.00 MECHANICAL SCHEDULES
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
M0.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
MECHANICAL
TITLE SHEET
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
Title Sheet Revision
T
T
A
A
C
C
B
B
R.R.
104
UTILITY / MECH
103
EVIDENCE / STOR.
102
STOR.
105
SHOP
101
UH-2
UH-1
EF-1
36"x24"
IL-1
50
4"
EH-1
EF-4
1 1
2 2
3 3
4 4
EF-3
150
6"
EH-2
250
6"
EH-2
EF-2
CO NO2
6"Ø E/A
4"Ø E/A
1
1
24"Ø C/A 4"Ø FLUE
4"Ø C/A4"Ø FLUE
3
3
13' AFF
KEYNOTES
1 PROVIDE MANUFACTURERS HORZONTAL CONCENTRIC VENT
KIT PER DETAIL /M7.00
2 NO2 SENSOR LOCATED AT 3' AFF, CO SENSOR LOCATED @ 5'
6" AFF
3 MOUNT UNIT HEATER TO CIELING 15' 6'' AFF
8'16'4'0
3/8" = 1'-0"1 LEVEL 1 HVAC PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
M1.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1 HVAC
PLAN
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
SECURE CONCENTRIC ADAPTER BOX
TO WALL WITH BRACKETS AND
ADJUST SO THAT THE BOX IS
SLIGHTLY SLOPED TO THE OUTSIDE
COMBUSTION AIR PIPE
VENT AIR PIPE
ONE PIECE
"TERMINAL END "
VENT PIPE-PITCH TO
DRAIN
THIMBLE
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
M7.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
MECHANICAL
DETAILS
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
N.T.S.1 CONCENTRIC VENT ASSEMBLY KIT
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
CONTROL SEQUENCE OF OPERATION
EXHAUST FANS:
EF-1 SHALL BE INTERLOCKED WITH THE CO/NO2 SENSOR AND SHALL ENERGIZE WHEN NO2 OR CO CONCENTRATION REACHES UNSAFE LEVELS.
MANUAL OVERIDE SWITCH SHALL ALSO BE PROVIDED.
EF-2 SHALL ENERGIZE DURING OCCUPANCY
LOUVERS: IL-1 SHALL BE INTERLOCKED WITH EF-1.
UNIT HEATERS: UH-1- UH-2 WILL BE SET TO MAINTAIN A HEATING SET POINT OF 68°F(ADJ) CONTROLLED BY A PROGRAMMABLE THERMOSTAT
LOCATED PER PLANS
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
M8.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
MECHANICAL
SCHEDULES
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
UNIT HEATER SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN HEATING
INPUT
HEATING
OUT PUT AFUE V/Ø/Hz MOCP FLA
WEIGHT
(LBS)NOTESMANUFACTURER MODEL
UH-1 NATURAL GAS UNIT HEATER REZNOR UDAS 75000 Btu/h 62250 Btu/h 83 120/1/60 15.0 A 3.3 A 81 lb 1
UH-2 NATURAL GAS UNIT HEATER REZNOR UDAS 75000 Btu/h 62250 Btu/h 83 120/1/60 15.0 A 3.3 A 81 lb 1
EXHAUST FAN SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN
AREA SERVED AIR FLOW
MOTOR
POWER
DESIGN
POWER RPM E.S.P.
ELECTRICAL
FLA WEIGHT NOTESMANUFACTURER MODEL VOLTAGE FREQUENCY PHASE
EF-1 SIDEWALL EXHASUT FAN GREENHECK SE1-16-426-VG WAREHOUSE 1100 CFM 0.50 hp 0.03 hp 695 0.050 in-wg 115 V 60 Hz 1 6.80 A 34.0 lb
EF-2 CEILING MOUNTED EXHAUST FAN LIGHT PANASONIC FV-30VQ3 WAREHOUSE 250 CFM 0.08 hp 0.08 hp 877 0.250 in-wg 120 V 60 Hz 1 0.24 A 10.4 lb
EF-3 CEILING MOUNTED EXHAUST FAN LIGHT PANASONIC FV-20VQ3 EVIDENCE 150 CFM 0.05 hp 0.02 hp 871 0.250 in-wg 120 V 60 Hz 1 0.24 A 10.4 lb
EF-4 CEILING MOUNTED EXHAUST FAN LIGHT PANASONIC FV-0511VKL2 RESTROOM 50 CFM 0.02 hp 0.02 hp 731 0.250 in-wg 120 V 60 Hz 1 0.24 A 10.4 lb
LOUVER SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN UNIT SIZE
(W"xH"xD")
FREE AREA
(FT^2)
PERFORMANCE
FINISH MOUNTING NOTESMANUFACTURER MODEL VOLUME SP (IN WC)
IL-1 INTAKE COMBINATION LOUVER GREENHECK EAC-401 36X24X4 2 1100 CFM 0.04 BLACK 1,2
EXHAUST HOOD SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN NECK INSTALLATION
DAMPERMANUFACTURER MODEL WIDTH HEIGHT BORDER TYPE
EH-1 EXHAUST WALL CAP BROAN 843BL SURFACE MOUNT INSTALLATION
EH-2 EXHAUST WALL CAP BROAN 843BL SURFACE MOUNT INSTALLATION
NOTES:
1. FLANGE MOUNT TO EXTERIOR WALL.
2. INCLUDE 120V ACTUATOR.
NOTES:
1. PROVIDE VERTICLE LOUVER AT -54°
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
WV
CA
CD
CW
F-CW
H-CW
S-CW
HW
HW 140°
HWC
HWC 140°
GV
GW
NG
OV
OW
V
W
RWL
RWLO
COMBINATION WASTE& VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
COLD WATER
FILTERED COLD WATER
HARD COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER 140°
HOT WATER RECIRC
HOT WATER RECIRC 140°
GREASE VENT
GREASE WASTE
NATURAL GAS
SAND/OIL VENT
SAND/OIL WASTE
SANITARY VENT
SANITARY SEWER
RAIN WATER LEADER
RAIN WATER LEADER OVERFLOW
CAP
PLUG
2"
4"
4"4"
PLUMBING AND PIPING SYMBOLS
KEYNOTE CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL PLUMBING SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
DRAIN SIZE
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
1
-
---
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
LP PROPANE GAS
TYPE (SEE SCHEDULE)
Room
4
RO REVERSE OSMOSIS WATER
IW INDIRECT WASTE
4000 SF
6" RD-1
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
ABBREVIATIONS
4" FD-1FLOOR DRAIN
4" FS-2FLOOR SINK
4" FD-3PFLOOR DRAIN
8 WFU
4" FD-13HUB DRAIN
DRAIN TAGS
"P" - INDICATES PRIMER
CONNECTION
FIXTURE UNITS
COMBINATION
DRAINS
ROOF AREA SERVED
BY DRAIN
2" DOM. WM
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
WATER CLOSET -
WALL HUNG - ADA
WC-5
UR-2
1 WFU
LAV-1A
1 CWFU
1 HWFU
LAV-1A
FIXTURE UNITS
4" WCO
PIPE ACCESORY
TAG
PLUMBING FIXTURE TAGS
4" WCO
TYPE (SEE SCHEDULE)
WC-5A
PIPING SYMBOLSGENERAL PLUMBING NOTES
1. ALL PLUMBING AND PRACTICE TO BE IN ACCORDANCE WITH
CURRENT UNIFORM PLUMBING CODE.
2. COMPLETE INSTALLATION OF PLUMBING SYSTEM TO
CONFORM TO STATE BUILDING, MECHANICAL ENERGY, FIRE,
AND HEALTH CODES, AND REGULATIONS ADOPTED BY LOCAL
JURISDICTIONS.
3. PLUMBING SYSTEMS AS SHOWN ARE SCHEMATIC IN NATURE
AND ITEMS NOT SPECIFICALLY CALLED FOR OR SHOWN, BUT
REQUIRED FOR INSTALLATION FOR THE COMPLETE MECH.
SHALL BE PROVIDED, AND ARE REQUIRED AS PART OF THE
CONTRACT. MANUFACTURER'S RECOMMENDATIONS AND
INDUSTRY STANDARDS SHALL APPLY.
4. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
PLUMBING SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED, AND AS REQUIRED BY CODE.
5. CONTRACTOR RESPONSIBILITY TO VERIFY QUANTITIES.
6. MAINTAIN A MINIMUM OF 6'-6" OF GROUND COVER OVER ALL
UNDERGROUND WATER MAINS AND A MINIMUM OF 3'0" OF
GROUND COVER OVER ALL UNDERGROUND SEWERS AND
DRAINS.
7. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.
8. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
9. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END
DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND LOW
POINTS.
10. SUBCONTRACTOR SHALL COORDINATE WITH GENERAL AND
VERIFY ALL ROUTING AND SUPPORT SYSTEMS & INCLUDE IN HIS
BID ALL NECESSARY TO PROVIDE THE OWNER WITH A
COMPLETE SYSTEM.
11. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES
INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
12. ALL "OR EQUAL" FIXTURES AND ACCESSORIES TO BE APPROVED
BY ARCHITECT OR ENGINEER.
13. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL FIXTURES SHALL
BE WHITE.
14. IT IS UNLAWFUL TO CONCEAL CRACKS, HOLES, OR OTHER
IMPERFECTIONS IN MATERIALS BY WELDING, BRAZING, OR
SOLDERING OR BY USING THEREIN OR THEREON ANY PAINT,
WAX, TAR, OR OTHER LEAK-SEALING OR REPAIR AGENT.
15. BURRED ENDS OF ALL PIPE AND TUBING SHALL BE REAMED TO
THE FULL BORE OF THE PIPE.
16. PLUMBING SYSTEMS SHALL BE INSTALLED IN A MANNER
CONFORMING TO THE PLUMBING CODE AND THE
MANUFACTURER'S RECOMMENDATIONS. IN INSTANCES
WHERE THE CODE AND THE MANUFACTURER'S INSTRUCTIONS
CONFLICT, THE MORE STRINGENT PROVISIONS SHALL PREVAIL.
17. ALL VALVES, PIPES, AND FITTINGS SHALL BE INSTALLED IN
CORRECT RELATIONSHIP TO THE DIRECTION OF FLOW.
18. NO PIPING SHALL BE DIRECTLY EMBEDDED IN CONCRETE OR
MASONRY. NO STRUCTURAL MEMBER SHALL BE SERIOUSLY
WEAKENED OR IMPAIRED BY CUTTING, NOTCHING OR
OTHERWISE.
19. PIPING SUBJECT TO UNDUE CORROSION, EROSION, OR
MECHANICAL DAMAGE SHALL BE PROTECTED IN AN APPROVED
MANNER.
20. NO WATER, SOIL, OR WASTE PIPE SHALL BE INSTALLED OR
PERMITTED OUTSIDE A BUILDING OR IN AN EXTERIOR WALL
UNLESS, WHERE NECESSARY, ADEQUATE PROVISION IS MADE
TO PROTECT SUCH PIPE FROM FREEZING.
21. ALL PIPE PENETRATING FLOOR/CEILING ASSEMBLIES AND FIRE-
RESISTANCE RATED WALLS OR PARTITIONS SHALL BE
PROTECTED WITH THE REQUIREMENTS OF THE BUILDING
CODE.
22. SLEEVES SHALL BE PROVIDED TO PROTECT ALL PIPING
THROUGH CONCRETE OR MASONRY EXTERIOR OR BEARING
WALLS, AND SHALL BE SIZED SO THERE IS A MINIMUM 1/2"
CLEARANCE AROUND THE PIPE AND/OR INSULATION.
23. PIPING THROUGH CONCRETE OR MASONRY WALLS SHALL NOT
BE SUBJECT TO ANY LOAD FROM BUILDING CONSTRUCTION.
24. ALL PIPING SHALL BE SUPPORTED IN SUCH A MANNER AS TO
MAINTAIN ITS ALIGNMENT, AND PREVENT SAGGING.
25. ALL PIPING SHALL BE HUNG AND/OR SUPPORTED TO
ELIMINATE NOISE AND VIBRATION WITH APPROPRIATE
HANGERS AND SUPPORTS. SEE DETAILS FOR REQUIREMENTS.
26. PIPING IN THE GROUND SHALL BE LAID ON A FIRM BED FOR ITS
ENTIRE LENGTH. WHERE SUPPORT IS OTHERWISE PROVIDED, IT
SHALL BE ACCEPTABLE TO THE ADMINISTRATIVE AUTHORITY.
27. HANGERS AND ANCHORS SHALL BE OF SUFFICIENT STRENGTH
TO SUPPORT THE WEIGHT OF THE PIPE AND ITS CONTENTS.
PIPING SHALL BE ISOLATED FROM INCOMPATIBLE MATERIALS.
28. THREADS ON IRON PIPE SIZE (IPS) PIPE AND FITTINGS SHALL BE
STANDARD TAPER PIPE THREADS. THREADS ON TUBING SHALL
BE APPROVED TYPES. THREADS ON PLASTIC PIPE SHALL BE
FACTORY CUT OR MOLDED. THREADED PLASTIC PIPE SHALL BE
SCHEDULE 80 MINIMUM WALL THICKNESS. TUBING THREADS
SHALL CONFORM TO FINE TUBING THREAD STANDARDS. WHEN
A PIPE JOINT MATERIAL IS USED, IT SHALL BE APPLIED ONLY ON
MALE THREADS AND SUCH MATERIALS SHALL BE APPROVED
TYPES, INSOLUBLE IN WATER, AND NONTOXIC. CLEANOUT
PLUGS AND CAPS SHALL BE LUBRICATED WITH WATER
INSOLUBLE, NON-HARDENING MATERIAL OR TAPE.
29. JOINTS IN COPPER TUBING SHALL BE MADE BY THE
APPROPRIATE USE OF APPROVED COPPER OR COPPER ALLOY
FITTINGS. SURFACES TO BE JOINED BY SOLDERING SHALL BE
CLEANED BRIGHT BY MANUAL OR MECHANICAL MEANS. THE
JOINTS SHALL BE PROPERLY FLUXED WITH AN APPROVED TYPE
FLUX, AND MADE UP WITH APPROVED SOLDER. ALL SOLDER
AND FLUXES SHALL BY MANUFACTURED TO APPROVED
STANDARDS.
30. SOLDERS AND FLUXES WITH A LEAD CONTENT WHICH EXCEEDS
TWO-TENTHS (0.20) OF ONE (1) PERCENT ARE PROHIBITED IN
PIPING SYSTEMS USED TO CONVEY POTABLE WATER.
31. JOINTS FROM COPPER TUBING TO THREADED PIPE SHALL BE
MADE BY THE USE OF BRASS ADAPTER FITTINGS.
32. APPROVED UNIONS MY BE USED IN DRAINAGE WORK WHEN
ACCESSIBLY LOCATED IN THE TRAP SEAL OR BETWEEN A
FIXTURE AND ITS TRAP; IN THE VENT SYSTEM, EXCEPT
UNDERGROUND OR IN WET VENTS; AT ANY POINT IN THE
WATER SUPPLY SYSTEM.
33. WHEN CONNECTING PLASTIC PIPE TO OTHER TYPES OF PIPING
USE ONLY APPROVED TYPES OF FITTINGS AND ADAPTERS
DESIGNED FOR THE SPECIFIC TRANSITION INTENDED.
BUILDING MECHANICAL SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES:
• 2018 INTERNATIONAL MECHANICAL CODE
• 2018 UNIFORM PLUMBING CODE
• 2018 INTERNATIONAL FUEL GAS CODE
• 2012 IECC INTERNATIONAL ENERGY CONSERVATION CODE
TRAPS AND INTERCEPTOR NOTES:
1. EACH PLUMBING FIXTURE, EXCEPTING THOSE HAVING INTEGRAL
TRAPS, SHALL BE SEPARATELY TRAPPED BY AN APPROVED TYPE
WATERSEAL TRAP. NOT MORE THAN ONE (1) TRAP SHALL BE
PERMITTED ON A TRAP ARM.
2. THE VERTICAL DISTANCE BETWEEN A FIXTURE OUTLET AND THE
TRAP WEIR SHALL BE AS SHORT AS PRACTICABLE, BUT IN NO
CASE SHALL THE TAILPIECE FROM ANY FIXTURE EXCEED TWENTY-
FOUR (24) INCHES IN LENGTH.
3. EACH PLUMBING FIXTURE TRAP, EXCEPT AS OTHERWISE
PROVIDED IN THE UPC, SHALL BE PROTECTED AGAINST
SIPHONAGE AND BACK-PRESSURE, AND AIR CIRCULATION
ASSURED THROUGHOUT ALL PARTS OF THE DRAINAGE SYSTEM
BY MEANS OF A VENT PIPE.
4. THE VENT PIPE OPENING FROM A SOIL OR WASTE PIPE, EXCEPT
FOR WATER CLOSETS AND SIMILAR FIXTURES, SHALL NOT BE
BELOW THE WEIR OF THE TRAP.
5. EACH TRAP SHALL HAVE THE MANUFACTURER'S NAME STAMPED
LEGIBLY IN THE METAL OF THE TRAP AND EACH TUBING TRAP
SHALL HAVE THE GAUGE OF THE TUBING IN ADDITION TO THE
MANUFACTURER'S NAME.
6. EVERY TRAP SHALL HAVE A SMOOTH AND UNIFORM INTERIOR
WATERWAY.
7. THE TRAP SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH
IT IS CONNECTED.
SUPPLY PIPING NOTES:
1. PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING
SYSTEM BRANCHES IN WHICH BRANCH PIPING SERVES TWO OR
MORE FIXTURES.
2. ALL WATER SUPPLY LINES SHALL BE TYPE L COPPER MIN.
3. ALL WATER LINES (HOT & COLD) SHALL HAVE 3/4" MIN.
INSULATION. OR AS SCHEDULED IN PLUMBING SPECS.
4. UNLESS OTHERWISE NOTED, ALL DOMESTIC COLD AND HOT
WATER PIPING SHALL BE 1/2" SIZE.
5. ALL STOPS, RISERS, ESCUTCHEON, P-TRAPS, OR OTHER
ACCESSORIES TO BE STAINLESS STEEL OR CHROME PLATED.
6. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,
TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING
ACCESS ARE ACCESSIBLE.
7. WHERE DOMESTIC COLD AND HOT WATER PIPING DROPS INTO A
PIPE CHASE, THE SIZE SHOWN FOR THE PIPE DROPS SHALL BE
USED TO THE LAST FIXTURE.
8. ALL JOINTS AND FITTINGS IN WATER LINES SHALL BE SOLDERED
TO MEET CURRENT REGULATIONS.
9. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE
OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS (100
FEET OR MORE) TO PERMIT DISASSEMBLY FOR ALTERATION AND
REPAIRS.
10. ALL VALVES IN THE WATER LINES TO BE BRASS.
11. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY
OPERATION.
12. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL
BE FULL SIZE OF PIPE BEFORE REDUCING SIZE TO MAKE
CONNECTIONS TO EQUIPMENT AND CONTROLS.
13. PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT WITH
ACCESSIBLE STOPS.
14. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE
PROVIDED WITH POSITION INDICATORS AND MAXIMUM
ADJUSTABLE STOPS.
15. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN
SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE OF
VALVE IS REMOVED.
16. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS
CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH
REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL
BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE, OR AS
INDICATED ON THE DRAWINGS.
17. IN ALL BUILDINGS WHERE POTABLE WATER AND NONPOTABLE
WATER SYSTEMS ARE INSTALLED, EACH SYSTEM SHALL BE
CLEARLY IDENTIFIED. EACH SYSTEM SHALL BE COLOR CODED AS
FOLLOWS:
POTABLE WATER: GREEN BACKGROUND WITH WHITE LETTERING
NONPOTABLE WATER: YELLOW BACKGROUND WITH BLACK
LETTERING, WITH THE WORDS "CAUTION: NONPOTABLE WATER, DO
NOT DRINK"
WASTE AND VENT PIPING NOTES:
1. RUN ALL WASTE AND VENT PIPING WITH 2% MINIMUM GRADE
UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL BE
GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY GRAVITY.
2. ELEVATIONS AS SHOWN ON THE DRAWINGS ARE TO THE
CENTERLINE OF ALL PRESSURE PIPING, AND TO THE INVERT OF
ALL GRAVITY PIPING.
3. ADJUST SEWER INVERTS TO KEEP TOPS OF PIPE IN LINE WHERE
PIPE SIZE CHANGES.
4. ALL DRAIN PIPING, VENT PIPING, AND RELATED FITTINGS TO BE
SCHEDULE 40 PVC AND CONFORM TO ASTM D-1785.
5. UNLESS OTHERWISE NOTED, ALL PIPING IS TIGHT TO UNDERSIDE
OF SLAB, WITH SPACE FOR INSULATION IF REQUIRED.
6. ALL FIXTURES TO HAVE P-TRAPS & WATER STOP VALVES OF
ADEQUATE SIZE PROVIDED.
7. UNLESS OTHERWISE NOTED, DRAINS SHALL BE INSTALLED AT THE
LOW POINT OF ROOFS, AREAWAYS, FLOORS, ETC.
8. ALL FLOOR DRAINS SHALL HAVE AUTOMATIC TRAP PRIMING
DEVICES.
9. PROVIDE CLEANOUTS IN SANITARY AND STORM DRAINAGE
SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTION, NEAR
THE BASE OF STACKS, EACH HORIZONTAL DRAINAGE PIPE SHALL
BE PROVIDED WITH A CLEANOUT AT ITS UPPER TERMINAL AND
EACH RUN OF PIPING, WHICH IS MORE THAN FIFTY (50) FEET IN
TOTAL DEVELOPED LENGTH, SHALL BE PROVIDED WITH A
CLEANOUT FOR EACH FIFTY (50) FEET, OR FRACTION THEREOF, IN
LENGTH OF SUCH PIPING..
10. ALL CLEANOUTS SHALL BE FULL SIZE OF PIPE FOR PIPE SIZES 6
INCHES AND SMALLER, AND SHALL BE 6 INCHES FOR PIPE SIZES
LARGER THAN 6 INCHES.
11. ALL VTR's AS SPECIFIED ARE MIN. SIZE TO ROOF. ALL ROOF
PENETRATIONS TO BE 3" MIN.
12. ALL ROOF PENETRATIONS TO PROTRUDE 16" MIN.
13. FITTINGS ON SCREWED PIPE SHALL BE OF THE RECESSED
DRAINAGE TYPE. BURRED ENDS SHALL BE REAMED TO THE FULL
BORE OF THE PIPE.
14. THE THREADS OF DRAINAGE FITTINGS SHALL BE TAPPED SO AS
TO ALLOW ONE-QUARTER (1/4) INCH PER FOOT GRADE.
15. FITTINGS USED FOR DRAINAGE SHALL BE OF THE DRAINAGE TYPE,
HAVE A SMOOTH INTERIOR WATERWAY, AND BE CONSTRUCTED
SO AS TO ALLOW ONE FOURTH (1/4) INCH PER FOOT GRADE.
16. CLEANOUTS SHALL BE DESIGNED TO BE GAS AND WATERTIGHT
WITHOUT THE USE OF ANY GASKET, PACKING, OR WASHER.
17. EACH PLUMBING FIXTURE TRAP, EXCEPT AS OTHERWISE
PROVIDED IN THE UPC, SHALL BE PROTECTED AGAINST
SIPHONAGE AND BACK PRESSURE, AND AIR CIRCULATION SHALL
BE ASSURED THROUGHOUT ALL PARTS OF THE DRAINAGE
SYSTEM BY MEANS OF VENT PIPES.
18. CHANGES IN DIRECTION OF VENT PIPING SHALL BE MADE BY THE
APPROPRIATE USE OF APPROVED FITTINGS AND NO SUCH PIPE
SHALL BE STRAINED OR BENT. BURRED ENDS SHALL BE REAMED
TO THE FULL BORE OF THE PIPE.
19. INDIRECT WASTE PIPES EXCLUDING 5' BUT LESS THAN 15' IN
LENGTH SHALL BE DIRECTLY TRAPPED, BUT SHALL NEED NOT BE
VENTED. TRAPS REQUIRING VENTING SHALL EXTEND SEPARATELY
TO THE OUTSIDE AIR.
20. NO MORE THAN 1/3 OF TOTAL PERMITTED VENT LENGTH PER
TABLE 703.2 OF CURRENT U.P.C. CAN BE INSTALLED IN
HORIZONTAL POSITION UNLESS SIZE IS INCREASED BY ONE PIPE
SIZE.
21. ALL RAIN WATER TO BE INSULATED.
4" AD-6 AREA DRAIN
4" SD-29 DECK DRAIN
FLOW CONTROL
DRAIN4" SD-12
STORM DRAIN4" SD-15
1-P1.02D
DENOTES BUILDING NUMBER
(OMIT ON SINGLE BUILDING PROJECTS)
DENOTES SPECIFIC DISCIPLINE
DENOTES SHEET TYPE
DENOTES DEMO PLANS
(OMIT ON NON DEMO SHEETS)
DENOTES SHEET COUNT
DENOTES BUILDING LEVEL
(O IS BASEMENT/CRAWLSPACE LEVEL 1 IS 1 ETC.)
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
CODE COMPLIANCE
IRR IRRIGATION
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P0.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
PLUMBING
TITLE SHEET
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
PLUMBING SHEET INDEX
P0.00 PLUMBING TITLE SHEET
P1.00 UNDERFLOOR PLUMBING PLAN
P1.10 LEVEL 1 PLUMBING SUPPLY PLAN
P2.10 LEVEL 1 WASTE & VENT PLAN
P3.00 ROOF PLUMBING PLAN
P7.00 PLUMBING DETAILS
P8.00 PLUMBING SCHEDULES
PLUMBING GENERAL NOTES
* FIELD VERIFY ALL NEW WATER, WASTE, AND VENT PIPING
CONNECTIONS AND PROVIDE NEW CONNECTIONS AS
REQUIRED FOR PROPERLY OPERATING SYSTEMS.
* PITCH UNDERFLOOR SANITARY WASTE PIPING AT 1/4" PER
FOOT, UNLESS NOTED OTHERWISE.
* PITCH UNDERFLOOR STORM PIPING 3" AND GREATER AT 1/8"
PER FOOT, UNLESS NOTED OTHERWISE. PITCH ALL OTHER
STORM PIPING AT 1/4" PER FOOT UNLESS OTHERWISE NOTED.
* FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR
TO INSTALLATION.
* ROUTE DOMESTIC WATER, FIRE PROTECTION, SANITARY
SEWER, AND STORM SEWER SERVICES TO SITE UTILITIES 5'-0"
FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL
PLANS.
* WASTE AND VENT PIPING BELOW FLOOR AND THROUGH
FLOOR SHALL BE 2" MINIMUM.
* PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF
ALL PLUMBING RISERS.
PROJECT GENERAL NOTES
* REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES.
* THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
FIELD VERIFYING, PRIOR TO FINAL BID, ALL EXISTING
CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS
WITHIN TENANT SPACE AND WITHIN CLOSE PROXIMITY OF
TENANT SPACE.
* WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF
CONSTRUCTION, PREVENT CONSTRUCTION DEBRIS FROM
ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO
START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
* COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT,
LIGHTS, CABLE TRAY, STRUCTURE, AND EQUIPMENT TO
PREVENT CONFLICTS.
* THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE
CONDITIONS BOTH EXISTING AND THOSE ILLUSTRATED BY
THESE DOCUMENTS AS WELL AS THOSE WHICH CAN BE
REASONABLY ANTICIPATED INCLUDING, BUT NOT LIMITED TO
ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND
OTHER SYSTEMS INVOLVED ON THIS PROJECT.
* FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING
SYSTEM, AND SHALL CONFORM TO ALL REQUIREMENTS OF
APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING
BUT NOT LIMITED TO THE INTERNATIONAL BUILDING CODE
AND INTERNATIONAL MECHANICAL CODE.
* ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0"
FROM EDGE OF ROOF.
* LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT
AWAY FROM THE SPACE ABOVE ELECTRICAL PANELS.
TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.
* FIRE SEAL AROUND DUCT AND PIPING PENETRATIONS OF FIRE
RATED WALLS. REFER TO SPECIFICATION.
* PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND
DUCTS THROUGH FOUNDATIONS, FLOORS, WALLS, AND ROOF.
* ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT
TO MECHANICAL EQUIPMENT.
* REFER TO PLUMBING SERIES DRAWINGS FOR GAS AND A.C.
CONDENSATE DRAIN PIPING.
* PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF
FLOW UNTIL ANOTHER SIZE IS SHOWN.
* FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT
SHOWN ON THE SEGMENTS, REFER TO DETAILS, SCHEDULES,
AND SPECIFICATIONS.
* INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE
RESPECTIVE MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS, AT A LEVEL OF QUALITY AND WORKMANSHIP
CONSISTENT WITH THE SPECIFICATIONS.
* LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS
INDICATED ON THE DRAWING, ARE APPROXIMATE AND
SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL
BE COORDINATED WITH ALL OTHER TRADES TO AVOID
INTERFERENCE IN THE FIELD.
* INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS
PRACTICAL IN ROOMS WITHOUT CEILINGS U.N.O.
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
Title Sheet Revision
A
A
C
C
B
B
R.R.
104
UTILITY / MECH
103
EVIDENCE / STOR.
102
STOR.
105
SHOP
101
2" FD-1
2" FD-1
4"
W
4" W
2" W
2" W
2"
V
2"
V
2"
V
FCO
1
1" CW
4'' TWO-WAY
CLEANOUT
3
4
4
1 1
2 2
3 3
4 4
4" W SCH 40 PVC @ 1/4'' PER 1' 0''
5
3" OW
3" OW SCH 40 PVC @1/4'' PER 1' 0''3" W FCO
(TYP.)
2
2" W
2" V
3" W
1
1" CW UP
2" V UP2" V UP 2" V UP
FCO
KEYNOTES
1 1/2" PEX TO PRIME TRAP FROM LAV TAIL PIECE PER DETAIL
1/P7.00
2 INSTALL FLOOR CLEANOUT PER DETAIL 2/P7.00
3 INSTALL 2-WAY CLEANOUT PER DETAIL
4 SEE CIVIL PLANS FOR CONTINUATION OF PIPING
5 SEE DETAIL 6 /P7.00 FOR SAND OIL SEPERATOR DETAIL
8'16'4'03/8" = 1'-0"1 UNDERFLOOR PLUMBING PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P1.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
UNDERFLOOR
PLUMBING
PLAN
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
A
A
C
C
B
B
R.R.
104
UTILITY / MECH
103
EVIDENCE / STOR.
102
STOR.
105
SHOP
101
1" CW
WC-1A
LAV-1A
MS-1
DHW-1
EWS-1
3/4" NG
1/2" NG
1/2" NG
METER:
150,000 BTU/H
14'' W.C. INLET
PRESSURE
1 1
2 2
3 3
4 4
1
3/4" CW
1/2" HW
1" HW
HB-1HYD-1
3/4" CW DN
1/2" CW DN
1/2" HW
1/2" CW
1/2" CW DN
1/2" CW DN
1" HW
1" CW
2
1" DCV
45
1" CW
KEYNOTES
1 PROVIDE RECESSSED WALL CABINET FOR THERMOSTATIC
MIXING VALVE (S19-2150 OR EQUIVELANT)
2 ROUTE GAS PIPING ALONG CEILING
3 SEE DETAIL 8/P7.00 FOR UNIT HEATER GAS CONNECTION
4 SEE DETIAL 9/P7.00 FOR WATER RISER DIAGRAM
5 SEE WATER HEATER DETAIL 10/P7.00
8'16'4'03/8" = 1'-0"1 LEVEL 1 PLUMBING PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P1.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1
PLUMBING
SUPPLY PLAN
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
3
3
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
A
A
C
C
B
B
R.R.
104
UTILITY / MECH
103
EVIDENCE / STOR.
102
STOR.
105
SHOP
101
WC-1A
DHW-1
LAV-1A
2" V DN 2" V DN
FCO
1 1
2 2
3 3
4 4
EWS-1MS-1
2" FD-1
FCO
3" FD-1
3" FD-1
3" FD-1
2" FD-1
2" V UP 2" V UP
3" VTR
2" V DN
FCO
FCO
4'' TWO-WAY
CLEANOUT
3" VTR3" VTR
1
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P2.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1 WASTE
& VENT PLAN
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
KEYNOTES
8'16'4'03/8" = 1'-0"1 LEVEL 1 PLUMBING WASTE & VENT PLAN
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
A
A
C
C
B
B
1 1
2 2
3 3
4 4
3" VTR 3" VTR
KEYNOTES
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P3.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ROOF
PLUMBING
PLAN
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
0 2'4'6'3/8" = 1'-0"1 ROOF PLUMBING PLAN
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
(2) PVC COMBINATION
WYE-1/8" BENDS BACK
TO BACK (TYP.) OR (1)
2-WAY CLEANOUT TEE
GRADE
PVC FITTING,
TYPICAL ALL FITTINGS
PVC THREADED
PLUG, TYP6"
M
A
X
FLANGED WITH
FLASHING COLLAR
AS REQ'D
FLOOR LINE
BRONZE
SCORATED TOPCENTER SECURING
SCREW
THREADED
PLUG
FITTING TYPE AS
REQ'D TO SUIT
FLASHING COLLAR
FLASHING PAN
FLOORING PER FINISH SCHEDULE
9" (225) DIA. TWO-PIECE NICKEL
BRONZE FLASHING STRAINER
LOOSE GRAVEL AT WEEP HOLES
CAULKED, NO-HUB OR
THREADED CONNECTION
CHROME PLATED BRASS
TAILPIECE WITH 1/2" Ø
BRANCH
1/2" Ø PEX
PIPE TO FLOOR DRAIN
COMPRESSION COUPLING
ESCHUTCHEON
1/2" STAINLESS STEEL
BRAIDED HOSE
LAVATORY
PRIMING DISTRIBUTION
TEE WHERE 3 FD'S ARE
BEING SERVED (SOUIX
CHIEF 695-D30) OR EQUAL
CONDENSATE FROM
ABOVE (IF REQUIRED)
ESCUTCHEON
CLEANOUT TEE
CLEANOUT PIPE
ACCESS COVER
FINISHED WALL
MIXING VALVE
FLOW SWITCH
WALL BRACKET
INLET
PLUGGED NIPPLE
EYEWASH DRAIN
FLANGE WITH 3 BOLT HOLES
ANCHOR WITH EXPANSION BOLTS
EYE-FACE WASH WITH STAINLESS
STEEL BOWL
DELUGE HEAD
1" BALL VALVE
7'
-0"
FLOW ALARM
ANNUNCIATOR
HW
SUPPLY
CW SUPPLY
BALL VALVE WITH
MEMORY STOP AND
LABELING TO PREVENT
UNAUTHORIZED
SHUT-OFF
EYEWASH VALVE
NOTE:
1. PROVIDE A LOOSE-KEY LOCKSHIELD TYPE SHUT-OFF VALVE IN DOMESTIC WATER SUPPLY DROP TO
EYEWASH. LABEL VALVE TO PREVENT UNAUTHORIZED SHUT-OFF.
WATER DEPTHMODEL
No.
DIM
"B"
DIM
"F"WEIGHTDIM
"E"
DIM
"D"DIM "C"
DIM
"A"
2'-10"2'-0"11,6315004'-0"6'-0"2'-2"3'-0"4113-SO
CAPACITY
GALLON
GROUT ALL
AROUND
INLET SIZE
PER PLANS OUTLET SIZE
PER PLANS
ADJUST TO GRADE
24" DIA. TRAFFIC
RATED, WATER TIGHT
BOLT DOWN LIDS
CLEAR ACCESS
OPENINGS
PRECAST BAFFLE
2" DIA. VENT HOLE
DI
M
"
F
"
DI
M
"
C
"
.
1'
-0"
DI
M
"
D
"
DI
M
"
E
"
1/3 LENGTH2/3 LENGTH
2/
3
W
A
T
E
R
T
A
B
L
E
VA
R
I
E
S
DIM "B"
DI
M
"
A
"
.
.
SAMPLE PORT RING AND
LID (TRAFFIC RATED)
CLEAN OUT/VENT
FLOATING OIL
ADSORBENT
SKIMMER
OLD CASTLE PRECAST (BASIS OF DESIGN)
SEE SAMPLE
PORT DETAIL
PLUG
.
CLEAN OUT
VENT
G
SHUT-OFF
COCK
(4)-1/2"DIA. STEEL
RODS WITH TURN
BUCKELS
UNION
SEE MECHANICAL
FLOOR PLANS FOR
CONTINUATION
AND SIZE
1'
-0"
M
I
N
.
DRIP LEG
1" POLY SERVICE LINE
SWEEP
SLEEVE THROUGH FLOOR AND SEAL
1"X1" POLY SWEAT COPPER
ADAPTER
1" COPPER LINE
1" WATTS LF007 (OR EQUAL)
BACKFLOW PREVENTER
SHUT-OFF VALVE
DRAIN VALVE
PRESSURE GAUGE TYP.
1" CW TO FIXTURES
CODED NOTES
1
2
3
4
5
6
7
8
9
6
7
5
4 3
2
1
9
P
P
10
10
CW
COLD WATER SERVICE, SIZE
AS SHOWN ON PLANS
CHECK VALVE SIZE TO PIPE SIZE
WATTS POTABLE WATER EXPANSION
TANK, PLT-5, INSTALL PER MFR.
RECOMMENDATION AND STATE & LOCAL
CODES.
UNION, DIELECTRIC IF REQ'D
WATER HEATER, SEE SCHEDULE
BALL VALVE
T&P RELIEF VALVE , AND DRAIN
PAN TO BE PIPED TO BATHROOM
BELOW
SEISMIC STRAP TO WALL PER UPC,
HOLDRITE HR-80-180
120°F WATER SERVICE LOOP, SIZE AS
SHOWN ON PLANS
CODED NOTES
1
7
2
8
4
5
4
8
11
1
2
3
4
5
7
8
9
10
11
9
HW
CW TO FIXTURES, SIZE PER PLANS
3
TM
V
THERMOSTATIC MIXING VALVE
(CALEFFI TANK MIXER 520) OR EQUAL
12
12
10
10
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P7.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
PLUMBING
DETAILS
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
N.T.S.4 2WAY CLEANOUT1
N.T.S.2 FLOOR CLEANOUT
N.T.S.3 FLOOR DRAIN1
N.T.S.1 TAILPIECE TRAP PRIMER
N.T.S.5 WALL CLEANOUT
3/32" = 1'-0"7 EMERGENCY EYEWASH PIPING DETAIL
N.T.S.6 SAND/OIL INTERCEPTOR DETAIL
N.T.S.8 UNIT HEATER-GAS
N.T.S.9 WATER RISER DIAGRAM
1" = 1'-0"10 ELEC. WATER HEATER
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
P8.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
PLUMBING
SCHEDULES
CLCMSM
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
DOMESTIC FIXTURE SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN TRIM
SPECIFICATIONMANUFACTURER MODEL MANUFACTURER MODEL
EWS-1 EMERGENCY EYEWASH/SHOWER STATION BRADLEY S19314 INCLUDE TEPID WATER TMV S19-2150
FD-1 FLOOR DRAIN WATTS FD-12 PVC FLOOR DRAIN WITH ADJUSTABLE ROUND HEEL PROOF NICKEL BRONZE STRAINER, TRAP PRIMING PORT, AND NO HUB OUTLET.
HB-1 HOSE BIBB WOODFORD 24 INTERIOR HOSE BIBB WITH VACUUM BREAKER, 3/4" HOSE THREAD OUTLET, LOCK SHIELD CAP, AND REMOVABLE "TEE" HANDLE. PROVIDE SHUTOFF VALVE IN COLD WATER SUPPLY AHEAD OF HOSE BIBB.
HYD-1 EXTERIOR WALL HYDRANT WOODFORD 67 WOODFORD 67 NON-FREEZE TYPE WALL HYDRANT, WITH DOUBLE CHECK BACKFLOW PREVENTER, VALVE ON THE INSIDE OF THE WALL, SPOUT WITH BACKFLOW PREVENTER, AND LOOSE KEY SOCKET ON THE OUTSIDE OF THE WALL. MAKE
ARRANGEMENTS WITH THE GENERAL CONTRACTOR TO PROVIDE THE NECESSARY RECESS IN THE WALL. WHERE A RISER TO A WALL HYDRANT OCCURS IN AN OUTSIDE WALL THE CONTRACTOR SHALL INSULATE THE CHASE WITH 2”
STYROFOAM INSULATION ON ALL SIDES OF THE CHASE, EXCEPT THE INSIDE WALL OF THE CHASE. PROVIDE SHUTOFF VALVE IN ACCESSIBLE LOCATION.
LAV-1A LAVATORY - WALL HUNG - ADA KOHLER K-1728 MOEN 8430F05 WALL HUNG LAVATORY WITH BACKSPLASH, FAUCET HOLES ON 4” CENTERS. MANUAL DECK-MOUNTED FAUCET, EXTERNAL ASSE 1070 COMPLIANT THERMOSTATIC MIXING VALVE, GRID DRAIN, LOOSE KEY ANGLE STOPS AND SUPPLIES.
INSULATE WATER AND WASTE WITH INSULATION KIT. MOUNT AT ADA COMPLIANT HEIGHT.
MS-1 JANITOR SINK EL MUSTEE 63M EL MUSTEE 63.600A SERVICE BASIN WITH CAP ON TWO SIDES, FAUCET SHALL INCLUDE PAIL HOOK AND ATMOSPHERIC VACUUM BREAKER SPOUT. INCLUDE HOSE AND HOSE HOLDER, MOP HANGER, AND STAINLESS STEEL BUMPER GUARDS, AND WALL
GUARDS.
WC-1A WATER CLOSET - FLOOR MOUNT - TANK TYPE - ADA KOHLER K-3979 TANK TYPE ELONGATED FLOOR MOUNTED TANK TYPE WATER CLOSET, WITH CHURCH 295CT ELONGATED OPEN FRONT SEAT. PROVIDE A 1/4" BRASS BALL VALVE AT WALL CONNECTION. INSTALL AT ADA COMPLIANT HEIGHT.
ELECTRIC WATER HEATER SCHEDULE
TAG
BASIS OF DESIGN
TYPE
ELECTRIC HEAT EXCHANGER
EF
UNIT
WEIGHT FLA VOLT PH REMARKSMANUFACTURER MODEL NO.
HEATING
CAP
WATERSIDE
STORAGE MAX TEMP
RISERECOVERY VOL
DHW-1 AO SMITH DEN-52 STORAGE 4.5 kW 18.6 gal/h 50.0 gal 95 °F 0 565 lb 37.5 A 240 V 1 PROVIDE ASSE 1017 COMPLIANT MIXING
VALVE; POWERS SERIES LFSH OR EQUAL.
PIPE ACCESSORY SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN VALVE PROPERTIES
REMARKSMANUFACTURER MODEL FLOW PRESSURE DROP AT RATED FLOW
DCV DOUBLE CHECK VALVE BACKFLOW PREVENTION DEVICE WATTS LF007 20.0 GPM 4.0 psi LEAD FREE, MOUNT VERTICAL
M O NTAN
A
C O U RTNEY
CAR RIER
No.15309P E
PR
O
F
E
S
SION A L E N G INEE
R
LICEN S E D
L
J
PB
XX-1
2
3
4
K
OS
MC
T
TD
D
J
P
P
J
R
OS
LS
PC
TC
H
T
W
D
S
S
V
M
F
F
F
F
F
F S
F
P
Z
I
FR
T
ES
ML
DC
CL
CR
MD
E
B
D
S
P 2
P 2
N1
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER OR AIR
CONDITIONER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
ELECTRICAL ABBREVIATIONS LIST
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
SYMBOL
RELAY
SYMBOL SYMBOL SYMBOL
ELECTRICAL SYMBOL LEGEND
J
2 POLE SINGLE THROW SW.
SINGLE POLE SW.
LIGHT ON CORD REEL (TYPE DENOTED)
LIGHTING CHANNEL WIRE (TYPE DENOTED)
DIMMER SWITCH
MOMENTARY CONTACT SWITCH
OCCUPANCY SENSOR SWITCH
PUSH BUTTON
SINGLE RECEPT.
TIME DELAY SWITCH
SPLIT DUPLEX RECEPT.
FOURPLEX RECEPT.
DUPLEX RECEPT.
RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)
ISOLATED GROUND RECEPT (DUPLEX SHOWN)
240 VOLT RECEPT.
RECEPT ON DROP CORD (DUPLEX SHOWN)
RECEPT ON CORD REEL (DUPLEX SHOWN)
FLOOR RECEPT. (DUPLEX SHOWN)
TIMER SWITCH
KEYED SW.
SW. W/PILOT
3-WAY SW.
4-WAY SW.
DESCRIPTION
WALL MOUNTED FLOODLIGHT (TYPE DENOTED)
POLE MOUNTED LIGHT (TYPE DENOTED)
RECESSED LIGHT (TYPE DENOTED)
SURFACE LIGHT (TYPE DENOTED)
EXIT SIGN (TYPE DENOTED)
SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)
TRACK AND TRACK LIGHT (TYPES DENOTED)
SURFACE LINEAR LIGHT (TYPE DENOTED)
STRIP LIGHT (TYPE DENOTED)
EMERGENCY BATTERY LIGHT (TYPE DENOTED)
RECESSED LINEAR LIGHT (TYPE DENOTED)
POLE MOUNTED FLOODLIGHT (TYPE DENOTED)
FOURPLEX RECEPTACLE ON EMERGENCY CIRCUIT
LIGHT FIXTURE ON (EM) LIFE SAFETY BRANCH
LIGHT FIXTURE ON (EM) CRITICAL BRANCH
CIRCUIT BREAKER PANEL
DASHED SYMBOL INDICATES REMOVED
HALFTONE SYMBOL INDICATES EXISTING
SOLENOID VALVE
BUS DUCT WITH PLUG IN DISCONNECT (FUSED)
LIGHT LEVEL SENSOR - TYPE DENOTED
TIME CONTROL SWITCH (TIME SWITCH)
HUMIDISTAT
THERMOSTAT
PHOTOCELL
ENCLOSED CIRCUIT BREAKER
PRESSURE SWITCH
SAFETY DISC. SW. (FUSED)
SAFETY DISC. SW. (NON-FUSED)
COMB. MOTOR STARTER (FUSED)
POWER OR DISTRIBUTION PANEL
MOTOR (SEE SCHEDULE)
TRANSFORMER (TYPE DENOTED)
STATIC GROUND RECEPTACLE (TYPE DENOTED)
SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)
JUNCTION BOX
PULL BOX
GROUND ROD (PLAN VIEW)
LIGHTNING PROTECTION AIR TERMINAL
SURGERY SERVICE COLUMN
CLOCK (TYPE DENOTED)
POWER POLE (OPEN OFFICE STYLE)
MULTIOUTLET ASSEMBLY (TYPE DENOTED)
DESCRIPTION
LIGHTNING PROTECTION CONDUCTOR SPLICE
UTILITY SERVICE POWER POLE (SITE)
OCCUPANCY SENSOR - TYPE DENOTED
FLOAT SWITCH
ANTENNA
DOOR SIGNAL - APT. UNIT
SPEAKER (WALL OR CEILING MT.)
MICROPHONE OUTLET
HORN TYPE SPEAKER
VOLUME CONTROL
BUZZER
BELL
INFORMATION OUTLET (TYPE DENOTED)
WALL TELEPHONE OUTLET (TYPE DENOTED)
TELEPHONE OUTLET (TYPE DENOTED)
TELEVISION OUTLET
DESCRIPTION
CHIME
WIRELESS ACCESS POINT
DESCRIPTION
GAS DETECTOR (TYPE DENOTED)
F.A. PULLSTATION (TYPE DENOTED)
F.A. DOOR CLOSER
F.A. DOOR HOLDER
F.A. INDIVIDUAL ADDRESSABLE MODULE
FIRE ALARM SHUT DOWN RELAY
SPRINKLER VALVE TAMPER SWITCH
SPRINKLER FLOW SWITCH
F.A. ZONE ADDRESSABLE MODULE
SPRINKLER TEMPERATURE SWITCH
SPRINKLER LEVEL SWITCH
SPRINKLER PRESSURE SWITCH
HEAT DETECTOR (TYPE & TEMP DENOTED)
FIRE ALARM BELL
FIRE ALARM BELL W/STROBE (CANDELAS)
SMOKE DETECTOR (TYPE DENOTED)
FIRE ALARM STROBE (CANDELAS)
FIRE ALARM SPEAKER W/STROBE (CANDELAS)
FLAME DETECTOR (TYPE DENOTED)
DUCT SMOKE DETECTOR (TYPE DENOTED)
REMOTE TEST/STATUS STATION
LINEAR HEAT DETECTOR
FIRE ALARM CHIME W/STROBE (CANDELAS)
FIRE ALARM HORN W/STROBE (CANDELAS)
FIRE ALARM REMOTE ANNUNCIATOR
END OF LINE RESISTOR
CCTV CAMERA WITH PAN/TILT DRIVE
CCTV CAMERA
NURSE CALL DOME LIGHT (2 LAMP)
DOOR CONTACTS
CARD READER
ELECTRIC STRIKE
MOTION DETECTOR (TYPE DENOTED)
NURSE CALL EMERG. STATION
NURSE CALL DUTY STATION
NURSE CALL STAFF STATION
NURSE CALL CODE BLUE EMERG. STATION
NURSE CALL SINGLE PATIENT STATION
NURSE CALL DUAL PATIENT STATION
KEYPAD
MAGNETIC LOCK
COMBINATION LOCK
1 KEYED NOTE (SEE SCHEDULE)
D
1,3,5
1
T1
LPN-102
1
ELECTRICAL SYMBOL NOTES
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY
"D".
SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE.
SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE
OF CONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY NUMBER(S) ADJACENT
TO THE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO CIRCUITS 1,
3, 5.
TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE
OR THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS. EXAMPLE: TRANSFORMER TYPE "T1".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE
OPENING SIDE OF RECESSED PANELBOARDS.
KEYNOTE. SEE THE SPECIAL NOTES ON THAT SHEET FOR THE NOTE NUMBER
INDICATED IN THE HEXAGON.
CONDUIT/WIRES SHOWN WITH SLASH MARKS.
SLASH MARK INDICATORS ARE: SHORT STRAIGHT=PHASE CONDUCTOR
LONG STRAIGHT=NEUTRAL
GROUND= DOT
ISOLATED GROUND = DOT WITH T
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD
DESIGNATION IS SHOWN WITH THE HOME RUN ARROW AIMING AT THE ID.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE
PANELBOARD SCHEDULE WITH THE CORRESPONDING PANELBOARD AND
CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO PANELBOARD LPN; CIRCUITS
1, 3, 5.
LPN-1,3,5
DISCONNECT NOTATION. EXAMPLE: 30A DISCONNECT, 2 POLE, NEMA 3R, 15
AMP FUSE
30A/2P/3R
15AF
CIRCUIT ID. NOTION IS FOUND NEXT TO A SWITCH, WIRE, LIGHT, RCPT OR
EQMT. INDICATES PANEL NAME AND CIRCUIT NUMBER(S).
EXAMPLE: PANEL P1, CIRCUIT NUMBERS 11 & 13.P1-11,13
..
(ISO)
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL EQUIPMENT, FIXTURES, MATERIALS, METHODS, AND WORK MUST BE IN ACCORDANCE AND COMPLIANCE WITH MOST RECENT APPROVED EDITION OF ADAAG, ANSI, IEEE, NEC, NEMA, NFPA,
OSHA, TIA, CODES AND STANDARDS. IN ADDITION, ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES, STANDARDS, AND ORDINANCES MUST BE FULLY MET.
2. ALL ELECTRICAL WORK IS TO BE PERFORMED, INSTALLED, TESTED, INSPECTED, AND APPROVED BY QUALIFIED AND LEGALLY LICENSED AND BONDED ELECTRICAL CONTRACTORS/PROFESSIONALS AND THEIR DIRECT
REPORTS. WORKING ON ENERGIZED PARTS REQUIRES PROPER EQUIPMENT AND SHALL ONLY BE PERFORMED BY OSHA CERTIFIED EMPLOYEES.
3. ALL ELECTRICAL MATERIAL, EQUIPMENT, FIXTURES, AND DEVICES SHALL BE NEW AND ORIGINAL (UNLESS OTHERWISE NOTED), AND BE LISTED WITH THE UNDERWRITERS LABORATORIES INC., OR EQUAL, AND
SHALL MEET THEIR REQUIREMENTS, AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. ALL ELECTRICAL MATERIAL,
EQUIPMENT, FIXTURES, AND DEVICES MUST BE INSTALLED PER THE MANUFACTURERS LISTING AGREEMENT AND IN ACCORDANCE WITH THE INTENDED PURPOSE. ANY SHOP, FIELD OR SITE MODIFICATIONS TO
ELECTRICAL MATERIAL, EQUIPMENT, FIXTURES, AND DEVICES, MUST NOT INTERFERE, REMOVE, OR ALTER ITS LISTING, WARRANTY, OR SAFETY AGREEMENTS.
4. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, TOOLS, TEST EQUIPMENT, TRANSPORTATION AND PERFORM ALL OPERATIONS NECESSARY OR INCIDENTAL TO PROPER EXECUTION AND
COMPLETION OF ALL "ELECTRICAL WORK" WHETHER SPECIFICALLY MENTIONED OR NOT.
5. ALL COMPLETED ELECTRICAL JOB(S) SHALL BE GUARANTEED BY THE ELECTRICAL CONTRACTOR FOR THE PERIOD OF ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER. ANY WORKMANSHIP PERFORMED BY
THE EC FOUND TO BE DEFECTIVE OR FAULTY DURING THAT PERIOD OF TIME SHALL BE CORRECTED AT ONCE, UPON WRITTEN NOTIFICATION AT THE SOLE EXPENSE OF THE EC.
6. ALL BROCHURES, OPERATING MANUALS, CATALOGS, SHOP DRAWINGS, ETC, RELATED TO ELECTRICAL WORK SHALL BE TURNED OVER TO THE OWNER AT JOB COMPLETION BY EC. ADDITIONALLY, ALL PRODUCT
WARRANTY REGISTRATION CARDS, APPLICATIONS, AND CERTIFICATES SHALL BE COMPLETED AND FILLED OUT AND TURNED OVER TO OWNER. ALL SPARE, SURPLUS, AND RELATED ADJUSTMENT PARTS, TOOLS OR
DEVICES ARE TO TURNED OVER TO OWNER.
7. GENERAL CONTRACTOR SHALL PROVIDE THE OWNER WITH ONE COMPLETE SET OF ELECTRICAL "AS BUILTS" DRAWINGS AT THE COMPLETION OF THE JOB.
8. ELECTRICAL DRAWINGS ARE ESSENTIALLY REPRESENTATIVE IN NATURE, AND DIAGRAMMATIC IN STYLE, SO THAT THE EXACT SIZE AND LOCATION OF EQUIPMENT SHOWN MAY NOT BE TO SCALE, ALL DIMENSIONS
AND CONDUIT/CONDUCTOR DATA SHALL BE VERIFIED IN THE FIELD. LOCATIONS AND DIMENSIONS SHALL BE PER ARCHITECTURAL DRAWINGS; ENGINEERING DOCUMENTS (IF ANY) SHALL PREVAIL IN CASE OF
VARIATION IN SPECIFICATIONS. DISCREPANCIES MUST BE BROUGHT TO THE ATTENTION OF GC AND OWNER BEFORE START OF WORK. FURNITURE INDICATED ON PLANS IS FOR REFERENCE ONLY.
9. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL MATERIAL, EQUIPMENT, FIXTURES, AND DEVICE LOCATIONS WITH ALL RELATED ARCHITECTURAL, MECHANICAL, AND STRUCTURAL DRAWINGS TO
AVOID AND PREVENT IMPROPER INSTALLATIONS OR WASTEFUL PRACTICES.
10. OWNER, GENERAL CONTRACTOR, AND ELECTRICAL CONTRACTOR SHALL COORDINATE AND VERIFY ALL ELECTRICAL WORK REQUIRED FOR ANY OTHER SCOPE OF WORK REQUIRED FOR AUDIO, FIRE/SECURITY
ALARMS; MECHANICAL SYSTEMS; TELEPHONE/DATA CABLES; LIFE SAFETY SYSTEMS; SITE/SEWERAGE WORK, UTILITY/TRENCHING REQUIREMENTS; EMERGENCY/STANDBY POWER SYSTEMS; AND THE LIKE;,
WHETHER OR NOT SPECIFICALLY SHOWN ON THIS PRINT PACK, PRIOR BID.
11. TYPICAL END USER (CORD CONNECTED) ELECTRICAL EQUIPMENT, SUCH AS BUT NOT LIMITED TO, TELEPHONES, COMPUTER, OFFICE EQUIPMENT, TOOLING, OTHER CORD CONNECTED EQUIPMENT, ETC., SHALL BE
PROVIDED BY OTHERS. GENERAL CONTRACTOR SHALL PROVIDE FOR COORDINATION WITH OUTSIDE VENDORS/INSTALLERS REGARDING DELIVERIES, COMMISSIONING, AND TRAINING AS DIRECTED BY OWNER.
12. COMPATIBILITY: ALL ELECTRICAL DEVICES, EQUIPMENT, WIRING, ETC. SHALL BE COMPATIBLE, EACH WITH ONE ANOTHER.
13. SHOP DRAWINGS AND SUBMITTALS SHALL BE PRODUCED WITH APPLICABLE ELECTRICAL DRAWING SHEET PER DESIGN SPECIFICATION AND ALL APPLICABLE CODES AND STANDARDS AND APPROVED CHANGES OR
ADDENDUMS.
14. PANEL SCHEDULES SHALL BE COMPUTER GENERATED (TYPED) AND PLACED IN THE PANEL COVER.
15. VERIFY BREAKER, FUSE, CONDUIT AND WIRE SIZES WITH THE NAMEPLATE RATING OF EQUIPMENT BEFORE INSTALLATION.
16. ELECTRICAL DEVICE COLOR AND STYLE SHALL BE CHOSEN BY THE OWNER. VERIFY PRIOR TO ORDERING/INSTALLING.
17. PROVIDE UFER GROUND AT EACH ELECTRICAL SERVICE ENTRANCE. REFER TO ELECTRICAL DETAIL.
18. ALL MANUFACTURERS SPECIFIED IN THE DRAWINGS AND SPECIFICATIONS ARE BASIS OF DESIGN. OR EQUAL PRODUCTS ARE ALSO ALLOWED.
19. PROVIDE LOCAL DISCONNECTING MEANS AT ALL EQUIPMENT WHERE REQUIRED.
20. PROVIDE GFCI AND ARC FAULT PROTECTION PER NEC 2017.
21. PROVIDE CONTACTOR WHERE APPROPRIATE FOR EXTERIOR LOADS CONTROLLED BY A PHOTOCELL.
22. WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUIT AND SWITCHING CONNECTIONS SHOWN.
23. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS INDICATED
OTHERWISE ON THE EQUIPMENT SCHEDULE.
24. CIRCUIT PATH WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT OF FIXTURES AND CONTROL OF DEVICES.
25. FOR COMMERCIAL SPACES, EMT/MC CABLE IS REQUIRED UNLESS NOTED OTHERWISE.
26. HOMERUNS SHALL CONSIST OF 3/4" EMT AND #12 COPPER MINIMUM.
ELECTRICAL MOUNTING HEIGHTS
RECEPTACLE 18"
SWITCH 46"
THERMOSTAT 58"
DATA/TEL 18"
PANELBOARD 72" TOP OF ENCLOSURE
FA PULL STATION 46"
FA HORN STROBE 12" BELOW CEILING, IF CEILING IS 80"-96" AFF
FA HORN HORN 86" OR 6" BELOW CEILING
TV/AV/INTERCOM 86"
EXIT SIGN 12" ABOVE DOOR TO CENTER OF FIXTURE, UNLESS
CEILING MOUNTED
HEIGHTS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E0.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ELECTRICAL
TITLE SHEET
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
INDEX OF ELECTRICAL DRAWINGS
E0.00 ELECTRICAL TITLE SHEET
E0.10 ELECTRICAL SITE PLAN
E1.10 LEVEL 1 LIGHTING PLAN
E1.20 LEVEL 2 LIGHTING PLAN
E2.10 LEVEL 1 POWER AND SYSTEMS PLAN
E2.20 LEVEL 2 POWER AND SYSTEMS PLAN
E5.00 ELECTRICAL DIAGRAMS
E7.00 ELECTRICAL DETAILS
E8.00 ELECTRICAL SCHEDULES
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
NEW BUILDING
FF: 2930.8'
EM
TEXISTING
15KVA
120/240V
1Ø TRANSFORMER
UTILITY METER,
SERVICE DISCONNECT
200A DISCONNECT
1 2
3
4
BUILDING DMARK
LOCATION
SITE PLAN GENERAL NOTES
* COORDINATE WITH UTILITY FOR SEPARATION OF WORK
ASSOCIATED WITH SERVICE ENTRANCE FEEDER, CONDUCTORS,
AND POTENTIAL TRANSFORMER UPGRADES.
* ALL COMMUNICATIONS CONDUIT AND CABLES SHALL BE
INSTALLED 36" (MINIMUM) BELOW FINISHED GRADE.
* REFER TO CIVIL DRAWINGS FOR ADDITIONAL SITE RELATED
INFORMATION.
1" = 10'-0"1 ELECTRICAL SITE PLAN
KEYNOTES
1 PROVIDE NEW ELECTRICAL SERVICE FEEDER AND 3" CONDUIT
FROM EXISTING 120/240V 1Ø TRANSFORMER TO NEW
SERVICE ENTRANCE METER BASE.
2 ELECTRICAL METER BASE TO BE EQUIPPED WITH BYPASS
PROVISIONS AS REQUIRED BY UTILITY. COORDINATE WITH
UTILITY FOR MORE INFORMATION.
3 TO UTILITY PROVIDED FIBER OPTIC BOX. REFER TO CIVIL
SHEETS FOR EXACT ROUTING AND ADDITIONAL
INFORMATION.
4 FIBER OPTIC SHALL TERMINATE WITHIN BUILDING DMARK
LOCATION.
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E0.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ELECTRICAL
SITE PLAN
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
3
D
OS4
D
OS2
3
OS
3
A
A
C
C
B
B
R.R.
104
UTILITY / MECH
103
EVIDENCE / STOR.
102
STOR.
105
SHOP
101
1 1
2 2
3 3
4 4
WP2
P1-8
WP2
P1-8
W1
WP1
P1-8
WP1
P1-8
P1
P1-4
P1-2
P1-7
1 2
E2
P1-4
E1
P1-7
L1
L1
L1
L1
L1
L1
L1E
3 3
4
P1-5 P1-12
KEYNOTES
1 LIGHTING SWITCH TO CONTROL MEZZANINE AREA LIGHTS. SEE
LEVEL 2 LIGHTING PLAN FOR MORE INFORMATION.
2 LIGHTING SWITCH TO CONTROL LEVEL 2 SHOP LIGHTING. SEE
LEVEL 2 LIGHTING PLAN FOR MORE INFORMATION.
3 SWITCHES SHALL BE NLIGHT WIRED ENABLED DEVICES TO
COMMUNICATE WITH OCCUPANCY SENSORS AND POWER PACKS.
BASIS OF DESIGN DEVICES SHALL BE: NLIGHT- NPODM-DX-WH.
4 SWITCHES SHALL BE NLIGHT WIRED ENABLED DEVICES TO
COMMUNICATE WITH OCCUPANCY SENSORS AND POWER PACKS.
BASIS OF DESIGN DEVICES SHALL BE: NLIGHT- NPODM-WH.
0 2'4'6'
3/8" = 1'-0"1 LEVEL 1 LIGHTING PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E1.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1
LIGHTING PLAN
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
LIGHTING GENERAL NOTES
* CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY
LIGHTING FIXTURES, CONTROL DEVICES, AND ACCESSORIES
NEEDED TO ENSURE INSTALLED SYSTEM IS COMPLETE AND IN
PROPER WORKING ORDER AS DESIGN INTENDED.
* TYPICAL EMERGENCY AND EXIT LIGHTS SHALL BE WIRED TO
NEAREST ROOM LIGHTING CIRCUIT AHEAD OF ANY CONTROLS OR
SWITCHING.
* ALL LAY-IN LIGHT FIXTURES ARE TO BE SUPPORTED INDEPENDENT
OF NON-RATED GRID CEILINGS FROM THE STRUCTURE ABOVE
FROM AT LEAST TWO CORNERS. ATTACH WITH GRID CLIPS OR
TABS RATED FOR LAY-IN CEILINGS.
* CONTRACTOR SHALL VERIFY EACH J-BOX HAS SUFFICIENT
ATTACHMENT ANCHORAGE TO SUPPORT LIGHTING OR FAN
WEIGHT LOADS
* EXIT SIGNS SHALL BE FURNISHED WITH NUMBER OF FACES AND
DIRECTIONAL ARROWS AS REQUIRED TO SUIT PLAN AND THE
LOCAL AUTHORITY.
* CONTRACTOR SHALL VERIFY ALL BULBS, COLORS, LENGTHS,
TRIMS, CEILING TYPES, MOUNTINGS, FINISHES, ETC., WITH THE
ENGINEER, PRIOR TO PLACING FINAL LIGHTING PURCHASE
ORDER, INCLUDING THE INTENT OF ALL APPROVED REVISIONS OR
PUBLISHED ADDENDUMS.
* WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.
PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUITING AND SWITCHING CONNECTIONS SHOWN.
* CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO
PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH
CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER
RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL
EQUIPMENT SCHEDULE.
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
OS1
OS1
OS1
A
A
C
C
B
B
1 1
2 2
3 3
4 4
LB1
LB1
LB1E
LB1
LB1E
LB1
LB1
LB1
P1-12
L1E
L1
L1
P1-5
WP1
P1-8
WP1
P1-8
+16'
+16'
0 2'4'6'
3/8" = 1'-0"1 LEVEL 2 LIGHTING PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E1.20
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 2
LIGHTING PLAN
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
LIGHTING GENERAL NOTES
* CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY
LIGHTING FIXTURES, CONTROL DEVICES, AND ACCESSORIES
NEEDED TO ENSURE INSTALLED SYSTEM IS COMPLETE AND IN
PROPER WORKING ORDER AS DESIGN INTENDED.
* TYPICAL EMERGENCY AND EXIT LIGHTS SHALL BE WIRED TO
NEAREST ROOM LIGHTING CIRCUIT AHEAD OF ANY CONTROLS OR
SWITCHING.
* ALL LAY-IN LIGHT FIXTURES ARE TO BE SUPPORTED INDEPENDENT
OF NON-RATED GRID CEILINGS FROM THE STRUCTURE ABOVE
FROM AT LEAST TWO CORNERS. ATTACH WITH GRID CLIPS OR
TABS RATED FOR LAY-IN CEILINGS.
* CONTRACTOR SHALL VERIFY EACH J-BOX HAS SUFFICIENT
ATTACHMENT ANCHORAGE TO SUPPORT LIGHTING OR FAN
WEIGHT LOADS
* EXIT SIGNS SHALL BE FURNISHED WITH NUMBER OF FACES AND
DIRECTIONAL ARROWS AS REQUIRED TO SUIT PLAN AND THE
LOCAL AUTHORITY.
* CONTRACTOR SHALL VERIFY ALL BULBS, COLORS, LENGTHS,
TRIMS, CEILING TYPES, MOUNTINGS, FINISHES, ETC., WITH THE
ENGINEER, PRIOR TO PLACING FINAL LIGHTING PURCHASE
ORDER, INCLUDING THE INTENT OF ALL APPROVED REVISIONS OR
PUBLISHED ADDENDUMS.
* WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.
PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUITING AND SWITCHING CONNECTIONS SHOWN.
* CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO
PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH
CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER
RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL
EQUIPMENT SCHEDULE.
KEYNOTES
1 LB1/LB1E FIXTURES SHOWN TO BE CONTROLLED VIA SWITCH
LOCATED ON LEVEL 1. SEE LEVEL 1 PLANS FOR MORE
INFORMATION.
2 L1/L1E FIXTURES SHOWN TO BE CONTROLLED VIA SWITCH
LOCATED ON LEVEL 1. SEE LEVEL 1 PLANS FOR MORE
INFORMATION.
1
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
2
48"
GFI
48
"
GF
I
48
"
GF
I
48"
GFI
48
"
GF
I
48"
GFI
48"
GFI
ACGF
I
GFI
GFI
GFI
GF
I
J
GFI
T
T
A
A
C
C
B
B
R.R.
104
UTILITY / MECH
103
EVIDENCE / STOR.
102
STOR.
105
SHOP
101
P1
1
2
DHW-1
1 1
2 2
3 3
4 4
EF-4
IT/SECURITY
RACK
EUH-1
EUH-1
P1-22
P1-17
P1-13
P1-24
P1-8
P1-6
P1-11
P1-19
P1-27
EF-3
P1-3
P1-1
EUH-1
P1-30
120/240V, 1Ø, 3W
200A SERVICE DISCONNECT
P1-9
P1-18,20
3
BUILDING DMARK
LOCATION 4
5
0 2'4'6'
3/8" = 1'-0"1 LEVEL 1 POWER AND DATA PLAN
KEYNOTES
1 INCOMMING ELECTRICAL SERVICE FROM UTILITY.
2 PROPOSED ELECTRICAL UTILITY METER, CT CAN, SERVICE
DISCONNECT LOCATION.
3 EF-4 TO BE CONTROLLED BY OCCUPANCY SENSOR LIGHT
SWITCH. SEE LIGHTING PLANS FOR MORE INFORMATION.
4 PROVIDE NECESSARY CONNECTION FROM BUILDING DMARK
TO IT/SECURITY RACK LOCATION. COORDINATE WITH
OWNER/I.T. FOR ALL NECESSARY EQUIPMENT CONNECTION.
5 CONTRACTOR SHALL PROVIDE SINGLE GANG J-BOX AND ALL
ASSOCIATED MATERIAL FOR MOUNTING AND
WATERPROOFING (EXTERIOR) FOR ALL CAMERA LOCATIONS
SHOWN. COORDINATE WITH OWNER IT DEPARTMENT FOR
SYSTEM REQUIREMENTS PRIOR TO PURCHASING.
COORDINATE WITH EQUIPMENT MANUFACTURER FOR ALL
ADDITIONAL INSTALLATION REQUIREMENTS. PROVIDE CAT6
CABLE FROM IT/SECURITY SERVER RACK TO EACH LOCATION
UNLESS NOTED OTHERWISE OR SELECTED SYSTEM REQUIRES
ALTERNATE MEANS OF CONNECTION.
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E2.10
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 1 POWER
AND SYSTEMS
PLAN
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
POWER GENERAL NOTES
* CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO
PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH
CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER
RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL
EQUIPMENT SCHEDULE.
* RECEPTACLES RATED FOR WET LOCATIONS SHALL BE NEMA 5-20R.
* PRIOR TO ROUGH-IN AND INSTALLATION, THE CONTRACTOR
SHALL FIELD VERIFY THE LOCATON AND REQUIREMENTS OF ALL
ELECTRICAL ITEMS.
* GROUNDING AND BONDING SHALL BE IN STRICT ACCORDANCE
WITH THE NEC AND UTILITY REGULATIONS. PROVIDE COPPER
EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS.
* RECEPTACLES ABOVE THE COUNTERTOPS WHERE INDICATED BY
"AC". EXACT LOCATION SHALL BE COORDINATED WITH THE
ARCHITECT.
* WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.
PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUITING AND SWITCHING CONNECTIONS SHOWN.
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
J
J
CLNG
CLNG
CLNG
A
A
C
C
B
B
1 1
2 2
3 3
4 4
P1-26
P1-15
P1-31
P1-28
UH-2
P1-23
P1-16
P1-10
EF-1
UH-1
EF-2P1-12
1
0 2'4'6'
3/8" = 1'-0"1 LEVEL 2 POWER AND DATA PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E2.20
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
LEVEL 2 POWER
AND SYSTEMS
PLAN
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
POWER GENERAL NOTES
* CIRCUIT NUMBERS AT DEVICES AND FIXTURES CORRESPOND TO
PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH
CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER
RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL
EQUIPMENT SCHEDULE.
* RECEPTACLES RATED FOR WET LOCATIONS SHALL BE NEMA 5-20R.
* PRIOR TO ROUGH-IN AND INSTALLATION, THE CONTRACTOR
SHALL FIELD VERIFY THE LOCATON AND REQUIREMENTS OF ALL
ELECTRICAL ITEMS.
* GROUNDING AND BONDING SHALL BE IN STRICT ACCORDANCE
WITH THE NEC AND UTILITY REGULATIONS. PROVIDE COPPER
EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS.
* RECEPTACLES ABOVE THE COUNTERTOPS WHERE INDICATED BY
"AC". EXACT LOCATION SHALL BE COORDINATED WITH THE
ARCHITECT.
* WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.
PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUITING AND SWITCHING CONNECTIONS SHOWN.
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
KEYNOTES
1 EF-2 SHALL BE CONTROLLED DURING OCCUPANCY. SEE
MECHANICAL SHEETS FOR MORE INFORMATION. PROVIDE
NLIGHT NPP16 POWER PACK TO TIE INTO LIGHTING
CONTROLS.
P1
225A
120/240V
3W, 1Ø
MCB
10K AIC
MSD (MAIN SERVICE DISCONNECT)
120/240V, 3W, 1Ø
AVAILABLE FAULT CURRENT: 9,192 AIC
AIC RATING: 10K AIC
EXISTING
15KVA
120/240V
1Ø, 3W UTILITY
TRANSFORMER
UTILITY U.G. FEEDER
UTILITY METER EQUIPPED
WITH UTILITY APPROVED
BYPASS PROVISIONS
M
225A
2P
MSD
UFER GROUNDING, BUILDING STEEL, WATER PER NEC 250.52
GROUND RODS PER NEC 250.52
REFER TO ELECTRICAL SHEET 1/E7.00 FOR GROUNDING DETAIL.
ALL BREAKERS SHALL BE BOLT-ON TYPE.
ALL PANELS SHALL HAVE LOCKING DOORS AND ENGRAVED LABLES
ALL CONDUCTORS SHALL BE COPPER.
T
INSTALL ELECTRICAL SERVICE AND
METER PER LOCAL UTILITY
POWER COMPANY REQUIREMENTS
EXISTING SERVICE FEEDING
ADJACENT PROPERTY BUILDING
(3) #4/0 CU, (1) #4 GND, 2-1/2"C
(3) #4/0 CU, (1) #4 GND, 2-1/2"C
SINGLE LINE GENERAL NOTES
* OVERCURRENT DEVICES OF ENTIRE DISTRIBUTION SYSTEM SHALL
MEET STATED FAULT CURRENT VALUES WITH FULLY RATED
EQUIPMENT.
* REFER TO PANEL SCHEDULES FOR ADDITIONAL REQUIREMENTS.
WHERE A DISCREPANCY EXISTS BETWEEN EQUIPMENT ON THE
SINGLE LINE DIAGRAM AND THE DETAILED SCHEDULES, THE ITEM
OR ARRANGEMENT WITH BETTER QUALITY, GREATER QUANTITY,
OR HIGHER COST SHALL BE USED.
* ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF
THE ENGINEER.
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E5.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ELECTRICAL
DIAGRAMS
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
N.T.S.1 ELECTRICAL SINGLE LINE DIAGRAM
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
M I N 2 0 '
N GØ
OUTLET BOX
GROUNDING CONDUCTOR
(GREEN)
TAPPED HOLE IN BOX
GROUND SCREW -#10 32 X 3/8"
SLOTTED HEXAGON HEAD,
WASHER FACE SCREW (TYP)
WIRE NUT (TYP)
CONDUIT NOTE:
GROUNDING CONDUCTOR
SHALL BE CONTINUOUS SO
THAT REMOVAL OF DEVICE
WILL NOT INTERFERE WITH
CONDUCTOR CONTINUITY.
STRIP INSULATION AND LOOP BARE
CONDUCTOR AROUND PHASE SCREW
WITHOUT CUTTING CONDUCTOR OR
PROVIDE ADDITIONAL WIRE NUT
TERMINATION EQUAL TO NEUTRAL.
G
N
Ø
RECEPTACLE GROUND
LUG SCREW
DETAIL KEY NOTES:
1. PROVIDE ENOUGH LENGTH TO TERMINATE
DIRECTLY TO GROUND BUS.
2. INSTALL AN ELECTRODE ENCASED BY AT LEAST 2"
OF CONCRETE, LOCATED WITHIN AND NEAR THE
BOTTOM OF A CONCRETE FOUNDATION OR
FOOTING THAT IS IN DIRECT CONTACT WITH THE
EARTH, CONSISTING OF AT LEAST 20 FT OF ZINC
GALVANIZED OR OTHER ELECTRICALLY
CONDUCTIVE COATED STEEL REINFORCING BARS
OF NOT LESS THAN 1/2" IN DIAMETER, OR
CONSISTING OF AT LEAST 20 FT OF BARE COPER
CONDUCTOR NOT SMALLER THAN #4 AWG.
REINFORCING BARS SHALL BE PERMITTED TO BE
BONDED TOGETHER BY THE USUAL STEEL TIE
WIRES OR OTHER EFFECTIVE MEANS.
3. GROUND THE INTERIOR METAL WATER PIPE
WITHIN 5 FEET OF THE WATER PIPE ENTRANCE TO
THE BUILDING. GROUNDING PATH CONTINUITY,
OR THE BONDING CONNECTION TO INTERIOR
PIPING, MUST NOT RELY ON WATER METERS OR
SIMILAR EQUIPMENT (NEC 250.53(D)).
4. MINIMUM OF (2) 5/8" X 8'-0" COPPER CLAD STEEL
GROUND RODS, 25 OHMS OR LESS. CLAMPS
SHALL BE RATED FOR DIRECT BURIAL.
5. BOND ALL METAL RACEWAYS CONTAINING
GROUNDING ELECTRODE CONDUCTORS AT BOTH
END AS REQUIRED BY NEC 250.64(E). PROVIDE
GROUNDING TYPE BUSHINGS AND FITTINGS.
6. BONDING JUMPERS AND COPPER GROUNDING
ELECTRODE CONDUCTORS SHALL BE SIZED BASED
UPON ELECTRICAL SERVICE SIZE (NEC 250.66).
7. PROVIDE COPPER BONDING JUMPER SIZED PER
NEC 250.28(D) OR FACTORY PROVIDED NEUTRAL
TO GROUND BAR LINK. THIS IS THE ONLY PLACE
IN THE BUILDING WHERE NEUTRAL TO GROUND
SHALL BE BONDED TOGETHER.
CONCRETE-ENCASED ELECTRODE
NEC 250.52(A)(3)
BUILDING STEEL
NEC 250.52(A)(2)
METAL WATER PIPE
NEC 250.52(A)(1)
GROUND ROD
NEC 250.52(A)(5)
1
5
6
4
6
3
26
6
G
N 7
METER/MAIN
DISCONNECT EQUIPMENT
6
6
6
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E7.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ELECTRICAL
DETAILS
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
N.T.S.2 TYP. RECEPTACLE GROUNDING DETAIL
N.T.S.1 GROUNDING DETAIL
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR PERMIT
KALISPELL
406-755-3208
#
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAW N:CHECKED:
info@jackola.com jackola.com
BI
M
3
6
0
:
/
/
A
D
2
0
2
0
/
C
O
K
_
S
e
a
r
c
h
B
u
i
l
d
i
n
g
_
M
E
P
2
0
.
r
v
t
E8.00
4/1/2021
CI
T
Y
O
F
K
A
L
I
S
P
E
L
L
PO
L
I
C
E
S
E
A
R
C
H
B
U
I
L
D
I
N
G
1S
T
A
V
E
W
.
KA
L
I
S
P
E
L
L
M
T
5
9
9
0
1
ELECTRICAL
SCHEDULES
MIBJSJ
PR
O
J
E
C
T
#
:
P
r
o
j
e
c
t
N
u
m
b
e
r
OCCUPANCY SENSOR SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN POWER
CONNECTION COVERAGE DELAY SENSITIVITY NOTESMANUFACTURER MODEL
OS1 CEILING MOUNT DUAL TECH OCCUPANCY SENSOR NLIGHT NCM-6-RJB LOW VOLTAGE 1200 SF 20 MIN MAX PROVIDE NECESSARY NPP16
POWER PACK WITH DEVICE AS
NEEDED.
OS2 DUAL RELAY WALL SWITCH OCCUPANCY SENSOR NLIGHT NCM-10-RJB LOW VOLTAGE 500 SF 30 MIN MAX PROVIDE NECESSARY NPP16
POWER PACK WITH DEVICE AS
NEEDED.
OS3 OCCUPANCY SENSOR WALL SWITCH SENSOR SWITCH WSX 2P FAN-WH LINE VOLTAGE 20FT NA NA
OS4 OCCUPANCY SENSOR WALL SWITCH SENSOR SWITCH WSX-WH LINE VOLTAGE 20FT NA NA
ELECTRIC HEATER SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN
MOUNTING WATTS VOLTAGE AMPS Ø POLE NOTESMANUFACTURER MODEL
EUH-1 ELECTRIC UNIT HEATER CADET CSC101TW WALL 1100 W 120 V 9.2 A 1 1
NOTES:
TOTAL EST. DEMAND:86.2 A
RCPT 8700 VA 100.00% 8700 VA TOTAL CONN.:84.9 A
LIGHTS 1225 VA 125.00% 1531 VA TOTAL EST. DEMAND:20681 VA
HVAC 874 VA 100.00% 874 VA TOTAL CONN. LEAD:20375 VA
HEAT 9576 VA 100.00% 9576 VA
LOAD CLASSIFICATION CONNECTED
LOAD
DEMAND
FACTOR
ESTIMATED
DEMAND PANEL TOTALS
TOTAL AMPS:95.1 A 102.2 A
TOTAL LOAD:11412 VA 12263 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 S. GARAGE DOOR 101 20 A 1 800 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 1100 VA 1 20 A EUH-1 R.R.104 30
27 RCPT S. SHOP 101 20 A 1 540 VA 720 VA 1 20 A RCPT MEZ STORAGE 28
25 SPARE 20 A 1 0 VA 800 VA 1 20 A N. GARAGE DOOR 101 26
23 UH-2 S. SHOP 101 15 A 1 288 VA 360 VA 1 20 A RCPT S. UTILITY / MECH 103 24
21 SPARE 20 A 1 0 VA 720 VA 1 20 A RCPT EVIDENCE / STOR. 105 22
19 RCPT N. SHOP 101 20 A 1 900 VA 4500 VA 20
17 RCPT EVIDENCE / STOR. 105 20 A 1 540 VA 4500 VA 2 50 A DWH-1 UTILITY / MECH 103
18
15 MID. GARAGE DOOR 101 20 A 1 800 VA 816 VA 1 20 A EF-1 SHOP 101 16
13 RCPT R.R. 104 20 A 1 360 VA 14
11 RCPT N. UTILITY / MECH 103 20 A 1 360 VA 688 VA 1 20 A LIGHTS/EF-2 SHOP 101 12
9 RCPT I.T. RACK 103 20 A 1 1800 VA 288 VA 1 15 A UH-1 N. SHOP 101 10
7 LIGHTS EVIDENCE / STOR. 105 20 A 1 131 VA 1100 VA 1 20 A EUH-1 UTILITY / MECH 103 8
5 LIGHTS MEZZANINE 20 A 1 105 VA 1100 VA 1 20 A EUH-1 EVIDENCE / STOR. 105 6
3 EF-3 EVIDENCE / STOR. 105 20 A 1 29 VA 75 VA 1 20 A LIGHTS UTILITY / MECH 103 4
1 EF-4 R.R. 104 20 A 1 29 VA 70 VA 1 20 A LIGHTS R.R. 104 2
CKT CIRCUIT DESCRIPTION TRIP POLE A B POLE TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE:NEMA 1 MCB RATING:225A
MOUNTING:SURFACE WIRES:3 MAINS RATING:225A
SUPPLY FROM:UTILITY MSD PHASES:1 MAINS TYPE:MCB
LOCATION:UTILITY/MECH...VOLTS:120/240 A.I.C. RATING:10,000 AIC
PANEL: P1
LIGHTING FIXTURE SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN
MOUNTING VOLT WATTS
LAMP
NOTESMFR CATALOG SERIES COLOR TEMP LUMENS
E1 CEILING EXIT LIGHT LITHONIA LES 1 R 120/277 EL N SD CEILING/SURFACE 120 V 5 W 90 MIN BATTERY BACKUP INCLUDED.
E2 EXIT/EMERGENCY COMBO LITHONIA LES 1 R 120/277 EL N SD CEILING/SURFACE 120 V 5 W 90 MIN BATTERY BACKUP INCLUDED.
L1 LED WRAPAROUND FIXTURE LITHONIA BLWP4-40L-ADSM-120-EZ1-LP840 SURFACE 120 V 35 W 4000K 4099 lm
L1E LED WRAPAROUND FIXTURE LITHONIA BLWP4-40L-ADSM-120-EZ1-LP880 SURFACE 120 V 35 W 4000K 4099 lm BATTERY BACKUP INCLUDED.
LB1 SUSPENDED LED LOW BAY FIXTURE LITHONIA MSL-10000LM-SBL-120-GZ10-40K-80CRI-CS1W-
WH
SURFACE 120 V 86 W 4000K 9798 lm
LB1E SUSPENDED LED LOW BAY FIXTURE LITHONIA MSL-10000LM-SBL-120-GZ10-40K-80CRI-CS1W-
WH
SURFACE 120 V 86 W 4000K 9798 lm BATTERY BACKUP INCLUDED.
W1 LED WRAPAROUND FIXTURE LITHONIA BLWP2-40L-ADSM-120-EZ1-LP830 WALL 120 V 17 W 3000K 1200 lm
WP1 LED WALL PACK LITHONIA ARC1LED-P3-40K-MVOLT-E4WH-PE-DBLXD WALL 120 V 24 W 4000K 3021 lm
WP2 DECORATIVE LED WALL SCONCE LITHONIA OLLWU LED-P1-40K-MVOLT-DDB WALL 120 V 24 W 4000K 500 lm FIXTURE TO BE EQUIPPED WITH EGRESS BATTERY BACKUP. PROVIDE AND INSTALL COMPATIBLE EMERGENCY
REMOTE DRIVER. BASIS OF DESIGN: BODINE BSL17 SERIES. COORDINATE WITH MANUFACTURER TO ENSURE
MAKE AND MODEL NUMBER IS CURRENT AND REMAINS APPLICABLE TO APPLICATION.
M O NTAN
A
No.71878PE
PR
O
F
E
S
S ION A L E N G INEE
R
LICE N S E D
MIKI IKEMOTO
BACKUS
Com-Check Info:
9.4.1.1 -Automatic controls to shut off all building lighting installed:
Occupancy sensors are installed in all areas.
9.4.1.2 -Indepent lighting controls installed per approved lighting plans and all manual controls are readily accessible and visible to occupants.
9.4.1.3 -Parking garage lighting is equipped with required lighting controls and daylight transition zone lighting.
Not applicable.
9.4.1.4 -Primary sidelighted areas >=250 ft2 are equipped with required lighting controls.
Not applicable.
9.4.1.5 -Enclosed spaces with daylight area under skylights and rooftop monitors >900 ft2 are equipped with required lighting.
Not applicable.
9.4.1.6 -Separate lighting control devices for specific uses installed per approved lighting plans.
Occupancy sensors, photocells, and digital controls are to be used for specific uses as shown.
9.4.1.7 -Automatic lighting controls for exterior lighting installed.
Exterior lighting shall be controlled via photocell as indicated on drawings and in lighting fixture schedule Catalog #.
9.4.3 -Exterior grounds lighting over 100 W provides >60 lm/W unless on motion sensor of fixture is exempt from scope of code or from
external LPD.
Not exterior lighting fixtures are >60 lm/W. Code article is not applicable.
9.7 -Plans, specificiations, and/or calculations provide all information with which compliance can be determined for the exterior
lighting and electrical systems and equipment and documant where exceptions to the standard are claimed. Information provided should
include interior lighting power calculations, wattage of bulbs and ballasts, transformers, and control devices.
Exterior Lighting:
Tradable Wattage 120W
Main door/Back Door -Allowed 120W
WP2 LED fixture -2 fixture @ 24W = 48W
Total Proposed Wattage = 48W
COMPLIES WITH ENERGY REQUIREMENTS.
4.2.2,9.4.4,9.7 -Plans, specificiations, and/or calculations provide all information with which compliance can be determined for the interior
lighting and electrical systems and equipment and documant where exceptions to the standard are claimed. Information provided should
include interior lighting power calculations, wattage of bulbs and ballasts, transformers, and control devices.
See lighting fixture schedule, occupancy sensor schedule and electrical sheets for device and fixture information.
Interior Lighting:
Warehouse (~1610 sq ft)
Allowed Wattage -1063
L1/E LED fixture -10 fixtures @ 35W = 350W
W1 LED fixture -1 fixture @ 17W = 17W
LB1 LED low bay fixture -8 fixtures @ 86W = 688W
Total Proposed Wattage = 1055W
COMPLIES WITH ENERGY REQUIREMENTS.
8.7.1 -Furnished asbuilt drawings for electric power systems within 30 days of system acceptance.
Contractor shall furnish asbuilts drawings for electric power systems within 30 days of system acceptance as required by code.
8.7.2 -Furnished O&M instructions for systems and equipment to the building owner or designated representative.
Contractor shall provide programming instructions associated with digital lighting controls as required by code.
9.4.2 -Exit signs do not exceed 5 watts per face.
Basis of design Exit sign is rated for 5W. Any lighting substitutions for Exit signs shall be <=5W.
9.6.2 -Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and
separated from general lighting.
All lighting controls are automatically controlled and are separate from general lighting.